NDPHC EXHAUST STACK REPAIR WORKS - DIC Advisory Note #001

Location/Date: Alaoji Power Station/24th September 2022


Contractor PM / gbolahan.adewuyi@trifectaintegrated.com,
Contact ikechuwku@trifectaintegrated.com
DIC Reviewer Name:Obiefuna Ezeoke, Arome Haruna, Anthony Ezenwokolo
DIC Rep Position:
Project Manager, EHS Manager
• Engr. Ayodele Fatona
NDPHC CC List: • Engr.Mohammed Dauda
• Engr. Abdullahi Kassim
Method Statement
SN To be amended/added Comments
3.5.7.1 - Surface Preparation
Procedure
Please note that while the ISO standard may be
1. The surface of the steel
acceptable the spec of ISO 8501-1 of SA2.5
1 structure shall be blast
would have been preferrable.
cleaned to ISO 8504-1:2019
in accordance to applicable
NDPHC spec
Please refer to email sent out to all contractors
on the 23rd of September 2022 and attached GE
Document #168A6553 (General paint
2 3.5.7.2 - Surface Finishing specification with relevant sections on lateral
and vertical exhaust systems). Your painting
procedures and specifications shall not deviate
from these standards.

3 3.5.7.4 Paint Materials Equivalent The above shall apply- refer to the document.

4
Schedule
SN To be amended/added Comments
A level three (L3) schedule of activities
would have been preferrable but the
1 PROJECT SCHEDULE supplied one shown below is okay. Please
confirm if the duration is for all units’
exhaust systems.
Risk Assessment
SN To be amended/added Comments
You shall be submitting your team to
1 Risk Assessment further risk assessment engagement should
the need arise.
A valid medical fitness certificate of at
2 Medical Fitness Certificate least 1 year for your employees will be a
plus but can be waived.

3rd party certifications/certificates for lifting


equipment (cranes, cherry pickers etc.)
lifting gears (shackles, slings, wire ropes
3 Critical Certifications/Certificates etc.) competency certificates (operators,
riggers) calibration certificates (gas
monitors etc.) will be made available on
site.

It is expected that all personnel mobilizing


4 Training
to site are adequately trained.

Figure 1: Vertical Exhaust Section


Figure 2: Vertical Exhaust Section
FO
R
EX
G EC
E U
TI
O
O N

DT-7C
ffi
c ia
l
GE Energy Products - Europe GENERAL PAINTING SPECIFICATION

CONTENTS

STATE OF MODIFICATIONS.................................................................................................................... 2
SPECIFICATION OF ANTI-CORROSION PROTECTING SYSTEMS APPLIED ON THE VARIOUS
EQUIPMENT MENTIONED HEREUNDER............................................................................................. 3
1.TYPE OF PRODUCTS USED..............................................................................................................................3
2.RELEVANT SYSTEM STANDARDS.................................................................................................................5
SUMMARY .................................................................................................................................................... 7

Reference : 168A6553 Rev. : E Section : 01 Page : 1 / 23


Ce document, propriété exclusive de GE Energy Products France SNC This document, exclusive property of GE Energy Products France SNC
est strictement confidentiel. Il ne peut être communiqué, is strictly confidential. It must not be communicated,
copié ou reproduit sans notre autorisation écrite. DT-7C copied or reproduced without our prior written consent.
GE Energy Products - Europe GENERAL PAINTING SPECIFICATION

STATE OF MODIFICATIONS
INDEX DATE DESCRIPTION
A 17/02/2005 First issue

B 24/03/2005 MODIF IMPORTANT REMARK SHEET 6


MODIF ITEM 1605 ( GAS COMPT VENTILATION
SKID)SHEET 13 AND 14
C 15/09/2005 ADD MODULE 262
MODIF IMPORTANT REMARK SHEET 6
D 27/09/2005 MODIF (MODULES
240,262,266,2F6,2G0,2J0,422,423,425,432;460,543,811,B10,
B51,A980,1617,1643)
E 14/12/2005 ADD FINAL COLOR ON MODULES MAKE WITH OUR
SUPPLIERS

Reference : 168A6553 Rev. : E Section : 01 Page : 2 / 23


Ce document, propriété exclusive de GE Energy Products France SNC This document, exclusive property of GE Energy Products France SNC
est strictement confidentiel. Il ne peut être communiqué, is strictly confidential. It must not be communicated,
copié ou reproduit sans notre autorisation écrite. copied or reproduced without our prior written consent.
GE Energy Products - Europe GENERAL PAINTING SPECIFICATION

SPECIFICATION OF ANTI-CORROSION PROTECTING SYSTEMS


APPLIED ON THE VARIOUS EQUIPMENT MENTIONED
HEREUNDER

1.TYPE OF PRODUCTS USED


1.1. Primer Coat (Item : P)
l P HEMPADUR 45880 or 47200 - Colour Red 50630 or Grey 11480
(according to final coat colour : see
important remark)
l P2 HEMPEL’S GALVOSIL 15700 - Colour Grey 19840
l P4 HEMPADUR 15500 - Colour Red 50900
l P8 HEMPEL'S SILICONE ZINC PRIMER 16900 - Colour Grey 19840
l P9 AMERON DIMECOT 9 - Colour Grey zinc
l P10A HEMPADUR 15550 - Colour Red 50890
l P10B HEMPADUR 4508H or HEMPADUR 15302 - Colour Red 50890

1.2. Final Coat (Item : F)


l F HEMPATHANE 55910
l F4 HEMPADUR 15500 - Colour White 11630
l F8 HEMPEL'S SILICONE ALUMINIUM 56910 - Colour Aluminium 19000
l F9 AMERON PSX 892 HS - Colour Aluminium
l F10 HEMPEL’S ANTI-SLINT 67500
1.3. Hempel/Ameron products are available all over the world (same composition, same quality, same
guarantee). To know the address of the nearest vendor, you can contact: Hempel/Ameron France…
HEMPEL PEINTURES FRANCE
60149 SAINT CREPIN IBOUVILLERS
Tel : (+33) (0) 3 44 08 28 90

AMERON B.V.
78400 CHATOU
Tel : (+33) (0) 1 30 71 50 50

Reference : 168A6553 Rev. : E Section : 01 Page : 3 / 23


Ce document, propriété exclusive de GE Energy Products France SNC This document, exclusive property of GE Energy Products France SNC
est strictement confidentiel. Il ne peut être communiqué, is strictly confidential. It must not be communicated,
copié ou reproduit sans notre autorisation écrite. copied or reproduced without our prior written consent.
GE Energy Products - Europe GENERAL PAINTING SPECIFICATION

