HV 804 W WDG 61 - Technical Data Sheet

FRAME HV 804 W
SPECIFICATIONS & OPTIONS
STANDARDS WINDINGS & ELECTRICAL PERFORMANCE

STAMFORD AC generators are designed to meet the All generator stators are wound to 2/3 pitch. This eliminates
performance requirements of IEC EN 60034-1. Other triplen (3rd, 9th, 15th …) harmonics on the voltage waveform
international standards, including BS5000, VDE 0530, and is found to be the optimum design for trouble-free supply
NEMA MG1-32, AS1359, CSA C22.2, UL and CE; as well of non-linear loads. The 2/3 pitch design avoids excessive
as a wide range of international Marine Certification neutral currents sometimes seen with higher winding pitches.
Approvals, can be met on request. For clarification A fully connected damper winding reduces oscillations during
regarding compliance please contact Cummins Generator paralleling. This winding, with the 2/3 pitch and carefully
Technologies. selected pole and tooth designs, ensures very low levels of
voltage waveform distortion.
DESCRIPTION
TERMINALS & TERMINAL BOX
The STAMFORD PI range of synchronous ac generators
are brushless with a rotating field. They are separately Standard generators feature a main stator with 6 ends
excited by the STAMFORD Permanent Magnet Generator brought out to the terminals, which are mounted on the
(PMG). This is a shaft mounted, high frequency, pilot exciter frame at the non-drive end of the generator. A sheet steel
which provides a constant supply of clean power via the terminal box contains the AVR and provides ample space for
Automatic Voltage Regulator (AVR) to the main exciter. the customers' wiring and gland arrangements. It has
The main exciter output is fed to the main rotor, through a removable panels for easy access.
full wave bridge rectifier, protected by surge suppression.
SHAFT & KEYS
VOLTAGE REGULATORS
All generator rotors are dynamically balanced to better than
The P range generators complete with a PMG are available BS6861:Part 1 Grade 2.5 for minimum vibration in operation.
with one AVR. The AVR has soft start voltage build up and Two bearing generators are balanced with a half key.
built in protection against sustained over-excitation, which
will de-excite the generator after a minimum of 8 seconds. INSULATION/IMPREGNATION
Underspeed protection (UFRO) is also provided on both
AVRs. The UFRO will reduce the generator output voltage The insulation system is class 'F'.
proportional to the speed of the generator below a pre- All wound components are impregnated with materials and
settable level. processes designed specifically to provide the high build
required for static windings and the high mechanical strength
The MA330 AVR is 3 phase rms sensed with a voltage required for rotating components.
regulation of 0.5% rms (see the note on regulation). The
UFRO circuit has adjustable slope and dwell for controlled QUALITY ASSURANCE
recovery from step loads. An over voltage protection circuit
will shutdown the output device of the AVR, it can also trip Generators are manufactured using production procedures
an optional excitation circuit breaker if required. As an having a quality assurance level to
option, short circuit current limiting is available with the BS EN ISO 9001.
addition of current transformers.
NOTE ON REGULATION
The MA330 AVR needs a generator mounted current The stated voltage regulation may not be maintained in the
transformer to provide quadrature droop characteristics for presence of certain radio transmitted signals. Any change in
load sharing during parallel operation. performance will fall within the limits of Criteria 'B' of EN
Provision is also made for the connection of the 61000-6-2:2001. At no time will the steady-state voltage
STAMFORD power factor controller, for embedded regulation exceed 2%.
applications, and a remote voltage trimmer.
NB Continuous development of our products entitles us to change
specification details without notice, therefore they must not be
regarded as binding.

Front cover drawing is typical of the product range.

2
FRAME HV 804 W
WINDING 61
RATINGS REFER TO SALES AND SERVICE BRIEFING
MAXIMUM ALTITUDE 1000 METRES ABOVE SEA LEVEL
MAXIMUM AMBIENT TEMPERATURE 40º C

CONTROL SYSTEM SERIES 3 SEPARATELY EXCITED BY P.M.G.


A.V.R. FULL WAVE RECTIFIED
VOLTAGE REGULATION ± 0.5% WITH 4% ENGINE GOVERNING
SUSTAINED SHORT CIRCUIT REFER TO SHORT CIRCUIT DECREMENT CURVES OF THIS SECTION

INSULATION SYSTEM CLASS F


PROTECTION IP23 STANDARD
RATED POWER FACTOR 0.8
STATOR WINDING DOUBLE LAYER LAP
WINDING PITCH 2/3
WINDING LEADS 6
R.F.I. SUPPRESSION BS EN 50081/2-1/2 VDE 0875G VDE 0875N For other standards apply to the factory
WAVEFORM DISTORTION NO LOAD < 1.5% NON-DISTORTING BALANCED LINEAR LOAD < 3.0%
MAXIMUM OVERSPEED 2250 Rev/Min
BEARING DRIVE END ISO 6236 C3
BEARING NON DRIVE END ISO 6324 C3
EFFICIENCY REFER TO EFFICIENCY CURVES OF THIS SECTION

