Reinforced Concrete D-Load Culvert, Storm Drain, and Sewer Pipe

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

M 242 SPECIFICATIONS FOR MATERIALS

Standard Specification for

Reinforced Concrete D-Load Culvert, Storm Drain, and Sewer Pipe

AASHTO DESIGNATION: M 242-94


(ASTM DESIGNATION: C 655-91)

1. SCOPE M 295 Fly Ash and Raw or Calcined 4.2 Age for Acceptance-Pipe shall be
Natural Pozzolan for Use as a considered ready for acceptance when
Mineral Admixture in Port- they conform to the requirements.
1.1 This specification covers reinforced land Cement Concrete
concrete pipe designed to specific D-
loads and intended to be used for the T 22 Compressive Strength of 5. DESIGN AND MANUFACTUR-
conveyance of sewage, industrial wastes, Cylindrical Concrete Speci- ING DATA
and storm water and for the construction mens
of culverts. T 23 Making and Curing Concrete
Compressive and Flexural 5.1 The producer shall provide the fol-
1.2 A complete metric companion to lowing information regarding the pipe
AASHTO M 242 has been developed-M Strength Test Specimens in
242M; therefore, no metric equivalents the Field unless waived by the purchaser:
are presented in this specification. T 24 Obtaining and Testing Drilled 5.1.1 Basis of acceptance,
Cores and Sawed Beams of 5.1.2 Pipe design strength.
NOTE 1-Experience has shown that the
successful performance of this product de- Concrete
5.1.3 Physical Characteristics:
pends upon the proper selection of the pipe T 280 Testing Concrete Pipe, Sec-
strength, the type of bedding and backfill, the
5.1.3.1 Diameter, wall thickness, laying
tions, or Tile
care that the installation conforms to the length, and joint details.
construction specifications, and provision for 2.2 ASTM Standard:
5.1.4 Design concrete strength, mini-
adequate inspection at the construction site. E 105 Recommended Practice for mum f c' equals 4000 psi.
This specification does not include require- Probability Sampling of Ma-
ments for bedding, backfill, the relationship 5.1.5 Admixtures.
terials
between field load conditions and the strength 5.1.6 Reinforcement:
designation of pipe, or durability under un-
usual environmental conditions. These re- 5.1.6.1 Type of reinforcement, applicable
3. TERMINOLOGY reinforcement specification, and grade.
quirements should be included in the project
specification. 5.1.6.2 Placement, placement tolerances,
3.1 Definitions-For definitions of terms diameter, spacing and cross-sectional
relating to concrete pipe, see AASHTO area of circumferential, longitudinal, and
2. REFERENCED DOCUMENTS M 262. special reinforcement.
5.1.7 Manufacturing and curing proc-
2.1 AASHTO Standards: ess.
4. BASIS OF ACCEPTANCE
M6 Fine Aggregate for Portland
Cement Concrete
4.1 The acceptability of the pipe design 6. MATERIALS AND MANUFAC-
M 31 Deformed and Plain Billet- shall be determined in accordance with TURE
Steel Bars for Concrete Rein- Section 9. After the pipe design has been
forcement accepted, or if the pipe design has been
M 32 Cold-Drawn Steel Wire for 6.1 Materials:
accepted previously in accordance with
Concrete Reinforcement Section 9, the purchaser may select and 6.1.1 Reinforced Concrete-The rein-
M 55 Welded Steel Wire Fabric for have applied the basis of acceptance forced concrete shall consist of cementi-
Concrete Reinforcement described in either Section 4.1.1 or Sec- tious materials, mineral aggregates, and
tion 4.1.2. Unless designated by the water, in which steel has been embedded
M 80 Coarse Aggregate for Port- in such a manner that the steel and con-
purchaser at the time of, or before placing
land Cement Concrete crete act together.
an order, either basis of acceptance shall
M 85 Portland Cement be permitted. 6.1.2 Cementitious Materials:
M 148 Liquid Membrane Forming 4.1.1 Acceptance on the Basis of Pipe 6.1.2.1 Cement-Cement shall conform to
Compounds for Curing Con- Load and Material Tests and Inspection the requirements for portland cement of
crete of Manufactured Pipe for Defects- AASHTO M 85 or shall be portland
M 221 Welded Deformed Steel Wire Determine in accordance with Sections 5, blast-furnace slag cement or portland-
Fabric for Concrete Rein- 6, 9, and 10. pozzolan cement conforming to the re-
forcement quirements of AASHTO M 240. except
NOTE 2-It is necessary that samples be
M 225 Deformed Steel Wire for selected at random. For guidance, see ASTM that the pozzolan constituent in the Type
Concrete Reinforcement Recommended Practice E 105. IP portland-pozzolan cement shall be fly
ash and shall not exceed 25 percent by
M 240 Blended Hydraulic Cements 4.1.2 Acceptance on the Basis of Con- weight.
M 262 Terms Relating to Concrete crete Compression and Materials Tests
6.1.2.2 Fly Ash-Fly ash shall conform to
Pipe and Related Products and Inspection of Manufactured Pipe for
the requirements of AASHTO M 295,
Defects-Determine in accordance with
Class F or Class C.
Sections 5, 6, 9, and 11.
355
M 242 SPECIFICATIONS FOR MATERIALS

