Professional Documents
Culture Documents
Final Lab HV
Final Lab HV
Final Lab HV
1
High Voltage Lab Layout
Experiment No. 1
High Voltage Lab Layout
A. General requirements of HV Lab:
1.Custom made according to the type of equipment, available space and
accessories.
2.Ground level location is preferred, and floor loading has to be considered
while designing the lab.
3.Lab should be free from dust, humidity, draught.
4.Windows should be located at ground level and should have provision for
black out so that arcing can be easily observed.
5.Control room should have good view of the lab.
6.Adequate access door should be provided to bring in the equipment and
test specimen.
7.Proper safety and warning system must be provided.
8.Lab should have adequate and proper clearance. Proper spacing should be
kept within the equipment.
9.Area around the equipment should be suitably demarked.
B. Classification of HV lab:
1.Small Lab:
• 200 to 400 kV DC
2.Medium size Lab:
• Used in the industries for routine test as well as type tests and
also for research
• Switching
• Lightning
8.DC voltage test
9.Radio interference voltage (RIV) measurement
10.High current test
D. Equipment in HV lab:
1.HV generator (Transformer)
2.Impulse Generator
3.HVDC source rectifier
4.High current generator
5.Oil testing kit
6.Power frequency testing equipment
7.Testing facilities for RIV and for partial discharge
8.Sphere gap for voltage measurement
9.Schering Bridge for dielectric testing
E. Grounding of HV lab:
There are three types of groundings:
1.Ideal Ground:
• Very Expensive
2.Single point Grounding:
• Least satisfactory
F. Design and Specification of grounding system:
1.Metal sheet is embedded in a concrete floor
2.Generally copper conductors are used
3.Grounding grid is a mesh of 1m X 1m and is connected to metal grids of
RCC construction of lab
4.Chicken mesh of 1cm X 1cm is used to reduce the electromagnetic
interference
• Output Voltage:
AC: 0 to 100 kV, 50Hz
DC: 0 to 60 kV
• Output current:
AC:50mA,50Hz
DC:20mA
2.Impulse voltage generator:
• Input:0 to 60kV
• Nominal impulse generating voltage:50 kV to 500 kV
• Capacitor:0.05 µF X 10 nos
Visual critical voltage: The potential difference at which corona just becomes
visible is called as visual critical voltage.
Vd = (2.17x103) r δ m In(D/r) kV
Where
r = radius of conductor in cm
D = spacing between the conductors in cm
δ = air density factor
δ = 3092*b/ (273+t)
m = irregularity factor for the surface of the conductor
5. EFFECTS OF CORONA:
i) Corona is accomplished by power loss
ii) A luminous glow is observed around the conductor (luminous glow).
iii) Hissing sound is produced.
iv) Ozone gas is produced.
v) Corona produces interference in communication circuit.
Empirical formula for calculating corona power loss under fair weather
condition:
Pc= (242.4 / δ) x (f+25) x (√r/D) x (Vph-Vd)2 x 10-5 kW/km/ph
Where
Vph =phase voltage in kV (rms)
Vd = Disruptive critical voltage in kV (rms)
r = radius of conductor in cm
D = spacing between the conductors in cm
f= supply frequency in Hz
δ = air density factor
δ = 3092*b / (273+t)
b = barometric pressure in cm of Hg
t= temperature in degree centigrade
Corona cage-
A corona cage in simplest arrangement consists of large which forms the outer
cage and a single thin conductor wire is string inside it. The metallic cylinder
is kept at the ground potential and the wire is connected to the High Voltage
terminal. The corona conductor and cylinder are co-axial. Normally cage
consists of three sections. A long middle section which is principal cage, with
two short guard cages at either end grounded in order to minimize edge
effects. An inspection window is provided in the middle position to the outer
cage so as to observe corona. The principal advantage of cage arrangement is
that it requires lower voltage for creating the required surface field gradient
on the conductor than in an overhead line above the ground.
8. OBSERVATIONS:
1.
2.
3.
4.
9. CONCLUSION:
Corona Cage
EXPERIMENT NO.3
When breakdown occurs in air along the surface of a solid dielectric, the term,
flashover is used instead of breakdown voltage for discharge in the
surrounding gas volume.
Under uniform fields, flashover voltage along the surface of a solid dielectric
is always considerably less than the breakdown voltage of a gap purely in air.