1.4. Remarks
lSee data sheet of products here above mentioned.
lAll the operations of applying anti-corrosion protection coating stated before are carried out
according to the standard general specification n 91–421 666
1.5. Protection of machined surfaces and bored holes

TYPE OF PRODUCT

THREADING Rustilo DW 378 by CASTROL

Product leaving an oily or


greasy film

MACHINED SURFACES Ardrox 3140 by BRENT

Product leaving a waxy film

1.6. Product vendor


CASTROL BRENT S.A
Trumel 280, rue J. Baptiste Godin
ZI des Pirey ZI villeneuve Saint Germain
25480 PIREY 02207 SOISSON Cedex
Tel : 03 81 53 32 55 Tel : 03 23 75 58 58

Reference : 168A6553 Rev. : E Section : 01 Page : 4 / 23


Ce document, propriété exclusive de GE Energy Products France SNC This document, exclusive property of GE Energy Products France SNC
est strictement confidentiel. Il ne peut être communiqué, is strictly confidential. It must not be communicated,
copié ou reproduit sans notre autorisation écrite. copied or reproduced without our prior written consent.
GE Energy Products - Europe GENERAL PAINTING SPECIFICATION

2.RELEVANT SYSTEM STANDARDS

TYPE A A' B
PROTECTED Insulated equipment Insulated equipment All internal surfaces of
SURFACES equipment and external
(T° < 150°C) (150°C < T < 500°C) surfaces installed within
building
PAINT SPECIFICATIONS P : 80 µm P8 : 50 µm mini P : 80 µm
(Mean dry thickness in F : 60 µm
microns)
SYSTEM STANDARDS ß HEMPADUR 45880 or ß HEMPEL’S SILICONE ß HEMPADUR 45880 or
47200 ZINC 16900 47200
ß HEMPATHANE 55910

TYPE D E H
PROTECTED All external surfaces of All external surfaces of Internal surfaces of fuel
SURFACES equipment exposed to a equipment exposed to a or oil tanks
mild or medium very aggressive
aggressive environment environment
(Maritimes, industrials,
corrosive)
PAINT SPECIFICATIONS P : 110 µm P : 140 µm P4 : 100 µm
(Mean dry thickness in F : 80 µm F : 100 µm F4 : 100 µm
microns)
SYSTEM STANDARDS ß HEMPADUR 45880 or ß HEMPADUR 45880 or ß HEMPADUR 15500
47200 47200 ß HEMPADUR 15500
ß HEMPATHANE 55910 ß HEMPATHANE 55910

TYPE L M N
PROTECTED Very hot surfaces GT External surfaces of Inlet Belmouth air flow
SURFACES (150°C < T° < 500°C), casing surfaces
except GT casing
PAINT SPECIFICATIONS P8 : 40 µm P2 : 75 µm P2 : 75 µm
(Mean dry thickness in F8 : 25 µm F8 : 25 µm P : 20 µm
microns)
F : 80 µm (mist coat technic)
SYSTEM STANDARDS ß HEMPEL’S SILICONE ß HEMPEL’S GALVOSIL ß HEMPEL’S GALVOSIL
ZINC 16900 15700 15700
ß HEMPEL’S SILICONE ß HEMPEL’S SILICONE ß HEMPATHANE 55910
ALUMINIUM 56910 ALUMINIUM 56910

Reference : 168A6553 Rev. : E Section : 01 Page : 5 / 23


Ce document, propriété exclusive de GE Energy Products France SNC This document, exclusive property of GE Energy Products France SNC
est strictement confidentiel. Il ne peut être communiqué, is strictly confidential. It must not be communicated,
copié ou reproduit sans notre autorisation écrite. copied or reproduced without our prior written consent.
GE Energy Products - Europe GENERAL PAINTING SPECIFICATION

TYPE S S1 S2
PROTECTED Internal surfaces of External surfaces of Surfaces of cheked plates
SURFACES exhaust duct exhaust duct
PAINT SPECIFICATIONS P9 : 65 µm P9 : 65 µm F : 60 mm
(Mean dry thickness in F9 : 50 µm F10 : 0.1kg/m²
microns)
F : 60 mm
SYSTEM STANDARDS ß AMERON ß AMERON DIMECOTE 9 ß HEMPATHANE 55910
DIMECOTE 9 ß AMERON PSX 892 HS ß HEMPEL’S ANTI-SLINT
67500
ß HEMPATHANE 55910

IMPORTANT REMARK:
-1-
When hot dip galvanized steel to be painted: before applying the GEEPE system (D, E …) add a primer coat
(50 µm) of HEMPADUR 15550 (P10A)
When zinc plated sheet on external surfaces to be painted: before applying the GEEPE system (D, E …) add a
primer coat (50 µm) of HEMPADUR 15550 (P10A)
When stainless steel, aluminium or copper to be painted: before applying the GEEPE system (D, E …) add a
primer coat (50 µm) of Hempadur 4508H or Hempadur 15302 (P10B)
When the final coat colour shade is pale (white or cream) use a primer coat of Grey 11480 instead of Red
50630

-2-
FINAL PAINT ON SITE TO BE SUPPLIED BY CUSTOMER.NOT IN GE SCOPE OF SUPPLY

Reference : 168A6553 Rev. : E Section : 01 Page : 6 / 23


Ce document, propriété exclusive de GE Energy Products France SNC This document, exclusive property of GE Energy Products France SNC
est strictement confidentiel. Il ne peut être communiqué, is strictly confidential. It must not be communicated,
copié ou reproduit sans notre autorisation écrite. copied or reproduced without our prior written consent.
GE Energy Products - Europe GENERAL PAINTING SPECIFICATION