6.1.2.3 Allowable Combinations of Ce- 6.2.3 Joints-The joints shall be of such TABLE 1 Standard Designated Inside Diameters,
in.
mentitious Materials-The combination of design and the ends of the concrete pipe 12 24 26 60 84 108 132
cementitious materials used in the cement sections so formed that when the sections 15 27 42 66 90 114 138
shall be one of the following: are laid together they will make a con- 18 30 48 72 96 120 144
(a) Portland cement only, tinuous line of pipe with a smooth inte- 21 33 54 78 102 126
rior free of appreciable irregularities in
(b) Portland blast-furnace slag cement 8.2 Design Tolerances-Except as speci-
the flow line, all compatible with the
only, fied in this section, all permissible design
permissible variations given in Section 8.
(c) Portland-pozzolan cement only, or tolerances shall be given in Section 5.
6.2.4 Lift Holes-When agreed upon by
(d) A combination of portland cement 8.2.1 Diameter Tolerances-The internal
the purchaser, lift eyes or holes may be
and fly ash wherein the proportion of diameter of 12 to 24-in. pipe shall vary
provided in each pipe for the purpose of
fly ash is between 5 and 25 percent not more than ± 1.5 percent from the
handling.
by weight of total cementitious mate- design diameter. The internal diameter of
rial (portland cement plus fly ash). 27 to 144-in. pipe shall vary not more
7. PHYSICAL REQUIREMENTS than ± 1 percent or ⅜ in., whichever is
6.1.3 Aggregates-Aggregates shall greater, from the design diameter.
conform to the requirements of AASHTO
M 6 and M 80, except that the require- 7.1 Strength-The design strength 8.2.2 Reinforcement Placement Toler-
ments for gradation shall not apply. designation of the pipe shall be the D- ances-The maximum variation in the
load to produce the 0.01-in. crack when nominal position of the reinforcement
6.1.4 Admixtures and Blends- shall be ± 10 percent of the wall thick-
Admixtures and blends may be used tested in accordance with AASHTO T
280. The relationship of ultimate strength ness or ± ⅝ in., whichever is greater. Pipe
unless prohibited by the purchaser. having variations in the position of the
D-load to the design strength D-load shall
6.1.5 Steel Reinforcement- be determined using a factor of 1.5 for reinforcement exceeding those specified
Reinforcement shall consist of wire design strength designations up to 2000 above shall be accepted if the three-edge
conforming to AASHTO M 32 or M 225, lbf/ft•ft of diameter, a factor varying in bearing strength requirements obtained
or of wire fabric conforming to AASHTO linear proportions from 1.5 to 1.25 for on a representative sample are met. In no
M 55 or M 221, or of bars of Grade 300 design strength designations from 2000 case, however, shall the cover over the
steel conforming to AASHTO M 31M. through 3000, and a factor of 1.25 for circumferential reinforcement be less
6.2 Manufacture: design strength designations in excess of than ⅝ in.
6.2.1 Mixture-The aggregates shall be 3000. 8.2.3 Length of Two Opposite Sides-
sized, graded, proportioned, and mixed Variations in the laying length of two
NOTE 3-As used in this specification, the
with such proportions of cementitious opposite sides of pipe shall not be more
0.01-in. crack is a test criterion for pipe tested
materials and water as will produce a in three-edge-bearing test and is not intended than 6 mm for all sizes through 600-mm
homogeneous concrete mixture of such as an indication of overstressed or failed pipe internal diameter, and not more than 10
