PYRO-SHIELD DESIGN CALCULATION WORKSHEET

200 BAR SYSTEMS ONLY ver 2.2

DATE: 11/11/2022
QUOTE/JOB NUMBER:
JOB DESCRIPTION:
CUSTOMER: CUSTOMER REF:
CUSTOMER CONTACT: FAX: EMAIL:
DESIGN ENGINEER: FAX: 166918102 EMAIL:

SYSTEM HAZARD NAME:

VOLUME CALCULATIONS: AREA 1 AREA 2 AREA 3 AREA 4 AREA 5 AREA 6


Area Name:
Length (m): 9.00 4.80 2.75 0.00
Width (m): 10.00 6.03 6.03 0.00
Height (m): 5.70 3.80 3.80 0.00

Area (m2): 90.00 28.94 16.58 0.00 0.00 0.00


Volume (m3): 513.00 109.99 63.01 0.00 0.00 0.00

Volume Reductions:
Structural Reductions (m3): 0.00 0.00
Reduced Volume(m3): 513.00 109.99 63.01 0.00 0.00 0.00
(Volume - Structural Reductions)

Movable Object Reductions (m3): 0.00 0.00


(Fixed Inpenetrable Objects Located in the Risk Rolume)

Total Reduced Volume (m3): 513.00 109.99 63.01 0.00 0.00 0.00
(Reduced Volume - Movable Object Reductions)

ROOM MINIMUM AMBIENT TEMP.: 18 18 18 0 0 0


DESIGN CONCENTRATION: 38.5% 38.5% 38.5% 0.0% 0.0% 0.0%
FLOODING FACTOR: 0.492 0.492 0.492 0.000 0.000 0.000
(From Formula or Table)

INITIAL PYROSHIELD QUANTITY CALC.:


PYROSHIELD Quantity (Kg): 358.61 76.89 44.05 0.00 0.00 0.00
(Total Reduced Volume x Flooding factor)/(Specific Volume at Minimum Temperature)

ALTITUDE CORRECTION:
Height Above or Below Sea Level (m): 0
Factor: 1.00
(From Design Manual Table)

ACTUAL PYROSHIELD QTY (Kg): 358.61 76.89 44.05 0.00 0.00 0.00
(Initial PyroShield Quantity x Altitude Correction Factor)

TOTAL PYROSHIELD QTY (Kg): 479.54


(Sum of all Actual PYROSHIELD qty's)
TOTAL PYROSHIELD QTY (Kg): 479.54
(From Page 1)

CYLINDER REQUIREMENTS: TOTAL CYLINDER CAPACITY (Kg):


(Total PYROSHIELD qty. ÷ Cylinder Capacity rounded to next highest whole number) (Cyl. qty. x Cyl. cap.)

80 ltr Cylinders: 21 480.69

CYLINDER SIZE SELECTED: 80


PYROSHIELD AGENT SUPPLIED (Kg): 480.69
(Cylinder qty. x Cylinder capacity)
AREA 1 AREA 2 AREA 3 AREA 4 AREA 5 AREA 6
UAL PYROSHIELD AGENT PER AREA (Kg): 359.47 77.07 44.15 0.00 0.00 0.00
PyroShield Qty.) x PYROSHIELD Agent Supplied)

ACTUAL PYROSHIELD FLOODING FACTOR: 0.493 0.493 0.493 0.000 0.000 0.000
[(Actual PYROSHIELD Agent per Area ÷ Alt. Correction Factor) ÷ Total Reduced Volume ÷ Specific Volume at Minimum Design Temperature]

CONCENTRATION RANGE CHECK:


Must be Below 52% For Occupied Spaces)

Room Max. Ambient Temp.: 28 28 28 0 0 0


Design Concentration at Max. Temp: 40.6% 40.6% 40.6% 0.0% 0.0% 0.0%
x. Temp. on Table, or Use Calc. in Standard)
0
DISCHARGE TIME:
Normal Ambient Temperature: 22 22 22 0 0 0
Design Concentration at Ambient Temp.: 39.0% 39.0% 39.0% 0.0% 0.0% 0.0%
x. Temp. on Table, or Use Calc. in Standard)
95% of Design Quantity Discharge Time (Sec.): 60.0 60.0 60.0 0.0 0.0 0.0
(60 Seconds)