Presence of air layers between the dielectric and electrodes exert influence on
the values of the flashover voltage since permittivity of solid dielectric
increases field intensity a few times on account of which ionisation in air layer
arises much earlier than in the main air gap. The products of ionisation go
out from the air layer to the surface of the dielectric and promote much earlier
initiation of the discharge along the surface. Therefore, in practical,
constructions all measures are taken to ensure compact joint between the
electrodes and the solid dielectric. The electrodes are usually fixed to porcelain
insulators with the help cement which ensures good mechanical strength and
absence of any air gap. However even with compact joints of electrodes and
the dielectric, the flashover voltage along the surface remains much lower
than, for pure air gap. This is shown in fig. 3
Flashover voltage depends on the following factors:-
1) Humidity: - It is observed that flashover voltage increases somewhat in
the beginning with increase in relative humidity of air. But at a value of
relative humidity corresponding to the consideration of moisture on the
surface of the dielectric (60%- 70%) a sharp decrease of flashover
voltage takes place.
PROCEDURE:-
1. Two samples were taken, one solid plain cylinder and the other
having similar dimensions but with corrugations.
2. High voltage was applied across the cylinder
3. Flashover voltage (kV) was noted down.
OBSERVATIONS:-
EFFECT OF CORRUGATIONS:-
CONCLUSION:-
Experiment No. 4
Breakdown of Liquid Dielectric
Experiment No. 4
Breakdown of Liquid Dielectric
Aim: To study breakdown of liquid dielectric.
Theory:
Liquid dielectrics are more useful as insulating materials than solids or
gases due to some of its inherent properties. They are the mixtures of
hydrocarbons and are weakly polarised. They are 10¹ times denser than gases.
The dielectric strength of gases are ideally considered to be 10 MV/cm, but
practically it is of the order of 100 kV/cm.
A liquid dielectric should withstand breakdown voltage without danger of
sparking. It should be free from moisture, products of oxidation, any fibrous
impurity and other contaminants. The presence of water in oil affects the
electric strength of insulating oil and it decreases very sharply if fibrous
impurities are present in addition to water.
Liquid dielectrics are used mainly as impregnants in high-voltage cables and
capacitors, and for filling up of transformers, circuit breakers, etc. It also acts
as heat transfer agents in transformers, and as arc-quenching media in
circuit breakers.
For the proper operation of transformer, transformer oil is tested in HV
laboratory using oil testing kit. Its ideal breakdown strength is 15 kV/mm.
The procedure for testing of oil in HV laboratory is given below.
Procedure:
1. The test cell (oil cup) is to be cleaned and dried.
2. Fill the test vessel with the dielectric oil sample to be tested, avoiding
bubble formation.
3. Set the gap between the electrodes as 2.5 mm and immerse the
electrodes in oil vessel. Place this assembly in the oil testing kit.
4. Switch on the supply from mains.
5. On the panel of the Oil Testing Kit, set maximum voltage value.(e.g.
Set the value as 70 kV).
6. Select option for breakdown test.
7. The voltage will increase gradually in steps till breakdown of oil in the
gap occurs.
8. Note down the reading for breakdown voltage, which is available on
the digital meter.
9. Take 6 readings and discard the first one (as per IS). Take average of
remaining 5 readings as breakdown voltage of oil.
10. Calculate the breakdown strength in kV/mm.
Observation Table:
Diagram:
EXPERIMENT NO. 5
Break down in Various Gap Configurations
EXPERIMENT NO. 5
Break down in Various Gap Configurations
Procedure:
1. Make arrangements to measure breakdown voltage by using various
electrode configurations.
2. Take anyone electrode configuration e.g. sphere-sphere . Adjust the
distance between the electrodes to a certain value.
3. Apply voltage till gap between two electrodes breaks down.
Theory: Liquid are use in high voltage equipment’s to serve a dual purpose of
insulation and heat dissipation. They have the advantage that a puncture
path is self-healing. Temporary failure due to overvoltage’s is reinsulated
quickly by liquid flow to the affected area. Highly purified liquids have
dielectric strength as high as 1MV/cm. Under actual service condition the
breakdown strength reduces considerably due to presence of impurities.
A liquid dielectric should withstand breakdown voltage without damage
or sparkling. The dielectric strength is measured in 1KV/mm. The breakdown
test is carried out with the help of standard test cell with polished spherical
or hemispherical electrodes separated by an oil gap.
Vb =A x dn
Where d=gap length
A = constant
N= constant(n<1)
Procedure :-
Internal connection diagram is shown in Fig. A. Testing kit is supplied by
1phase,230V,50Hz supply. In this testing kit there is facility of automatic
discharge of electrodes. To carry out the experiment, the procedure to be
followed is as given below
1. The test cell(oil cup) is cleaned, dried and oil is poured to a certain level
in the cell, avoiding bubble formation.