quality that the pipe will conform to the under installed conditions. mm/m of internal diameter for all larger
test and design requirements of this sizes, with a maximum of 16 mm in any
NOTE 4-Ultimate strength of concrete pipe in
specification. All concrete shall have a pipe through 2100-mm internal diameter,
the buried condition is dependent upon varying
water-cementitious materials ratio not soil bedding factors and varying failure modes
and a maximum of 19 mm for 2250-mm
exceeding 0.53 by weight. Cementitious and may have no relationship to the ultimate internal diameter or larger, except where
materials shall be as specified in Section strength as defined under threeedge-bearing beveled end pipe for laying on curves is
6.1 and shall be added to the mix in a conditions. specified by the purchaser.
proportion not less than 470 lb/yd3 unless 7.2 Test Equipment and FacilitiesThe 8.2.4 Length of Pipe-The underrun in
mix designs with a lower cementitious manufacturer shall furnish without charge length of a section of pipe shall not be
material content demonstrate that the all samples, facilities, and personnel more than ⅛ in./ft with a maximum of ½
quality and performance of the pipe meet necessary to carry out the tests required in. in any length of pipe.
the requirements of this specification. by this specification. 8.2.5 Wall Thickness Tolerances-The
6.2.2 Reinforcement: 7.3 Pipe Load Tests-The tests for crush- wall thickness shall be not less than the
6.2.2.1 Placement-Reinforcement shall ing strength, when required, shall be nominal specified in the design given in
be placed as indicated in Section 5.1.6.2, made in accordance with AASHTO T Section 5.1.3.1 by more than 5 percent or
3
subject to the tolerances given in Sections 280. When alternative methods of load /16 in., whichever is greater. A wall
5.1.6.2 and 8.2.2. Minimgm design pro- testing are specified, tests shall be made thickness more than that required in the
tective cover of concrete over the circum- in accordance with the alternative re- design is not a cause for rejection except
ferential reinforcement in the barrel of quirements. that such a pipe may not be used for the
the pipe shall be 1 in. for wall thickness tests required in Section 7.3.
of 2 ½ in. or greater, and ¾ in. for wall
thicknesses less than 2 ½ in., subject to 8. DIMENSIONS AND PERMISSI-
BLE VARIATIONS 9. ACCEPTANCE OF DESIGN
the tolerances given in Section 8.2.2.
6.2.2.2 Splices-The strength of the pipe 9.1 Acceptance by Tests of Specimens-
shall not be adversely affected by the 8.1 Standard Diameters-Pipe shall be Three to five representative specimens, or
splice. manufactured in the standard inside special test pipe that are shorter than
6.2.2.3 Spacing-The spacing center-to- diameters listed in Table 1. standard production pipe, as agreed upon
center of adjacent rings of circumferen- NOTE 5-Diameters other than those shown in by the purchaser and producer, shall be
tial reinforcement in a cage shall not Table I and diameters larger than 144 in. may tested to the 0.01-in. crack and to ulti-
exceed 4 in. for pipe with a wall thick- be available. When such sizes are required, the mate strength and the results recorded.
ness up to and including 4 in. and shall purchaser should contact the producers in the Compute the values in Sections 9.1.1 and
not exceed the wall thickness or 6 in., area. 9.1.2 for both the 0.01-in. crack and the
whichever is smaller, for larger pipe. ultimate strength.
356
M 242 SPECIFICATIONS FOR MATERIALS