SUMMARY
1 GAS TURBINE WITH ASSOCIATED MODULES................................................................................. 9
100 GAS TURBINE and direct auxiliaries .............................................................................................................9
Item 1605 GT UNIT OFF-BASE ACOUSTICAL ENCLOSURE........................................................................9
Item 1605 TURBINE EXHAUST FRAME COOLING FANS (TK) ACOUSTICAL ENCLOSURE ............10
Item 1605 WATER INJECTION SKID OFF-BASE ACOUSTICAL ENCLOSURE......................................12
Item 1605 GAS COMPARTMENT VENTILATION SKID...............................................................................13
Item 1617 LOAD COMPARTMENT....................................................................................................................13
Item 1643 GAS COMPARTMENT VENTILATION SKID...............................................................................13
Item A014 TURBINE CONTROL PANEL..........................................................................................................14
Item A016 GENERATOR CONTROL PANEL ..................................................................................................14
Item A035 WATER INJECTION SKID...............................................................................................................14
Item A040 SELF CLEANING AIR FILTER .......................................................................................................14
Item A041 VERTICAL INLET DUCT .................................................................................................................15
Item A098 OIL MIST ELIMINATOR SKID.......................................................................................................15
Item A108 EQUIPMENT network tOpology ......................................................................................................16
Item A124 CONTROL SKID.................................................................................................................................16
Item A980 INLET SUPPORTING STRUCTURES ............................................................................................16
Item MS99 EXHAUST PLENUM MODULE ......................................................................................................16
2 TURBINE AUXILIARIES ....................................................................................................................... 16
240 GT UNIT FIRE FIGHTING SYSTEM..........................................................................................................16
266 COUPLING BARRIER WALL......................................................................................................................17
280 TURBINE WASHING.....................................................................................................................................17
2F6 WALKWAYS...................................................................................................................................................17
2G0 GT GAS FUEL SUPPLY ...............................................................................................................................18
2JO COMPRESSED AIR SYSTEM (with container).........................................................................................18
4 EXHAUST SYSTEM ................................................................................................................................ 19
422– LATERAL EXHAUST ..................................................................................................................................19
423 INSULATION UNDER EXHAUST...............................................................................................................19
425 ELBOW AND DOWNSTREAM DUCTING ................................................................................................19
432 EXHAUST STACK ON SIDE EXHAUST ....................................................................................................19
460 GRID AT GT EXHAUST FOR PERSONNAL PROTECTION................................................................20
5 GENERATOR & ENERGY EVACUATION .......................................................................................... 20

Reference : 168A6553 Rev. : E Section : 01 Page : 7 / 23


Ce document, propriété exclusive de GE Energy Products France SNC This document, exclusive property of GE Energy Products France SNC
est strictement confidentiel. Il ne peut être communiqué, is strictly confidential. It must not be communicated,
copié ou reproduit sans notre autorisation écrite. copied or reproduced without our prior written consent.
GE Energy Products - Europe GENERAL PAINTING SPECIFICATION

510 GT GENERATOR ...........................................................................................................................................20


543 GENERATOR ACCESSORY COMPARTMENT.......................................................................................20
560 MV BUS DUCTS..............................................................................................................................................21
8 COOLING SYSTEM ................................................................................................................................ 21
811 FIN FAN COOLERS .......................................................................................................................................21
9 PIPING SYSTEM ..................................................................................................................................... 22
910 PIPING..............................................................................................................................................................22
B GT CONTROL & LV DISTRIBUTION ................................................................................................. 22
B10 TURBINE CONTROL COMPARTMENT (TCC) ......................................................................................22
B51 GT & GENERATOR AUXILIARIES LV DISTRIBUTION (MCC) ........................................................22
B52 125 V DC BATTERY CHARGER CUBICLE .............................................................................................23
B53 125 V DC BATTERY ......................................................................................................................................23
D POWER PLANT ELECTRICAL AUXILIARIES.................................................................................. 23
D11 UNIT STEP UP TRANSFORMER ...............................................................................................................23
D12 AUXILIARY TRANSFORMERS .................................................................................................................23
ELECTRICAL MOTORS PUMPS FANS VALVES & IN LINE INSTALLED EQUIPMENTS AND
DEVICES ..................................................................................................................................................... 23
MANUTENTION & MAINTENANCE TOOLS ........................................................................................ 23

Reference : 168A6553 Rev. : E Section : 01 Page : 8 / 23


Ce document, propriété exclusive de GE Energy Products France SNC This document, exclusive property of GE Energy Products France SNC
est strictement confidentiel. Il ne peut être communiqué, is strictly confidential. It must not be communicated,
copié ou reproduit sans notre autorisation écrite. copied or reproduced without our prior written consent.
GE Energy Products - Europe GENERAL PAINTING SPECIFICATION

ESTIMATED
SYSTEM SURFACE FINAL
ITEM EQUIPMENT SHOP SITE REMARKS
TYPE FOR FINAL COLOUR
COAT IN M²

1 GAS TURBINE WITH ASSOCIATED MODULES


100 GAS TURBINE AND DIRECT AUXILIARIES
A External cold surface B P / / Grey (1)
T° < 150°C F RAL 7035
B Internal air inlet N P2 / / Blue (1)
surface (Bellmouth) I RAL 5012
T° < 150°C F
C Trunnion lifting base B P / / Yellow (1)
T°< 150°C F RAL 1028
D Oil tank internal B P / / Grey
surfaces F RAL 7035
T° < 150°C
E All casing outside M P2 / / Alu 19000 (1)
surfaces T>200°C F8
Item 1605 GT UNIT OFF-BASE ACOUSTICAL ENCLOSURE
A ∑ Steel structure B P / / Grey
∑ Handrails indoor F RAL 7035
B ∑ Grating / X / / / Galvanised steel
C PANELS OF ROOF / X / / Grey Galvanised and
AND WALL RAL 9002 lacquered sheets
Internal perforated
sheets
D PANELS OF ROOF A P / / Red 50630 Sand blasted SA2.5
AND WALL or zinc plated sheets
Internal surfaces
under acoustical
treatment
E PANELS OF ROOF B P / Grey RAL Sand blasted SA2.5
AND WALL F 9002 or zinc plated sheets
Internal surfaces
F PANELS OF ROOF E P F 600 (2) Sand blasted SA 2.5
AND WALL or zinc plated sheets
External surfaces and
edges
G DOORS HATCH / X / / Grey Galvanised and
Internal perforated RAL 9002 lacquered sheets
sheets

(1) GE Energy Products France SNC Standard


(2) Final colour shall be selected by the customer according to one of the following colour range charts :
AFNOR, RAL840HR, BS4800 or 381C or MUNSELL
(3) Total surfaces shall be given later

(4) Colour of lacquered sheets shall be selected in supplier standard restricted colour range
(5) The duct casing will be internally painted (after grid-blasting) on. All carbon steel areas which are not
internally covered by insulation (for example, silencer duct areas where baffles are put on) and a width of
100 mm at the inlet and the outlet borders of the duct casing.
Reference : 168A6553 Rev. : D Section : 01 Page : 9/ 23
Ce document, propriété exclusive de GE Energy Products France SNC This document, exclusive property of GE Energy Products France SNC
est strictement confidentiel. Il ne peut être communiqué, is strictly confidential. It must not be communicated,
copié ou reproduit sans notre autorisation écrite. copied or reproduced without our prior written consent.
GE Energy Products - Europe GENERAL PAINTING SPECIFICATION