95% of Design Quantity Discharge Time (Min): 1.00 1.00 1.00 0.00 0.00 0.00
(Discharge Time (Sec.) ÷ 60)

ESTIMATED FLOW RATES:


Estimated System Flow Rate (Kg/min): 456
[(PYROSHIELD Design Quantity x .95) ÷ 95% Discharge Time (Min.)]

Estimated Main Feed Pipe Size: 2


(Refer to Pipe Sizing Chart)

Nozzle Quantity: 4 1 1 1 0 0
÷ 10 (Rounded to Next Highest Whole Number)
÷ 10 (Rounded to Next Highest Whole Number)]

Estimated Nozzle Flow Rate (Kg/min): 85.2 73.0 41.8 #DIV/0! 0.0 0.0
[((PyroShield Design Quantity Per Area x .95) ÷ 90% Discharge Time (min.)) ÷ Nozzle Quantity)

Estimated Nozzle Pipe Size:


Pipe Size: 1 1 0.75
(Refer to Pipe Sizing Chart)

STIMATED % OXYGEN AFTER DISCHARGE:


At Maximum Temperature: 12.4 12.4 12.4
At Nominal Temperature: 12.8 12.8 12.8

SPECIFIC GAS QUANTITY:


Total PYROSHILD design Quantity (Kg): 358.6 76.9 44.0
Specific gas quantity per area (Kg/m3): 0.69904 0.69904 0.69904
DATE: 11/11/2022
QUOTE/JOB NUMBER: 12/30/1899

CUSTOMER: #REF!

AREA 7 AREA 8 AREA 9 AREA 10 AREA 11 AREA 12

0.00 0.00 0.00 0.00 0.00 0.00


0.00 0.00 0.00 0.00 0.00 0.00

0.00 0.00 0.00 0.00 0.00 0.00

0.00 0.00 0.00 0.00 0.00 0.00

0 0 0 0 0 0
0.0% 0.0% 0.0% 0.0% 0.0% 0.0%
0.000 0.000 0.000 0.000 0.000 0.000

0.00 0.00 0.00 0.00 0.00 0.00

0.00 0.00 0.00 0.00 0.00 0.00


DATE: 11/11/2022

AREA 7 AREA 8 AREA 9 AREA 10 AREA 11 AREA 12


0.00 0.00 0.00 0.00 0.00 0.00

0.000 0.000 0.000 0.000 0.000 0.000

0 0 0 0 0 0
0.0% 0.0% 0.0% 0.0% 0.0% 0.0%

0 0 0 0 0 0
0.0% 0.0% 0.0% 0.0% 0.0% 0.0%

0.0 0.0 0.0 0.0 0.0 0.0

0.00 0.00 0.00 0.00 0.00 0.00

0 0 0 0 0 0

0.0 0.0 0.0 0.0 0.0 0.0


PRESSURE VENTING CALCULATION:

DATE: 11/11/2022
QUOTE/JOB NUMBER: 12/30/1899
CUSTOMER: #REF!
Allowable Enclosure Strength AREA 1: Nozzle Qty. (Length): 1

Nozzle Qty. (Width): 2


Light Building Construction: 25 lb./sq. ft.
Normal Building Construction: 50 lb./sq. ft. AREA 2: Nozzle Qty. (Length): 1

Vault Building Construction: 100 lb./sq. ft. Nozzle Qty. (Width): 1

AREA 3: Nozzle Qty. (Length): 1


Nozzle Qty. (Width): 1

AREA 4: Nozzle Qty. (Length): 0


Nozzle Qty. (Width): 0
AREA 1 AREA 2 AREA 3 AREA 4 AREA 5 AREA 6
Allowable Enclosure Strength (PSI): 0 0 AREA 5: Nozzle Qty. (Length): 0
Multiplier for Tight Enclosures: 1 1 1 1 1 1 Nozzle Qty. (Width): 0
Venting (m3): 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
[(0.0855 x Estimated Area Flow Rate) ÷ Square Root of Allowable Enclosure Strength] AREA 6: Nozzle Qty. (Length): 0
Nozzle Qty. (Width): 0