9.1.1 Compute the estimated standard the lot of pipe shall be acceptable. When 11.4 Compression Testing of Cylin-
deviation, s, by Eq. 1 or Eq. 2, which the arithmetic mean X is less than the ders:
equations yield identical values. 11.4.1 Prepare test cylinders in accor-
computed value of X s , the lot of pipe
s= [∑ ( X i ]
− X ) 2 /(n − 1) (1) shall be rejected for that design strength
dance with AASHTO T 23, except that
the cylinders may be prepared by meth-
D-load strength.
s= [∑ ( X i
2
]
− X i ) 2 / n /(n − 1) (2) 10.2 Use of Design Test Pipe-When
ods comparable to those used to consoli-
date and cure the concrete in the actual
the pipe tested in Section 9 were selected pipe manufactured, or for concrete of a
where: at random from a production lot, the test consistency too stiff for compaction by
Xi = observed value of the load to data may be used in the acceptance rodding or internal vibration, the follow-
produce the 0.01-in. crack (and analysis of that lot. ing alternative method may be used for
the load to develop the ultimate 10.3 Use of Pipe Tested to 0.01-in. cylinder fabrication: Bolt a mold as
strength). Crack-Pipe that have been tested only to described in AASHTO T 23 to the top of
X = average (arithmetic mean) of the the formation of the 0.01-in. crack and a vibrating metal table. Place concrete in
values of Xi, and that meet the design strength require- three equal lifts within the cylinder.
ments shall be acceptable for use. All Externally vibrate each lift on a metal
n = number of observed values. pipe that test less than the design strength table by means of a vibrator rigidly at-
9.1.2 Compute the minimum allowable shall be removed from the lot and marked tached to the underside of the metal table
arithmetic mean, X s , by Eq. 3. In Eq. 3, so that they will not be shipped. top. Operate the vibrator at a speed of at
the value of the estimated standard devia- least 800 vibrations/minutes. Place a
TABLE 2 Sample Size
tion, s, shall be as calculated by Eq. 1 or Sample Equation cylindrical hammer on the surface of
Lot Size Equation each concrete lift during vibration 1/4 in.
2 or equal to 0.07L, whichever is greater. Size Nº
0 to 300 3 Xs = L + 1.08s (4) smaller in diameter than the inside di-
301 to 500 4 Xs = L + 1.09s (5,
X s = L + 1.07 s (3) 501 to 800 5 Xs = L+ 1.10s (6)
ameter of the mold and weighing 0.353
where: 801 to 1300 7 Xs = L + 1.16s (7 psi of end surface of the cylinder. Con-
tinue vibration until cement paste begins
L = specification limit (specified D- to ooze up around the bottom edge of -
load). 11. ACCEPTANCE OF PIPE BY the hammer. Repeat this procedure until
9.1.3 The pipe design shall be accept- CONCRETE COMPRESSION the mold is filled. Make compression
able if the arithmetic mean X for the
TESTING tests of the cylinders in accordance with
0.01-in. crack and ultimate strength is AASHTO T 22.
equal to or greater than the computed 11.1 Type of Test Specimen-When the 11.4.2 Prepare not less than five test
acceptance is to be determined in accor- cylinders from each day's production of
values of X s and if all the tested speci-
dance with Section 4.1.2, concrete com- the lot of pipe.
mens meet or exceed the specification
limit. pression tests on either cores or cylinders 11.5 Acceptability by Cylinder Tests:
shall be permitted.
9.2 Alternative Acceptance Method-The 11.5.1 When the average compressive
producer may request approval of designs 11.2 Compression Testing of Cores: strength of all cylinders tested is equal to
based on empirical evaluations of the 11.2.1 Obtain and test cores in accor- or greater than the design concrete
strength of the pipe including, but not dance with the provision of AASHTO T strength and not more than 10 percent of
limited to, designs based on interpolation 24, except that the requirements for the cylinders tested have a compressive
between designs approved in accordance moisture conditioning shall not apply. strength less than the design concrete
with Section 9.1, or designs evaluated on 11.2.2 Cut one core from each specimen strength, and no cylinder tested has a
the basis of tests other than the three- of a sample randomly selected from a lot, compressive strength less than 80 percent
edge-bearing test method. Acceptance of and the sample size shall be as shown in of the design concrete strength, then the
design tests need not be performed for Table 2. lot shall be accepted.
each contract or order. 11.5.2 When the compressive strength
11.3 Acceptability by Core Tests:
of the cylinders tested does not conform
11.3.1 When the compressive strength to the acceptance criteria in Section
10. ACCEPTANCE OF PIPE BY of all cores tested is equal to or greater 11.5.1, the acceptability of the lot shall be
LOAD TESTING than the design concrete strength, the lot determined in accordance with the provi-
shall be accepted. sions of Section 10.
10.1 Lot Sampling-When the accep- 11.3.2 When the compressive strength
tance is to be in accordance with Section of one or more of the cores tested is less
than the design concrete strength, the 12. INSPECTION
4.1.1, randomly select from the lot a
sample of the size listed in Table 2 and pipe from which those cores were taken
test each specimen to the 0.01-in. crack. may be recored. When the compressive 12.1 The quality of materials, process
When all specimen test strengths are strength of the recore is equal to or of manufacture, and the finish pipe shall
greater than the minimum design strength greater than the design concrete strength, be subject to inspection by the purchaser.
D-load, the lot shall be accepted. When the lot shall be accepted.
one or more specimen test strengths are 11.3.3 When the compressive strength
less than the minimum design strength D- 13. REJECTION
of any recore is less than the design
load, the values for X and s shall be concrete strength, each pipe of the sam-
computed and substituted into the appli- ple shall be tested by the three-edge- 13.1 Pipe shall be subject to rejection
cable equation given in Table 2. When bearing method and the acceptability of for failure to conform to any of the speci-
the arithmetic mean X is equal to or the lot shall be determined in accordance fication requirements. Individual sections
with the provisions of Section 10. of pipe may be rejected because of any of
greater than the computed value of X s the following:
357
M 242 SPECIFICATIONS FOR MATERIALS