ESTIMATED
SYSTEM SURFACE FINAL
ITEM EQUIPMENT SHOP SITE REMARKS
TYPE FOR FINAL COLOUR
COAT IN M²
H DOORS HATCH A P / / Red 50630 Sand blasted SA2.5
Internal surfaces or zinc plated sheet
under acoustical
treatment
I DOORS HATCH E P F 30 (2) Sand blasted SA2.5
External surfaces and or zinc plated sheet
edges
J Miscellaneous B P / / Grey Zinc plated sheet
(partition …) F RAL 7035
K ∑ Fan / X / / / Supplier standard
∑ Electrical motor
L Manutention and / / / / / See at the end of
maintenance tools the specification
VENTILATION
A Internal surfaces for B P / / Grey (1)
air ventilation duct F RAL 7035
(T<150°C) without
acoustical treatment

B Internal surfaces for A P / / Red 50630 (1)


air ventilation duct
(T<150°C) with
acoustical treatment

C External and internal A' P8 / / Grey (1)


surfaces for air 19840
ventilation duct
(T≥150°C) with or
without acoustical
treatment

D External surfaces E P F 50 (2)

Item 1605 TURBINE EXHAUST FRAME COOLING FANS (TK) ACOUSTICAL ENCLOSURE
A PANELS OF ROOF / X / / Grey Galvanised and
AND WALL RAL 9002 lacquered sheets
Internal perforated
sheets

(1) GE Energy Products France SNC Standard


(2) Final colour shall be selected by the customer according to one of the following colour range charts :
AFNOR, RAL840HR, BS4800 or 381C or MUNSELL
(3) Total surfaces shall be given later

(4) Colour of lacquered sheets shall be selected in supplier standard restricted colour range
(5) The duct casing will be internally painted (after grid-blasting) on. All carbon steel areas which are not
internally covered by insulation (for example, silencer duct areas where baffles are put on) and a width of
100 mm at the inlet and the outlet borders of the duct casing.
Reference : 168A6553 Rev. : D Section : 01 Page : 10/ 23
Ce document, propriété exclusive de GE Energy Products France SNC This document, exclusive property of GE Energy Products France SNC
est strictement confidentiel. Il ne peut être communiqué, is strictly confidential. It must not be communicated,
copié ou reproduit sans notre autorisation écrite. copied or reproduced without our prior written consent.
GE Energy Products - Europe GENERAL PAINTING SPECIFICATION

ESTIMATED
SYSTEM SURFACE FINAL
ITEM EQUIPMENT SHOP SITE REMARKS
TYPE FOR FINAL COLOUR
COAT IN M²
B PANELS OF ROOF A P / / Red 50630 Sand blasted SA2.5
AND WALL or zinc plated sheets
Internal surfaces
under acoustical
treatment
C PANELS OF ROOF B P / Grey RAL Sand blasted SA2.5
AND WALL F 9002 or zinc plated sheets
Internal surfaces
D PANELS OF ROOF E P F 40 (2) Sand blasted SA 2.5
AND WALL or zinc plated sheets
External surfaces and
edges
E DOORS HATCH / X / / Grey Galvanised and
Internal perforated RAL 9002 lacquered sheets
sheets
F DOORS HATCH A P / / Red 50630 Sand blasted SA2.5
Internal surfaces or zinc plated sheet
under acoustical
treatment
G DOORS HATCH E P F 4 (2) Sand blasted SA2.5
External surfaces and or zinc plated sheet
edges
H Miscellaneous B P / / Grey Zinc plated sheet
F RAL 7035
VENTILATION
A Internal surfaces for B P / / Grey (1)
air ventilation duct F RAL 7035
(T<150°C) without
acoustical treatment

B Internal surfaces for A P / / Red 50630 (1)


air ventilation duct
(T<150°C) with
acoustical treatment

(1) GE Energy Products France SNC Standard


(2) Final colour shall be selected by the customer according to one of the following colour range charts :
AFNOR, RAL840HR, BS4800 or 381C or MUNSELL
(3) Total surfaces shall be given later

(4) Colour of lacquered sheets shall be selected in supplier standard restricted colour range
(5) The duct casing will be internally painted (after grid-blasting) on. All carbon steel areas which are not
internally covered by insulation (for example, silencer duct areas where baffles are put on) and a width of
100 mm at the inlet and the outlet borders of the duct casing.
Reference : 168A6553 Rev. : D Section : 01 Page : 11/ 23
Ce document, propriété exclusive de GE Energy Products France SNC This document, exclusive property of GE Energy Products France SNC
est strictement confidentiel. Il ne peut être communiqué, is strictly confidential. It must not be communicated,
copié ou reproduit sans notre autorisation écrite. copied or reproduced without our prior written consent.
GE Energy Products - Europe GENERAL PAINTING SPECIFICATION

ESTIMATED
SYSTEM SURFACE FINAL
ITEM EQUIPMENT SHOP SITE REMARKS
TYPE FOR FINAL COLOUR
COAT IN M²
C External and internal A' P8 / / Grey (1)
surfaces for air 19840
ventilation duct
(T≥150°C) with or
without acoustical
treatment

D External surfaces E P F 50 (2)

Item 1605 WATER INJECTION SKID OFF-BASE ACOUSTICAL ENCLOSURE


A ∑ Steel structure B P / / Grey
∑ Handrails indoor F RAL 7035
B ∑ Grating / X / / / Galvanised steel
C PANELS OF ROOF / X / / Grey Galvanised and
AND WALL RAL 9002 lacquered sheets
Internal perforated
sheets
D PANELS OF ROOF A P / / Red 50630 Sand blasted SA2.5
AND WALL or zinc plated sheets
Internal surfaces
under acoustical
treatment
E PANELS OF ROOF B P / Grey RAL Sand blasted SA2.5
AND WALL F 9002 or zinc plated sheets
Internal surfaces
F PANELS OF ROOF E P F 100 (2) Sand blasted SA 2.5
AND WALL or zinc plated sheets
External surfaces and
edges
G DOORS HATCH / X / / Grey Galvanised and
Internal perforated RAL 9002 lacquered sheets
sheets
H DOORS HATCH A P / / Red 50630 Sand blasted SA2.5
Internal surfaces or zinc plated sheet
under acoustical
treatment
I DOORS HATCH E P F 9 (2) Sand blasted SA2.5
External surfaces and or zinc plated sheet
edges

(1) GE Energy Products France SNC Standard


(2) Final colour shall be selected by the customer according to one of the following colour range charts :
AFNOR, RAL840HR, BS4800 or 381C or MUNSELL
(3) Total surfaces shall be given later