AREA 7 AREA 8 AREA 9 AREA 10 AREA 11 AREA 12 AREA 7: Nozzle Qty. (Length): 0
Allowable Enclosure Strength (PSI): Nozzle Qty. (Width): 0
Multiplier for Tight Enclosures: 1 1 1 1 1 1
Venting (sq. in.): 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 AREA 8: Nozzle Qty. (Length): 0
[(0.0855 x Estimated Area Flow Rate) ÷ Square Root of Allowable Enclosure Strength] Nozzle Qty. (Width): 0

AREA 9: Nozzle Qty. (Length): 0


Nozzle Qty. (Width): 0

AREA 10: Nozzle Qty. (Length): 0


Nozzle Qty. (Width): 0

AREA 11: Nozzle Qty. (Length): 0


Nozzle Qty. (Width): 0

AREA 12: Nozzle Qty. (Length): 0


Nozzle Qty. (Width): 0
PIPE SIZE EST. CHART
NOZZLE - SHORT
PIPE SIZE EST. CHART 20 0.5
ORIFICE UNION 35 0.75
20 0.5 65 1
35 0.75 125 1.25
65 1 170 1.5
125 1.25 310 ADD NOZZLES
170 1.5
310 2
570 2.5
1000 3
3000LARGER THAN 3"
5000LARGER THAN 4"
ESTIMATED OVER-PRESSURISATION VENTING:

HAZARD NAME: STRUCTURAL STRENGTH


HAZARD AREA 1: 0.00 1
HAZARD AREA 2: 0.00 1
HAZARD AREA 3: 0.00 1
HAZARD AREA 4: 0.00
HAZARD AREA 5: 0.00
HAZARD AREA 6: 0.00
HAZARD AREA 7: 0.00
HAZARD AREA 8: 0.00
HAZARD AREA 9: 0.00
HAZARD AREA 10: 0.00
HAZARD AREA 11: 0.00
HAZARD AREA 12: 0.00
TOTAL VENTING AREA REQUIRED (m2):

KEY:
STRUCTURE STRUCTURE CODE
STRUCTURAL STRENGTH (mmBar)
PARTITIONED WALL 1 2.5
BRICK WALL 2 5
VAULT 3 10
VOIDS 4 1
NO. OF CYLINDERS VENTING AREA (m2)
15.67 0.5640 x 1.5 = actualy venting area
3.36 0.1209 x 1.5 = actualy venting area
1.92 0.0693 x 1.5 = actualy venting area
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
ING AREA REQUIRED (m2): 0.7542
PROJECT : Bank Sul Sel Bar
SUBJECT : PRECISION AIR CONDITIONING
DATE : 2 Mei 2012
PREPARED BY : PT. DAYA PERKASA ABADI

NO ACTIVITY VOLUME

PAC
Presicion Air Conditioning
PXD 60 A
Air flow 12.600 m3/s
Total Capacity 58.00 kW / 197.896 Btu/h
Sensible Capacity 49.61 kW / 169.269 Btu/h
Electric Reheat capacity 12 KW
Dimensi D 885 x W 1800 x H 1954 mm
Weight 682 Kgs
Refrigerant R-407C
Power 380 Volt, 3 Phase, 50 Hz

1 PAC PXD 60 A 2 Unit

2 Material Installation 1 Lot

3 Installation Fee + Testing & Commisioning 1 Lot

Note : Instalasi Piping Outdoor ke Indoor = ± 30 Meter

Model
PXD 60 A
Humidifier
Water Detection Kit
SNMP Card
CACR

Model
PXD 60 A
Optional Items
Humidifier
Water Detection Kit
SNMP Card
Wooden Crate
Standard Air Cooled Condensers
CACR 326+326
Wooden Crate