04MSC7PO

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

3URGXFW2YHUYLHZ

*
6
0
06&53URGXFW2YHUYLHZ

3UHGHILQHG6HWWLQJV
System: GSM 900/1800
Release: R7
Hardware: BYB501
Transmission: E1 (32 channels)

)XQFWLRQDOLW\
Included functionality: MSC/VLR
Supported additional functionality: MSC/VLR/HLR
MSC/VLR/HLR/AUC
MSC/VLR/SSF
MSC/VLR/PRA
MSC/VLR/SSF/PRA

3URGXFW5DQJH

&KDUDFWHULVWLFV 06& 06& 06& 06& 06& 06& 06& 06& 06& 06&
Traffic capacity
on the A-interface 300 450 950 1450 1950 2450 2950 3450 3950 4450
(Erlang) 1
Dimensioned no
of subscribers 2 12 000 18 000 38 000 58 000 78 000 98 000 118 000 138 000 158 000 178 000
Max number of
subscribers 3 30.000 45.000 95.000 145.000 195.000 245.000 295.000 345.000 395.000 445.000

Number of SLs4 40 64 64 64 64 64 64 64 64 64
Number of CSR-
D devices (R2) 96 128 256 384 512 640 768 896 1024 1152

Number of E1 42 56 98 140 182 224 266 308 350 392


Total power
consumption (W) 1040 2757 3013 3269 3525 3781 4138 4394 4791 5047
Number of
cabinets 3 5+2 6+2 7+2 8+2 9+2 10+2 11+2 13+2 14+2
(BYB501+202)
Cabinet foot print
(m2) 5 0.7 2.0 2.3 2.5 2.7 3.0 3.2 3.5 3.9 4.2
Required floor
area 6(m2) 2.2 4.9 5.6 6.3 7.1 7.8 8.5 9.2 10.7 11.4

1
Only valid for MSC/VLR and when standard traffic values are used as defined by Ericsson
2
Valid when standard traffic values are used as defined by Ericsson, 25mE/subscriber assumed
3
Valid when standard traffic values are used as defined by Ericsson except for traffic per subscriber which is set
to 10 mE/subscriber
4
Figure based on total number of RPG2
5
Footprint includes footprint of AXE HW cabinets only, no power or maintenance space included
6
Including maintenance space 0.8 m from cabinets

LK/XX-97:161 Rev B 1998-02-18 1(2)


3URGXFW2YHUYLHZ

)XQFWLRQDO6HWWLQJVDQG2SWLRQV
&KDUDFWHULVWLFV 'HIDXOW 2SWLRQV $GGLWLRQDO+: 2SWLRQLPSDFW
3ULFH 7LPH
MSC/VLR core HLR functionality
Node functionality functionality in steps of 25.000 no yes no
subscribers
AUC functionality
in steps of 25.000 no yes no
subscribers

SSF SSF cabinet yes no

PRA PRA cabinet yes no

VMS support yes no

SMS support yes no

6LWH6HWWLQJVDQG2SWLRQV
3URSHUWLHV2SWLRQV 'HIDXOW 2SWLRQ 2SWLRQLPSDFW
3ULFH 7LPH

Cabling overhead under floor no no


Ericsson raised
Raised floor no floor7 yes yes

DDF no yes yes no

ETC-DDF max cabling distance < 30 m > 30 yes no

Power cable length 15 m 25 yes no

Power common with other node no Yes no Yes

IOG-PC terminal cable length 15 m 15 m– 5 km8 yes No

Floor plan standard 9 customised yes Yes

Extra cable chutes no 10-50 m yes no

Inverters (Power supply for terminals)) no yes yes no

5HODWHG3URGXFWV QRWLQFOXGHGLQ06& 5HODWHG6HUYLFHV QRWLQFOXGHGLQ06&


PC terminals and printers HW repair agreements
PC terminals software (WinFiol, Dynatext) SW support
Spare part kits Implementation services
Power and back up system
Cooling
Basic and Optional SW
Test equipment and tools
Transmission products

7
Raised floor is a product package of its own
8
Requires short range modems, to be defined
9
There are three types of standard floor plans, see separate description

LK/XX-97:161 Rev B 1998-02-18 2(2)