(4) Colour of lacquered sheets shall be selected in supplier standard restricted colour range
(5) The duct casing will be internally painted (after grid-blasting) on. All carbon steel areas which are not
internally covered by insulation (for example, silencer duct areas where baffles are put on) and a width of
100 mm at the inlet and the outlet borders of the duct casing.
Reference : 168A6553 Rev. : D Section : 01 Page : 12/ 23
Ce document, propriété exclusive de GE Energy Products France SNC This document, exclusive property of GE Energy Products France SNC
est strictement confidentiel. Il ne peut être communiqué, is strictly confidential. It must not be communicated,
copié ou reproduit sans notre autorisation écrite. copied or reproduced without our prior written consent.
GE Energy Products - Europe GENERAL PAINTING SPECIFICATION

ESTIMATED
SYSTEM SURFACE FINAL
ITEM EQUIPMENT SHOP SITE REMARKS
TYPE FOR FINAL COLOUR
COAT IN M²
J Miscellaneous B P / / Grey Zinc plated sheet
(partition …) F RAL 7035
K ∑ Fan / X / / / Supplier standard
∑ Electrical motor
L Manutention and / / / / / See at the end of
maintenance tools the specification
VENTILATION
A Internal surfaces for B P / / Grey (1)
air ventilation duct F RAL 7035
(T<150°C) without
acoustical treatment

B Internal surfaces for A P / / Red 50630 (1)


air ventilation duct
(T<150°C) with
acoustical treatment

C External and internal A' P8 / / Grey (1)


surfaces for air 19840
ventilation duct
(T≥150°C) with or
without acoustical
treatment

D External surfaces E P F (50) (2)

Item 1605 GAS COMPARTMENT VENTILATION SKID


A ∑ Steel structure B P / / Grey
F RAL 7035
B ∑ Fan / X / / / Supplier standard
∑ Electrical motor
Item 1617 LOAD COMPARTMENT
A All internal surfaces / / / / Grey Galvanised steel
RAL 7035
B All external surfaces E P F (60) (2)

Item 1643 GAS COMPARTMENT VENTILATION SKID


Steel structure P Grey
A E / /
Handrails indoor F RAL 9002

(1) GE Energy Products France SNC Standard


(2) Final colour shall be selected by the customer according to one of the following colour range charts :
AFNOR, RAL840HR, BS4800 or 381C or MUNSELL
(3) Total surfaces shall be given later

(4) Colour of lacquered sheets shall be selected in supplier standard restricted colour range
(5) The duct casing will be internally painted (after grid-blasting) on. All carbon steel areas which are not
internally covered by insulation (for example, silencer duct areas where baffles are put on) and a width of
100 mm at the inlet and the outlet borders of the duct casing.
Reference : 168A6553 Rev. : D Section : 01 Page : 13/ 23
Ce document, propriété exclusive de GE Energy Products France SNC This document, exclusive property of GE Energy Products France SNC
est strictement confidentiel. Il ne peut être communiqué, is strictly confidential. It must not be communicated,
copié ou reproduit sans notre autorisation écrite. copied or reproduced without our prior written consent.
GE Energy Products - Europe GENERAL PAINTING SPECIFICATION

ESTIMATED
SYSTEM SURFACE FINAL
ITEM EQUIPMENT SHOP SITE REMARKS
TYPE FOR FINAL COLOUR
COAT IN M²
P Grey
B Miscellaneous E / / Zinc plated sheet
F RAL 9002
Fan
C / X / / / Supplier standard
Electrical motor
VENTILATION
Internal surfaces for
air ventilation duct P Grey
A B / / (1)
(T<150°C) without F RAL 7035
acoustical treatment
Internal surfaces for
air ventilation duct
B A P / / Red 50630 (1)
(T<150°C) with
acoustical treatment
External surfaces P
C E F (50) (2)
(T<150°C)
Item A014 TURBINE CONTROL PANEL
A Speedtronic / X / / Innovation
Graphite
Item A016 GENERATOR CONTROL PANEL
A Generator control / X / / Grey
panel RAL 7032
Item A035 WATER INJECTION SKID
A Frame D P / / Grey (1)
F RAL 7035
B Steam piping L P8 / / Alu 19000 Stainless steel
F8 piping is not painted
C Trunnion lifting base E P / / Yellow (1)
F RAL 1028
C Water piping D P / / Grey Stainless steel
F RAL 7035 piping is not painted
Item A040 SELF CLEANING AIR FILTER
A Internal surfaces D P / / Grey (1)
clean air side: F RAL 7038
∑ Clean air housing
sheets
∑ Transition duct
sheets
∑ Internal structure

(1) GE Energy Products France SNC Standard


(2) Final colour shall be selected by the customer according to one of the following colour range charts :
AFNOR, RAL840HR, BS4800 or 381C or MUNSELL
(3) Total surfaces shall be given later

(4) Colour of lacquered sheets shall be selected in supplier standard restricted colour range
(5) The duct casing will be internally painted (after grid-blasting) on. All carbon steel areas which are not
internally covered by insulation (for example, silencer duct areas where baffles are put on) and a width of
100 mm at the inlet and the outlet borders of the duct casing.
Reference : 168A6553 Rev. : D Section : 01 Page : 14/ 23
Ce document, propriété exclusive de GE Energy Products France SNC This document, exclusive property of GE Energy Products France SNC
est strictement confidentiel. Il ne peut être communiqué, is strictly confidential. It must not be communicated,
copié ou reproduit sans notre autorisation écrite. copied or reproduced without our prior written consent.
GE Energy Products - Europe GENERAL PAINTING SPECIFICATION

ESTIMATED
SYSTEM SURFACE FINAL
ITEM EQUIPMENT SHOP SITE REMARKS
TYPE FOR FINAL COLOUR
COAT IN M²
B Dirty air side: D P / / Grey
∑ Internal structure F RAL 7038
C External surfaces E P F (250) (2) Duckboard in hot dip
∑ steel structure galvanised steel are
∑ Clean air housing not painted
sheets
∑ Transition duct
sheets
D Handrails, gangways, E P F (50) (2) Steps are
walkways, ladders galvanised
E SELF CLEANING AIR / X / / / Galvanised
FILTER ACCESS
Gratings
F SELF CLEANING AIR / X / / / Supplier standard
FILTER
Local control panel
G COMPRESSED AIR
PIPEWORK
∑ Piping / X / / / Galvanised steel
∑ Blow pipes / / / / / Aluminium
H EVAPORATIVE E P / / (2) Ladders are
COOLER F galvanised steel
Internal and external
surfaces
Item A041 VERTICAL INLET DUCT
A Internal surfaces D P / / Grey (1)
without noise F RAL 7038
insulation parts
B Paint under noise A P / / Red 50630 (1)
insulation parts
C All external surfaces E P F (120) (2) Duckboard in hot dip
galvanised steel are
not painted
Item A098 OIL MIST ELIMINATOR SKID
A ∑ Motor / X / / RAL 5000 GE Energy Products
∑ Fan Blue France approved
supplier's standard