2. Set the distance between electrode gap as 1mm.
3. Check that the door of testing kit is closed properly, and then switch of
the power supply.
4. Set the maximum test voltage at 70kV.
5. Click on new select and select 70kV as maximum test voltage.
6. Click on the start button. This will automatically gradually increase
voltage across the electrodes from 0kV.
7. Observe the test cell. As soon as the oil breaks down, trip signal is
initiated and the voltage at which this breakdown occurs is recorded as
breakdown voltage for that oil gap length.
8. Now set various gap distances. And repeat procedure from step3.
Observation Table:-
Sr.No Gap Break Break Break Break Break Avg- Break
Length Down Down Down Down Down Break Down
(mm) Voltage Voltage Voltage Voltage Voltag Down Strength
e
(kV) (kV) (kV) (kV) Voltag (kV/mm)
(kV) e
I II III IV
V (kV)
1
Conclusion:
EXPERIMENT NO 7
Sphere gap Voltmeter
Key
1. Insulating support
2. Sphere bank
3. Operating gear, showing maximum dimensions
4. High-voltage connection with serios resistor
P Sparting point of high-voltage sphere
A Height of P above earth plane
B Radius of space free from external structuras
X ltem 4 not to pass through this plane within a distance B from P
NOTE: The figure is drawn to scale for a 25 cm sphero-gap at radius spacing.
Figure 2 - Horizontal sphero-gap
Key
1. Insulating support
2. Sphero shank
3. Operating gear, showing maximum dimensions
4. High-voltage connection with series resistor
5. Stress distributor, showing maximum dimensions
P Sparking point of high-voltage sphere
A Height of P Above earth plane
B Radius of space free from external structures
X Item 4 not to pass through this plane within a distance B from P
NOTE: The figure is drawn to scale for a 100 cm sphero-gap at radius spacing.
Figure 1 - Vertical Sphere-gap
EXPERIMENT NO. 7
To measure the High voltage using sphere gap voltmeter
Title: To measure High voltage using sphere gap voltmeter.
Aim: To study the use of sphere-gap arrangement as a voltmeter.
Equipment’s: High voltage source 11 ph Transformer 230/100 kV, 50 Hz).
sphere-gap arrangement with control panel
Theory: The breakdown voltage at spark between two metal parts may be
used as measure of voltage highest encountered value in HV testing.
Configuration of two spheres is a classical example of weakly non uniform
field. The degree of non-uniformity increases with increase in distance
between conductor diameters D. Sphere gap happens to be the commonly
acknowledged means in international practice for measuring direct,
alternating and pulsating/impulse voltage.
Out of all gaps having weak non uniform field, sphere gap can be
manufactured most easily
The methods of mounting spheres are:
1. Horizontal arrangement.
2. Vertical arrangement.
Horizontal arrangement:
Since the voltage to be measured is applied between HV terminal and earth
between High voltage terminal and sphere Supports are mounted on
arrangement. At same time, in order to avoid earth effects: the set is mounted
on higher level: it again increases size of insulators
Vertical arrangement:
This arrangement is very suitable for measuring high voltages. We can
increase the gap by simply moving HV sphere. The height of lab is to be very
large i.e. approximately 15 m.
Calibration table is to be completed on basis of spheres and different sizes of
spheres and different gap length at specified condition of temperature
pressure. (760 mm of Hg. 20° C.)
Advantages of sphere gap voltmeter:
1. It may be conveniently used for calibration of measuring devices for HV
testing
2. This method is simple and can be used for voltages in range of 1kV to
2,500 KV.
3. Sphere gap is also used for voltage measurement in surge test
4. It provides cheap, simple and reliable method
Precaution:
1. ultra violet insolation in the gap decreases the spark over voltage and
therefore ultraviolet or ionizing radiations should be avoided.
2. Clearance as per is as shown in fig. should be maintained.
3. In order to avoid pitting of sphere a current limiting resistance of
1n/volt may be used.
4. After testing, spheres should be properly cleaned and maintained.
5. No body having conducting surface should be present near to sparking
point of high voltage sphere at a distance of (0.25V + V/300) m.
6. Time interval between consecutive flashover should be large enough to
avoid heating of spheres.
Factors affecting the spark voltage of sphere gap:
Various factors that affect the spark over voltage of sphere gap are.
a) Atmospheric Conditions
b) Nearby earthing objects
c) Polarity & rise time
A) Effects of atmospheric conditions:
I. Air density:
The spark over voltage for sphere gap depends upon air density which varies
in change in temperature and pressure. If spark over is under test condition
of temp T, pressure P Torr: if spark over voltage is Vy under standard
condition of temperature & pressure.