13.1.1 Fractures or cracks passing 17. PRODUCT MARKING X = average (arithmetic mean) of the
through the wall, except for a single end
crack that does not exceed the depth of observed values X s and
the joint. 17.1 The following information shall
s = estimated standard deviation.
be legibly marked on each section of
13.1.2 Defects that indicate mixing, and pipe: NOTE X1-The observed values of pipe
molding not in compliance with Section strengths will be divided by 100 to simplify
6.2. 17.1.1 The pipe strength shall be indi-
the computations in accordance with the
cated by the 0.01-in. crack D-load desig- recommendation made in Section 25 of ASTM
13.1.3 The ends of the pipe are not nated in Section 5.1.2 followed by the STP 15-C. Manual on Quality Control of
normal to the walls and center line of the capital letter D and specification designa- Materials. The effect is to reduce the size of
pipe, within the limits of variations given tion. the numbers so they can be computed more
in Section 8.2.3. readily on a desk calculator.
17.1.2 Date of manufacture,
13.1.4 Damaged ends where such dam-
age would prevent making a satisfactory 17.1.3 Name or trademark of the manu- X1.7 Calculate the values for X as
joint. facturer, follows:
17.1.4 Plant identification, and 17.1.3
13.1.5 Surface defects that indicate Xi X i2
honeycombed or open texture that would One end of each section of pipe designed
to be installed with a particular axis of 480 230400
adversely affect the function of the pipe. 325 105625
orientation shall be clearly marked during
13.2 The exposure of the ends of 430 184900
the process of manufacturing or immedi- 450 202500
longitudinals, stirrups, or spacers that ately thereafter on the inside and outside 405 164025
have been used to position the cages of opposite walls on the vertical axis or
during the placement of the concrete is shall be designated by location of lift ∑ Xi = 2090 ∑ X i2 = 887450
not a cause for rejection. holes. (∑ X i )2 = (2090)2
17.2 Markings shall be indented on the 4368100
14. DISPOSITION OF A REJECTED pipe section or painted thereon with X = (∑ X i / n )x100
LOT waterproof paint.
X = (2090 / 5)x100
14.1 A lot of pipe which fails to meet APPENDIX X = 41800lbf
the criteria for acceptability may be X1.8 The standard deviation, s, may be
(Non-mandatory Information)
utilized in accordance with a procedure computed by either Eq. 1 or Eq. 2. Since
mutually agreed upon by the producer Eq. 2 is a simpler form for computation,
and the purchaser. The procedure may X1. EXAMPLE CALCULATION this will be used.
demonstrate improvement in the lot,
statistically calculate a reduced D-load
strength for the lot, or develop an accept- X1.1 As required by Section 10.1, the s= [∑ ( X i
2
]
− X i ) 2 / n /(n − 1)