(1) GE Energy Products France SNC Standard


(2) Final colour shall be selected by the customer according to one of the following colour range charts :
AFNOR, RAL840HR, BS4800 or 381C or MUNSELL
(3) Total surfaces shall be given later

(4) Colour of lacquered sheets shall be selected in supplier standard restricted colour range
(5) The duct casing will be internally painted (after grid-blasting) on. All carbon steel areas which are not
internally covered by insulation (for example, silencer duct areas where baffles are put on) and a width of
100 mm at the inlet and the outlet borders of the duct casing.
Reference : 168A6553 Rev. : D Section : 01 Page : 15/ 23
Ce document, propriété exclusive de GE Energy Products France SNC This document, exclusive property of GE Energy Products France SNC
est strictement confidentiel. Il ne peut être communiqué, is strictly confidential. It must not be communicated,
copié ou reproduit sans notre autorisation écrite. copied or reproduced without our prior written consent.
GE Energy Products - Europe GENERAL PAINTING SPECIFICATION

ESTIMATED
SYSTEM SURFACE FINAL
ITEM EQUIPMENT SHOP SITE REMARKS
TYPE FOR FINAL COLOUR
COAT IN M²
B ∑ Support legs and B P / / Grey
maintenance F RAL 7035
platform
∑ Silencer
∑ Buffer box
Item A108 EQUIPMENT NETWORK TOPOLOGY
A Equipment network / X / / Grey
topology RAL 7032
Item A124 CONTROL SKID
A Gt local control / X / / Grey Supplier standard
equipment RAL 7032
Item A980 INLET SUPPORTING STRUCTURES
A Steel structure E P F (250) (2)

B ACCESS E P F (50) (2)


Ladders, stairways,
etc.
C ACCESS / X / / / Galvanised grating
Steps, gratings panels
D Ladder bars S2 F / / Light Grey
F10 RAL 7035
F
Item MS99 EXHAUST PLENUM MODULE
A External surfaces / X / / Supplier Supplier standard
standard

2 TURBINE AUXILIARIES
240 GT UNIT FIRE FIGHTING SYSTEM
A CO2 bottles / X / / Red Supplier standard
RAL 3000 (100µm mini )
B CO2 rack / X / / / Galvanised steel
not painted
C CO2 piping / X / / / Hot dip galvanised
steel is not painted
D CO2 container E P / / Red (1)
External surfaces F RAL 3000
E CO2 container B P / / White (1)
Internal surfaces F

(1) GE Energy Products France SNC Standard


(2) Final colour shall be selected by the customer according to one of the following colour range charts :
AFNOR, RAL840HR, BS4800 or 381C or MUNSELL
(3) Total surfaces shall be given later

(4) Colour of lacquered sheets shall be selected in supplier standard restricted colour range
(5) The duct casing will be internally painted (after grid-blasting) on. All carbon steel areas which are not
internally covered by insulation (for example, silencer duct areas where baffles are put on) and a width of
100 mm at the inlet and the outlet borders of the duct casing.
Reference : 168A6553 Rev. : D Section : 01 Page : 16/ 23
Ce document, propriété exclusive de GE Energy Products France SNC This document, exclusive property of GE Energy Products France SNC
est strictement confidentiel. Il ne peut être communiqué, is strictly confidential. It must not be communicated,
copié ou reproduit sans notre autorisation écrite. copied or reproduced without our prior written consent.
GE Energy Products - Europe GENERAL PAINTING SPECIFICATION

ESTIMATED
SYSTEM SURFACE FINAL
ITEM EQUIPMENT SHOP SITE REMARKS
TYPE FOR FINAL COLOUR
COAT IN M²
F Unit fire panel / X / / Light Grey Supplier standard
RAL 7032
262 EXHAUST ACOUSTIC WALL
P Grey
A Steelwork structure E / /
F RAL 7035
PANELS OF WALL
AND ACCES OR
Grey Galvanised and
B DOOR HATCH / X / /
RAL 9002 lacquered sheets
Internal perforated
sheets
PANELS OF WALL
AND ACCES OR
DOOR HATCH Sand blasted SA2.5
C A P / / Red 50630
Internal surfaces or zinc plated sheets
under acoustical
treatment
PANELS OF WALL
AND ACCES OR
P Grey Sand blasted SA 2.5
D DOOR HATCH E / (50)
F RAL 7035 or zinc plated sheets
External surfaces and
edges
P Grey
E Miscellaneous E / / Zinc plated sheet
F RAL 9002
266 COUPLING BARRIER WALL
A ( 1ST External surfaces on E P F (150) (2)
CASE )
cladding
B Internal perforated / X / / Grey Lacquered sheets
sheets RAL 9002
C ( 2ND Steelwork structure E P / / Grey
CASE )
(outside configuration) F RAL 7035
280 TURBINE WASHING
A All external surfaces E P / (30) Grey
without insulated F RAL 7035
parts
B Washing tank internal / / / / / Stainless steel
surfaces
C Washing tank external / / / / / Stainless steel
surfaces
2F6 WALKWAYS
(1) GE Energy Products France SNC Standard
(2) Final colour shall be selected by the customer according to one of the following colour range charts :
AFNOR, RAL840HR, BS4800 or 381C or MUNSELL
(3) Total surfaces shall be given later

(4) Colour of lacquered sheets shall be selected in supplier standard restricted colour range
(5) The duct casing will be internally painted (after grid-blasting) on. All carbon steel areas which are not
internally covered by insulation (for example, silencer duct areas where baffles are put on) and a width of
100 mm at the inlet and the outlet borders of the duct casing.
Reference : 168A6553 Rev. : D Section : 01 Page : 17/ 23
Ce document, propriété exclusive de GE Energy Products France SNC This document, exclusive property of GE Energy Products France SNC
est strictement confidentiel. Il ne peut être communiqué, is strictly confidential. It must not be communicated,
copié ou reproduit sans notre autorisation écrite. copied or reproduced without our prior written consent.
GE Energy Products - Europe GENERAL PAINTING SPECIFICATION

ESTIMATED
SYSTEM SURFACE FINAL
ITEM EQUIPMENT SHOP SITE REMARKS
TYPE FOR FINAL COLOUR
COAT IN M²
A HANDRAILS E P F (25) (2)

B GANGWAYS E P F (25) (2)