FREQUENCY 50Hz
TELEPHONE INTERFERENCE THF< 2%
COOLING AIR 3.75 m3/sec
VOLTAGE STAR (Y) 6300 6600 6900
kVA BASE RATING FOR
3255 3410 3410
REACTANCE VALUES
Xd DIRECT AXIS SYNCHRONOUS 2.51 2.40 2.20
X'd DIRECT AXIS TRANSIENT 0.195 0.186 0.170
X''d DIRECT AXIS SUB-TRANSIENT 0.143 0.137 0.125
Xq QUADRATURE AXIS REACTANCE 1.77 1.690 1.55
X''q QUAD. AXIS SUB-TRANSIENT 0.272 0.260 0.238
XL LEAKAGE REACTANCE 0.100 0.095 0.087
X2 NEGATIVE PHASE SEQUENCE 0.208 0.199 0.182
X0 ZERO PHASE SEQUENCE 0.035 0.033 0.030
REACTANCES ARE SATURATED VALUES ARE PER UNIT AT RATING AND VOLTAGE INDICATED
T'd TRANSIENT TIME CONSTANT 0.223
T''d SUB-TRANSIENT TIME CONSTANT 0.016
T'do O.C. FIELD TIME CONSTANT 4.95
Ta ARMATURE TIME CONSTANT 0.085
SHORT CIRCUIT RATIO 1/Xd

STATOR WINDING RESISTANCE (L-N) 0.0888


ROTOR WINDING RESISTANCE 1.470
EXCITER STATOR FIELD RESISTANCE 17.00
EXCITER ROTOR RESISTANCE (L-L) 0.092
PMG STATOR RESISTANCE (L-L) 3.800
RESISTANCE VALUES ARE IN OHMS AT 20º C

NO LOAD EXCITATION VOLTAGE 15.0


FULL LOAD EXCITAION VOLTAGE 67.0

Continuous development of our products entitles us to change specification details without notice,
therefore they must not be regarded as binding.

3
FRAME HV 804 W WDG 61 50 Hz
THREE PHASE EFFICIENCY CURVES

6300 V
98.0

97.5
1.0

97.0
0.9

96.5 0.8

96.0
% P.F.
95.5

95.0 3255.0 kVA

94.5
0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1

3255 kVA

6600 V
98.0

97.5
1.0

97.0 0.9

96.5 0.8

96.0
% P.F.
95.5

95.0

94.5
0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1

3410 kVA

6900 V
98.0

97.5 1.0

97.0 0.9

96.5 0.8

96.0

% 95.5 P.F.
95.0

94.5

94.0
0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1

3410 kVA

4
FRAME HV 804 W WDG 61 50Hz
FULL WAVE RECTIFIED AVR
LOCKED ROTOR MOTOR STARTING CURVE
6300V 6600V 6900V
X
30.0
PER CENT TRANSIENT VOLTAGE DIP

25.0

20.0

15.0

10.0

5.0

0.0
0 1000 2000 3000 4000 5000 6000
LOCKED ROTOR kVA

FRAME HV 804 W WDG 61 50Hz

Three Phase Short Circuit Decrement Curve


No- Load Excitation at Rated Speed
Based on series star (wye) connection

x NOTE 1
10000
THE FOLLOWING MULTIPLICATION FACTORS SHOULD BE USED TO ADJUST THE VALUES

SYMMETRIC FROM CURVES BETWEEN THE 0.001 SECONDS AND THE MINIMUM CURRENT POINT IN
RESPECT OF NOMINAL OPERATING VOLTAGE

ASYMMETRICAL VOLTAGE FACTOR

6300V X 1.00
6600V X 1.05

THE SUSTAINED CURRENT VALUE IS CONSTANT IRRESPECTIVE OF VOLTAGE LEVEL


CURRENT (Amps)

1000
NOTE 2

THE FOLLOWING MULTIPLICATION FACTORS SHOULD BE USED TO CONVERT THE


VALUES CALCULATED IN ACCORDANCE WITH NOTE 1 TO THOSE APPLICABLE
TO THE VARIOUS TYPES OF SHORT CIRCUIT

3 PHASE 2 PHASE L-L 1 PHASE L-N

INSTANTANEOUS X 1.0 X 0.87 X 1.30


MINIMUM X 1.0 X 1.80 X 3.20
SUSTAINED X 1.0 X 1.50 X 2.50
MAX SUSTAINED DURATION 10 SEC 5 SEC 2 SEC
ALL OTHER TIMES ARE UNCHANGED
100
0.001 0.01 0.1 1 10
TIME (secs)
SUSTAINED SHORT CIRCUIT = 1089 Amps

5
FRAME HV 804 W
WINDING 61 0.8 Power Factor

RATINGS

Class - Temp Rise Cont. F - 105/40°C Cont. H - 125/40°C Class F Standby - 125/40°C Class F Standby - 138/27°C

50Hz Star (V) 6300 6600 6900 6300 6600 6900 6300 6600 6900 6300 6600 6900

kVA 3255 3410 3410 N/A N/A N/A 3475 3640 3640 3608 3780 3780

kW 2604 2728 2728 N/A N/A N/A 2780 2912 2912 2886 3024 3024

Efficiency (%) 96.6 96.6 96.7 N/A N/A N/A 96.5 96.5 96.6 96.5 96.5 96.6

kW Input 2697 2824 2822 N/A N/A N/A 2881 3017 3015 2992 3133 3131

60Hz Star (V) N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

kVA N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

kW N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

Efficiency (%) N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

kW Input N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

TYPICAL DIMENSIONS - Further arrangements available - please refer to factory

Barnack Road • Stamford • Lincolnshire • PE9 2NB


Tel: 00 44 (0)1780 484000 • Fax: 00 44 (0)1780 484100

© 2009 TD_HV804W.61.GB_03.09_09_GB