able disposition. The producer shall bear acceptability of a lot of 520 sections of
54-in. designated inside diameter pipe s = (887450) − 4368100 / 5) /(5 − 1)
all expenses incurred by the procedure.
will be determined in accordance with
Section 4.1.1. The design strength (0.01 s = 3458
15. REPAIRS in. crack) D-load is specified as 1250 s = 58.8
lbf/linear ft per foot of designated inside
X1.9 Multiply by 100 to obtain total
diameter (1250 D pipe).
15.1 Pipe may be repaired, if neces- pounds-force:
sary, because of imperfections in manu- X1.2 From the lot, randomly select a
s = 58.8 X 1.10
facture, damage during handling, or pipe sample of five specimens (n = 5) each 6
ft long as shown in Table 2. s = 5880 lbf
that have been cored for testing, and will
be acceptable if, in the opinion of the X1.3 Test the pipe and record the The required minimum allowable arith-
purchaser, the repairs are sound and observed values of Xi, in pounds-force metic mean X s is computed by Eq. 6:
properly finished and cured and the which produce the 0.01-in. crack: 48000,
repaired pipe conforms to the require- 32500, 43000, 45000, and 40500. Xs = L+1.10s
ments of this specification. X1.4 Since in this example Xi is in Xs = 33750 + 1.10 X 5880
pounds-force, convert the specification
16. CERTIFICATION limit L (design strength D-load) to Xs = 40218 lbf
pounds by multiplying the D-load times
the designated inside diameter in feet Since the actual X of 41800 lbf is
16.1 When agreed upon in writing by times the pipe length in feet, or greater than the required minimum al-
the purchaser and the producer, a certifi- L = 1250 X (54/12) X 6 = 33750 lbf lowable X s of 40218 lbf, the lot of pipe
cation shall be made the basis of accep- is acceptable.
tance. This shall consist of a copy of the X1.5 Since an observed value of the
producer's test report or a statement by test loads (Xi=32500) is less than the X1.10 ASTM STP 15-D, Manual on
the producer, accompanied by a copy of specification limit (L=33750), compli- Presentation of Data and Control Chart
the test results, that the pipe has been ance with the acceptability criteria must Analysis, is a valuable source of informa-
sampled, tested, and inspected in accor- be determined in accordance with Section tion regarding statistical procedures and
dance with the provisions of Section 4. 10. simplified computational methods.
Each certification so furnished shall be X1.6 The following values for X and s
signed by an authorized agent of the must be computed (see Note X1):
producer.

358

You might also like