T-20C, P=760 mm of Hg
Then V = Vok
Since k=const.
Table 2 – Peak values of disruptive discharge voltages(U50 values in impulse
tests) in kV for alternating voltages at power frequencies, full lighting and
switching Impulse volatages of negative polarity and direct voltages of both
polarities
Experiment No:8
Breakdown of Solid Dielectrics
Experiment No:8
Breakdown of Solid Dielectrics
Aim: To study breakdown of various Solid Dielectrics.
Equipment: HV Testing Equipments, High Voltage Transformer, Sheets of
different Solid dielectric material.
Theory: Solid insulators are insulators forming barriers to the flow of charge
between various parts of apparatus when high voltage is applied across them.
Requirements of a good dielectric are:
1. They should have high resistivity to reduce leakage current. They must
withstand high voltage without breakdown, i.e., high dielectric strength
2. Their density must be low as they are used on volume basis and not on
weight basis. 3. High thermal conductivity is essential
4. Low co-efficient of thermal expansion to avoid stresses and structural
damages.
5. They must be chemically inactive
There is a wide range of synthetically produced as well as natural
dielectrics. Insulator choice depends upon thermal, mechanical, chemical and
electrical properties. Classification of Solid insulating materials is made as
follows:
a) Naturally occurring: Carbon, varnish, rubber, marble, mica, asbestos, etc.
b) Fibrous nature: Wood, paper, cardboard, cloth, etc. c) Synthetic materials:
Plastic, polythene, polystyrene, ceramic, etc.
d) Solid dielectrics: Bituminous, waxes, resins, thermoplastics, thermostats,
etc.
Breakdown of Solid dielectrics
In practice, breakdown of solid insulating material occurs due to prolonged
processes. This can be due to:
1. Partial discharge
2. Tracking on the surface
3. Chemical and Electrochemical deterioration
i) Oxidation
ii) Hydrolysis in the presence of moisture
iii) Chemical action in the presence of oxygen moisture, ozone etc., resulting
in degradation of the insulation
4. Intrinsic breakdown:
When voltages are applied only for short durations of the order of 10-8 s the
dielectric strength of a solid dielectric increases very rapidly to an upper limit
called the intrinsic electric strength. Based on this principle, two types of
intrinsic breakdown mechanisms have been proposed.
1. Electronic Breakdown
2. Avalanche or Streamer Breakdown
5. Electronic Breakdown:
When solid dielectrics are subjected to high electric fields, failure occurs due
to electrostatic compressive forces which can exceed the mechanical
compressive strength
6. Thermal Breakdown:
When an electric field is applied to a dielectric, conduction current, however
small it may be, flows through the material. If the heat generated exceed the
heat dissipated breakdown occurs. Thermal breakdown sets up an upper limit
for increasing the breakdown voltage when the thickness of insulation is
increased.
Procedure:
Different solid dielectric in the form of the thin sheets were tested in the
laboratory for their breakdown strength and results are tabulated in the
observation table.
Observation table:
Sr. Types Thickness Breakdown Voltage rms(kV) Breakdown
No. of strength(kV/mm)
(mm)
paper
I II III Avg
1.
2.
3.
4.
Conclusion:
Breakdown test on solid dielectric:
Experiment No: 9
Breakdown of composite dielectri
Experiment No: 9
Breakdown of composite dielectrics
Aim: To find dielectric strength of composite dielectrics.
Theory: In insulating system more than one insulating material is used. The
different materials can be used in parallel with each other; such insulation
systems are called as composite dielectric. Such composite dielectric is used in
low and high voltage appliances such as cables, capacitors, transformers, oil
filled switchgear, bushing, etc.
Properties of composite dielectrics
If electric field is very high, failure may occur in seconds or even faster without
any substantial damage to insulating surface prior to breakdown. The
breakdown results from one or discharges, when applied voltage is high.
Breakdown was observed to occur more readily when breakdown particles are
electrons rather than positive ions. Variation in thickness of solid insulation
affects breakdown voltage.
Procedure
2.
3.
Calculations:
Conclusion:
EXPERIMENT NO. 10
Testing of Cables
EXPERIMENT NO. 10
Testing of Cables
11.1.3 after
'18.1.3 The following shall constitute additional type tests
for cables with
improved performance as per the categories given in
Appendix A:
( Reaffirmed 2001 )