C GRATINGS / X / / / Hot dip galvanised


steel is not painted
D Ladder bars S2 F / / Light Grey
F10 RAL 7035
F
E Cheked plates (top of S2 F / / Brown light Hot dip galvanised
walkways) F10 Munsell steel
F 10 YR 6/2
2G0 GT GAS FUEL SUPPLY
A All external surfaces E P / / Grey Stainless steel
without insulated F RAL 7035 piping are not
parts painted
(1)
B Paint under insulated A P / / Red 50630 (1)
parts
2JO COMPRESSED AIR SYSTEM (WITH CONTAINER)
A Compressor unit E P / / Light Grey
F RAL 7035
B Air tank capacity / X / / / Galvanised steel not
painted
C Frame E P / / Light Grey
F RAL 7035
D Air cooler E P / /
F Light Grey
RAL 7035 Galvanised steel
or / X / / and stainless steel
are not painted
E Air dryer E P / / Light Grey
F RAL 7035
F Piping E P / / Light Grey
F RAL 7035
Galvanised steel and
or / X / / stainless steel are not
paintedpiping is not
/ painted

(1) GE Energy Products France SNC Standard


(2) Final colour shall be selected by the customer according to one of the following colour range charts :
AFNOR, RAL840HR, BS4800 or 381C or MUNSELL
(3) Total surfaces shall be given later

(4) Colour of lacquered sheets shall be selected in supplier standard restricted colour range
(5) The duct casing will be internally painted (after grid-blasting) on. All carbon steel areas which are not
internally covered by insulation (for example, silencer duct areas where baffles are put on) and a width of
100 mm at the inlet and the outlet borders of the duct casing.
Reference : 168A6553 Rev. : D Section : 01 Page : 18/ 23
Ce document, propriété exclusive de GE Energy Products France SNC This document, exclusive property of GE Energy Products France SNC
est strictement confidentiel. Il ne peut être communiqué, is strictly confidential. It must not be communicated,
copié ou reproduit sans notre autorisation écrite. copied or reproduced without our prior written consent.
GE Energy Products - Europe GENERAL PAINTING SPECIFICATION

ESTIMATED
SYSTEM SURFACE FINAL
ITEM EQUIPMENT SHOP SITE REMARKS
TYPE FOR FINAL COLOUR
COAT IN M²

4 EXHAUST SYSTEM
422– LATERAL EXHAUST
A Internal surfaces S P9 / / Grey Zinc Perforated sheets of
the silencer are in
stainless steel
(1) / (5)
B External surfaces S1 P9 / / Aluminium (1)
without cladding and F9
insulation
C Structure support for E P F (80) (2)
duct
423 INSULATION UNDER EXHAUST
A External surfaces E P F (80) (2)

425 ELBOW AND DOWNSTREAM DUCTING


A Internal surfaces S P9 / / Grey Zinc Perforated sheets of
the silencer are in
stainless steel
(1)
B External surfaces S1 P9 / / Aluminium (1)
without cladding and F9
insulation
432 EXHAUST STACK ON SIDE EXHAUST
A Internal shield / X / / / Internal ferritic
stainless steel
B Internal surface of S P9 / / Grey (1)
external shield
C External surface of S1 P9 / / Grey (1)
external shield F9
(corten)
D Liner belt (corten) S1 P9 / / Grey (1)
F9
E Transition stiffeners S1 P9 / / Grey (1)
(corten) F9
F Access and gangway E P F (3) (2) (1)

(1) GE Energy Products France SNC Standard


(2) Final colour shall be selected by the customer according to one of the following colour range charts :
AFNOR, RAL840HR, BS4800 or 381C or MUNSELL
(3) Total surfaces shall be given later

(4) Colour of lacquered sheets shall be selected in supplier standard restricted colour range
(5) The duct casing will be internally painted (after grid-blasting) on. All carbon steel areas which are not
internally covered by insulation (for example, silencer duct areas where baffles are put on) and a width of
100 mm at the inlet and the outlet borders of the duct casing.
Reference : 168A6553 Rev. : D Section : 01 Page : 19/ 23
Ce document, propriété exclusive de GE Energy Products France SNC This document, exclusive property of GE Energy Products France SNC
est strictement confidentiel. Il ne peut être communiqué, is strictly confidential. It must not be communicated,
copié ou reproduit sans notre autorisation écrite. copied or reproduced without our prior written consent.
GE Energy Products - Europe GENERAL PAINTING SPECIFICATION

ESTIMATED
SYSTEM SURFACE FINAL
ITEM EQUIPMENT SHOP SITE REMARKS
TYPE FOR FINAL COLOUR
COAT IN M²
G Ladder bars S2 F / / Light Grey
F10 RAL 7035
F
H Structure support of E P F (100) (2)
chimney
460 GRID AT GT EXHAUST FOR PERSONNAL PROTECTION
A Wire netting / X / / / Supplier standard
B Structure support E P F (50) (2)

5 GENERATOR & ENERGY EVACUATION


510 GT GENERATOR
A All internal surfaces / X / / / Supplier standard
B All external surfaces / X F (220) (2) Supplier standard

543 GENERATOR ACCESSORY COMPARTMENT


A Internal surfaces / X / / / Supplier standard
B External surfaces E P F (70) (2) Carbon Steel
(GLAC & GNAC)

Or / X / / / Aluminium 5754 or
Stainless Steel 316

Other Aluminium or
Stainless Steel
Or B P F (70) (2) quality (add 50 µm
of 15550, 4508H or
15302 before
applying system B)

(1) GE Energy Products France SNC Standard


(2) Final colour shall be selected by the customer according to one of the following colour range charts :
AFNOR, RAL840HR, BS4800 or 381C or MUNSELL
(3) Total surfaces shall be given later

(4) Colour of lacquered sheets shall be selected in supplier standard restricted colour range
(5) The duct casing will be internally painted (after grid-blasting) on. All carbon steel areas which are not
internally covered by insulation (for example, silencer duct areas where baffles are put on) and a width of
100 mm at the inlet and the outlet borders of the duct casing.
Reference : 168A6553 Rev. : D Section : 01 Page : 20/ 23
Ce document, propriété exclusive de GE Energy Products France SNC This document, exclusive property of GE Energy Products France SNC
est strictement confidentiel. Il ne peut être communiqué, is strictly confidential. It must not be communicated,
copié ou reproduit sans notre autorisation écrite. copied or reproduced without our prior written consent.
GE Energy Products - Europe GENERAL PAINTING SPECIFICATION

ESTIMATED
SYSTEM SURFACE FINAL
ITEM EQUIPMENT SHOP SITE REMARKS
TYPE FOR FINAL COLOUR
COAT IN M²
C External surfaces E P F (50) (2) Carbon Steel
(GLAC & GNAC Bus
Duct)

