System Terminology

DS Agile Training Level 1


Global Systems Engineering
03/05/2012

GRID

GSE
SAM
1.1) Summary

00-System-Terminology 06-Computer Maintenance Tool

01-DS AGILE Presentation 07-DS Agile OI Overview

02- DS Agile Architecture 08-DS Agile SCE Overview

03-MiCOM C264 Hardware 09-DS Agile SMT Overview

04-MiCOM C264 HMI 10-DS Agile GTW Overview

05-MiCOM C264 Overview 11-DS Agile Management

12-Synthesis and Questionary

GSE
L1-00-System Terminology - Rev G - P 2
Summary

1) Generalities Page 4

2) Datapoint Terminology Page 9

GSE
L1-00-System Terminology - Rev G - P 3
1.1) Electric Terminology

SITE
SUBSTATION
VOLTAGE
LEVEL

BAY

MODULE
GSE
L1-00-System Terminology - Rev G - P 4
1.2) SCE Pre-view
SITE

SUBSTATION SUBSTATION

VOLTAGE VOLTAGE VOLTAGE


LEVEL 1 LEVEL 2 LEVEL N

BAY FEEDER 1 BAY TRANSFO BAY FEEDER 2

CB 1 SW 1 TR 1 SW 2
Position Position TPI
Control Control Control
GSE
L1-00-System Terminology - Rev G - P 5
1.3) Levels of Substation Control philosophy

Control Centre Level

SUBSTATION Level

Bay Level

Process Level

Primary Equipment

GSE
L1-00-System Terminology - Rev G - P 6
1.4) Electric definitions
Substation
Site Partition => Local/Remote substation
Substation Control Uniqueness
(nb=1) The Business DB (except Cascade)
Voltage Level
Association of Bus Bars for Auto Volt. Regul.
Often only one BB (nb 4-5-x)
Bay
ANSI => 1 CB with associate circuits & protections
Association of switchgears/transformers & functions
Local/Remote Bay, SBMC, Bay Control Uniqueness
Special (coupler, section, feeder, transformer)
Often Generic (more easy)
Bay belongs to only one C264
Module
Primary Electric Device, ANSI functions, Group of DP
Special (CB, disconnector, transformer, AR, Sync)
Often Generic (DPS/DPC association possible)
Data Point
Real Time information (95% electric)
At any level GSE
L1-00-System Terminology - Rev G - P 7
Summary

1) Generalities Page 4

2) Datapoint Terminology Page 9

1) Generalities

GSE
L1-00-System Terminology - Rev G - P 8
2) Datapoint Terminology
REAL TIME DATA = DATAPOINTS
IEC61850
Several KIND of DP
BINARY SPS_ST , SPC_ST
SPS Single Point Status
DPS_ST, DPC_ST
DPS Double Point Status INPUTS
INS_ST
MPS Multiple Point Status

MV, WYE_MX, DEL


MV Measurement Value MEASUR.
TPI Tap Position Indication
DM Digital Measurement &
COUNTERS BCR_ST
SCT Single CounTer
DCT Double CounTer

SPC Single Point Control OUTPUTS


DPC Double Point Control SPC_CO
SP Set Point DPC_CO,BST_CO
GSE
L1-00-System Terminology - Rev G - P 9
2.1) Supervision Datapoint Attributes
Supervision
Status/Value Quality

SPS, Reset/Set Valid / FSS / Invalid

DPS, Open(01)/Close(10) Valid / FSS / Invalid

MPS State16 Valid / FSS / Invalid

MV, TPI, DM Value (Float32) Valid / FSS / Threshold / Invalid

SCT, DCT
Common Invalid Unknown (IED), Self-Check Fault (Hard)
+DPS invalid Jammed (00) Undefined (11)
+MV, xCT invalid Open Circuit, Undefined, OverRange
FSS Force (auto/Manu) an Invalid DP
Suppress (Make DP invalid)
Substitute (Force the Status/Value of DP)
Threshold For Alarm,
L,LL,LLL, H, HH, HHH with hysteresis
GSE
L1-00-System Terminology - Rev G - P 10
2.2) Control Datapoint

SPC, DPC, SP
Kind
Direct Execute Select Before Operate
One Shot Selection / Wait(cancel) / Execute
Medium/Low Volt. HV + Control Uniqueness => order run Bay

Where Direct Execute Select Before Operate


2) Supervision
OI DE, SBO like pop-up SBO pop-up
SCADA DE DE, SBO

1) SBUS/C264 DE SBO
Select Open/Close
Execute Open/Close
3) Hardware/IED DE SBO

GSE
L1-00-System Terminology - Rev G - P 11
2.3) Controls
Station
Operator Right / Gateway channel in control
Remote/Local Station
Device operating mode (operational, not stand-by…)
Control Uniqueness Station (GOOSE)
Topological ILK
Bay
Control Uniqueness Bay (order running)
Remote/Local Bay

Module (switch, transformer..)


Current Module State/Value

Bay interlock open/close (including module specific conditions)


Locking
Auto/Manu Dependency (automation running)
Recuperation Time

Inner Simple “Built-in” Automation


Output / feedback input Delays….
Physical SBO, Direct Execute, 3 phases, Communication IED GSE
L1-00-System Terminology - Rev G - P 12