Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

M LEGENDS

GENERAL ELECTRICAL NOTES LED CEILING DOWN LIGHT

1. ALL ELECTRICAL INSTALLATION SHALL BE DONE IN LED TRACK LIGHT


ACCORDANCE WITH THESE PLANS AND SPECIFICATIONS. THE
APPLICABLE PROVISION OF LATEST EDITION OF THE PHILIPPINE LED LIGHTING STRIPS
ELECTRICAL CODE, THE NATIONAL BUILDING CODE, THE
CITY/MUNICIPAL ELECTRICIANS, AND THE NATIONAL POWER LED PENDANT LIGHT
CODE.
15 15
1 2 POWER BREAKER
2. TYPE OF ELECTRICAL VOLTAGE SHALL BE 230V, 1 PHASE, 2 15 15
WIRE, 60Hz. 3 4 ELECTRIC CIRCUIT WIRE
15 15
3. METHOD OF WIRING SHALL BE IN PVC FOR BOTH EXPOSED 5 6 LIGHTING SWITCH CIRCUIT
AND EMBEDED WORK WITH PROPER FITTINGS AND SUPPORTS, 15 15
SERVICE ENTRANCE CONDUIT SHALL BE IN RIGID STEEL (RSC). 7 8
20 20 S2 SWITCH 2-GANG
4. ALL WALL OUTLETS SHALL BE INSTALLED AT THE 9 10
30 S3 SWITCH 3-GANG
FOLLOWING HEIGHT ABOVE FINISHED FLOOR LEVEL UNLESS
OTHERWISE SPECIFIED.
11
DUPLEX COVENIENCE OUTLET
A. WALL SWITCHES
1.40mts. ACU AIRCONDITIONING OUTLET
B. WALL OUTLETS
0.30mts. FLOOR OUTLET
C. PANEL BOARD
1.60mts.

D. A.C.U. OUTLETS
1.60mts. 1 DETAIL OF PANEL
A-2 SCALE: NTS

5. ALL MATERIALS AND EQUIPMENT SHALL BE BRAND NEW


AND APPROVE TYPE FOR BOTH LOCATION AND PURPOSE
INTENDED.
PANEL BOARD: 70 AT, 2 POLE, 230 V (BOLT ON)
6. ALL LIGHTINGS AND CONVENIENCE RECEPTACLE CIRCUIT NO. OF LOAD CKT SIZE
LOAD
HOMERUNS SHALL BE WIRED NOT LESS THAN 3.50sq.mm. CKT
DESCRIPTION
VOLTS WATTS (amp) PROTECTION POLE
COPPER INDICATORS UNLESS OTHERWISE INDICATED IN THE CO LIGHTS WIRE CONDUIT
PLAN.
1 DOWNLIGHTS (LED)9W 2 20 2 2-3.5mm 2 THHN + 1-3.5mm 2 Ø 20mm PVC
7. ALL LIGHTINGS AND PANEL BOARDS SHALL BE IN CIRCUIT DOWNLIGHTS (LED)8W 11 20 2 2-3.5mm 2 THHN + 1-3.5mm 2 Ø 20mm PVC
BREAKER TYPE, FLUSH MOUNTED OR AS INDICATED IN THE
PLANS. PENDANT LIGHTS (LED)3W 5 20 2 2-3.5mm 2 THHN + 1-3.5mm 2 Ø 20mm PVC
230 733 3.19
8. ALL OUTDOOR INSTALLATION SHALL BE WEATHERPROOF.
SPOT LIGHTS (LED)6W 3 20 2 2-3.5mm 2 THHN + 1-3.5mm 2 Ø 20mm PVC
SPOT LIGHTS (LED)3W 9 20 2 2-3.5mm 2 THHN + 1-3.5mm 2 Ø 20mm PVC
9. UNLESS OTHERWISE SPECIFIED, JUNCTION BOX AND UTILITY
STRIP LIGHTS (LED)14.4W/M 5 20 2
BOX SHALL BE PROVIDED WHENEVER REQUIRED. ALTHOUGH LTOTAL = 39 M
LED = 1170
2-3.5mm 2 THHN + 1-3.5mm 2 Ø 20mm PVC
SUCH BOXES ARE NOT SHOWN IN THE PLANS.
TOTAL

2 POWER 6 20 2 2-3.5mm 2 THHN + 1-3.5mm 2 Ø 20mm PVC


230 1800 7.83
10. ALL ELECTRICAL WORKS HEREIN SHALL BE DONE UNDER 2
FLOOR MOUNTED 4 20 2-3.5mm 2 THHN + 1-3.5mm 2 Ø 20mm PVC
THE DIRECT AND IMMEDIATE SUPERVISION OF A DULY
LICENSED ELECTRICAL ENGINEER. 3 ACU 1 230 1440 6.26 30 2 2-3.5mm 2 THHN + 1-3.5mm 2 Ø 20mm PVC
4 SPARE 230 4.35 20 2 2-3.5mm 2 THHN + 1-3.5mm 2 Ø 20mm PVC
TOTAL: 21.63

COMPUTATION: [21.63 + 0.25(8)] x 80% D.F = 18.90 AMP


USE 2 - 14 mm 2 THHN + 1 - 5.5mm 2 IN Ø 25mm IMC (18.90 A/ 70A)
NAME AND SECTION:

MORIDO, JAN WESLEY C. | BS ARCH 4-2 2 LOAD SCHEDULE


INSTRUCTOR:
A-2 SCALE: NTS

ARCH. CASHMERE JOY R. ABUTAN, UAP