Or / X / / / Aluminium 5754 or
Stainless Steel 316

Other Aluminium or
Stainless Steel
Or B P F (50) (2) quality (add 50 µm
of 15550, 4508H or
15302 before
applying system B)
D Supporting structure / X / / / Galvanised steel
(100 µm mini)
560 MV BUS DUCTS
A All surfaces / X / / Grey Supplier standard
RAL 7032
B Supporting structure / X / / / Galvanised steel
(100 µm mini)

8 COOLING SYSTEM
811 FIN FAN COOLERS
A Internal surfaces E P / / Light grey (1)
| silencers F RAL 7035
| fans or same as
| plenum external
surfaces
B All external surfaces E P F (200) (2)
| silencers
| fans
| plenum
| water-box
C Expansion tank H P4 / / White
| internal surface F4 11630
D Expansion tank E P F (10) (2)
| external surface
E | Steel structure E P F (30) (2)
F | Pumping skid E P F (10) (2)

(1) GE Energy Products France SNC Standard


(2) Final colour shall be selected by the customer according to one of the following colour range charts :
AFNOR, RAL840HR, BS4800 or 381C or MUNSELL
(3) Total surfaces shall be given later

(4) Colour of lacquered sheets shall be selected in supplier standard restricted colour range
(5) The duct casing will be internally painted (after grid-blasting) on. All carbon steel areas which are not
internally covered by insulation (for example, silencer duct areas where baffles are put on) and a width of
100 mm at the inlet and the outlet borders of the duct casing.
Reference : 168A6553 Rev. : D Section : 01 Page : 21/ 23
Ce document, propriété exclusive de GE Energy Products France SNC This document, exclusive property of GE Energy Products France SNC
est strictement confidentiel. Il ne peut être communiqué, is strictly confidential. It must not be communicated,
copié ou reproduit sans notre autorisation écrite. copied or reproduced without our prior written consent.
GE Energy Products - Europe GENERAL PAINTING SPECIFICATION

ESTIMATED
SYSTEM SURFACE FINAL
ITEM EQUIPMENT SHOP SITE REMARKS
TYPE FOR FINAL COLOUR
COAT IN M²
G Ladder bars S2 F / / Light Grey
F10 RAL 7035
F

9 PIPING SYSTEM
910 PIPING
A Insulated pipes fluid A P / / Red 50630 Stainless steel and
temperature T°< galvanised steel
150°C piping are not
painted
B insulated pipes fluid A' P8 / / Grey Stainless steel and
temperature T° > 19840 galvanised steel
150°C piping are not
painted
C Not insulated pipes E P F (200) (2) Stainless steel and
galvanised steel
piping are not
painted
D Piping supports E P F (50) (2)
E Underground pipes (1) X / / / GE Energy Products
France approved
Supplier standard
* Cold wrapping tape
consisting of a
combinated anti-
corrosive mastic and
pressure sensitive
adhesive laminated to
a robust and flexible
plastic backing

B GT CONTROL & LV DISTRIBUTION


B10 TURBINE CONTROL COMPARTMENT (TCC)
A Package internal / X / / / Supplier standard
surfaces
B Package external E P F (150) (2)
surfaces
B51 GT & GENERATOR AUXILIARIES LV DISTRIBUTION (MCC)

(1) GE Energy Products France SNC Standard


(2) Final colour shall be selected by the customer according to one of the following colour range charts :
AFNOR, RAL840HR, BS4800 or 381C or MUNSELL
(3) Total surfaces shall be given later

(4) Colour of lacquered sheets shall be selected in supplier standard restricted colour range
(5) The duct casing will be internally painted (after grid-blasting) on. All carbon steel areas which are not
internally covered by insulation (for example, silencer duct areas where baffles are put on) and a width of
100 mm at the inlet and the outlet borders of the duct casing.
Reference : 168A6553 Rev. : D Section : 01 Page : 22/ 23
Ce document, propriété exclusive de GE Energy Products France SNC This document, exclusive property of GE Energy Products France SNC
est strictement confidentiel. Il ne peut être communiqué, is strictly confidential. It must not be communicated,
copié ou reproduit sans notre autorisation écrite. copied or reproduced without our prior written consent.
GE Energy Products - Europe GENERAL PAINTING SPECIFICATION

ESTIMATED
SYSTEM SURFACE FINAL
ITEM EQUIPMENT SHOP SITE REMARKS
TYPE FOR FINAL COLOUR
COAT IN M²
A Gt & generator / X / / Grey Supplier standard
auxiliaries lv RAL 7032
distribution (mcc)
B52 125 V DC BATTERY CHARGER CUBICLE
A 125 v dc battery / X / / Grey Supplier standard
charger cubicle RAL 7032

B53 125 V DC BATTERY


A 125 v dc battery / X / / Grey Supplier standard
RAL 7032
A Container battery / X / / / Supplier standard
Internal surfaces
B Container battery E P F (30) (2)
External surfaces

D POWER PLANT ELECTRICAL AUXILIARIES


D11 UNIT STEP UP TRANSFORMER
A Unit step up / X / / Light grey Supplier standard
transformer RAL 7032
D12 AUXILIARY TRANSFORMERS

A Auxiliary transformers / X / / Light grey Supplier standard


RAL 7032
A HV Distribution board / X / / Grey Supplier standard
RAL 7032
/ X / / / Supplier standard
ELECTRICAL MOTORS
PUMPS FANS VALVES
& IN LINE INSTALLED
EQUIPMENTS AND
DEVICES
E P / / Yellow
MANUTENTION & F RAL 1028
MAINTENANCE TOOLS

(1) GE Energy Products France SNC Standard


(2) Final colour shall be selected by the customer according to one of the following colour range charts :
AFNOR, RAL840HR, BS4800 or 381C or MUNSELL
(3) Total surfaces shall be given later

(4) Colour of lacquered sheets shall be selected in supplier standard restricted colour range
(5) The duct casing will be internally painted (after grid-blasting) on. All carbon steel areas which are not
internally covered by insulation (for example, silencer duct areas where baffles are put on) and a width of
100 mm at the inlet and the outlet borders of the duct casing.
Reference : 168A6553 Rev. : D Section : 01 Page : 23/ 23
Ce document, propriété exclusive de GE Energy Products France SNC This document, exclusive property of GE Energy Products France SNC
est strictement confidentiel. Il ne peut être communiqué, is strictly confidential. It must not be communicated,
copié ou reproduit sans notre autorisation écrite. copied or reproduced without our prior written consent.