Boundary Wall Drawing
Boundary Wall Drawing
Boundary Wall Drawing
"A"
1. All dimensions are in mm unless otherwise specified.
40MMx40mmx5mm 12x14x swg 4no. BW
MS HDG Angle 2. Clear cover for slab 25mm
(IS 278-2009 Heavy coted
Minimum 80 micron 3. Grade of concrete: For Precast/Prestressed wall panel
A 230/240 gsm Zinc on wire
slab & column M-30, For Footing M-20
4. ISA 40x40x5 Should be Welded with 8mm Thk. Plate.
5. Additional Column Expansion joints shall be provided at
a) Every 15 No's. of column And (b) Every 300mm Change in Ground level.
450
150
M30
Column Post Concrete
2700mmx150mmx150mm
(TYP)
300
S1 DETAIL-A
1800
STRUCTURAL DETAILS
S1 LEGENDS :
1800 1800
Wall Panel TYP : TYPICAL
1800mmx300mmx50mm 1 No. Anchor bolt of 12" NGL : NATURAL GROUND LEVEL
length embeded inside
S1 150 the column
40
S2
02-11-2022
NGL NGL
150
40
50
50
70
50mm dia weep hole at equal spacing Mortar Filling in CM(1:4)
Provisions for Excess Water Flow
40
Provided as per requirement Gujarat State Electricity Corporation Limited : RE & BD Cell.
Base plate 100mmx100mm
This document has been reviewed as noted with regard to general conformity with the with 8mm thk.
contract specification and requirements. The Premier Solar Powertech Pvt. Ltd. is
DETAIL -A hot deep galvanized PURPOSE:
1000
responsible for correctness of design, calculation and details. Approval of this document
does not relieve the vendor/contractor of his responsibility in carrying out the work correctly ISA 40x40x5 hot deep
and fulfilling the complete requirement of the contract nor does it limit the GSECL’s rights
under the contract. galvanized
OUTSIDE
"C"
INSIDE
S1
25
3 NOS. OF 3MM
0
C Welding with one
45°
WIRON 50
Angle to another Angle
1800 S1
ISA 40x40x5
200
Single Angle
SLAB-M30
300
CLIENT / OWNER :
300
S1
8mm Plate with hole
for Anchor Bolt
C
DETAIL- C DETAIL- B COLUMN-M30 S1
SLAB S1 WITH PRESTRESSED TECHNOLOGY SECTION C-C
S2
NGL PROJECT :
4 NOS. OF 3MM
D WIRON
1800 50 300Ø
B B
1000
DRAWING TITLE : BLOCK :
300
Footing M-20
300
SECTION A-A
This document is the exclusive property of Premier Energies Limited. And its
ownership rests with them. its use in any form other than intended or copying,
reproducing or handing over to third party is strictly prohibited.