Alaoji Advisory - 001
Alaoji Advisory - 001
Alaoji Advisory - 001
3 3.5.7.4 Paint Materials Equivalent The above shall apply- refer to the document.
4
Schedule
SN To be amended/added Comments
A level three (L3) schedule of activities
would have been preferrable but the
1 PROJECT SCHEDULE supplied one shown below is okay. Please
confirm if the duration is for all units’
exhaust systems.
Risk Assessment
SN To be amended/added Comments
You shall be submitting your team to
1 Risk Assessment further risk assessment engagement should
the need arise.
A valid medical fitness certificate of at
2 Medical Fitness Certificate least 1 year for your employees will be a
plus but can be waived.
DT-7C
ffi
c ia
l
GE Energy Products - Europe GENERAL PAINTING SPECIFICATION
CONTENTS
STATE OF MODIFICATIONS.................................................................................................................... 2
SPECIFICATION OF ANTI-CORROSION PROTECTING SYSTEMS APPLIED ON THE VARIOUS
EQUIPMENT MENTIONED HEREUNDER............................................................................................. 3
1.TYPE OF PRODUCTS USED..............................................................................................................................3
2.RELEVANT SYSTEM STANDARDS.................................................................................................................5
SUMMARY .................................................................................................................................................... 7
STATE OF MODIFICATIONS
INDEX DATE DESCRIPTION
A 17/02/2005 First issue
AMERON B.V.
78400 CHATOU
Tel : (+33) (0) 1 30 71 50 50
1.4. Remarks
lSee data sheet of products here above mentioned.
lAll the operations of applying anti-corrosion protection coating stated before are carried out
according to the standard general specification n 91–421 666
1.5. Protection of machined surfaces and bored holes
TYPE OF PRODUCT
TYPE A A' B
PROTECTED Insulated equipment Insulated equipment All internal surfaces of
SURFACES equipment and external
(T° < 150°C) (150°C < T < 500°C) surfaces installed within
building
PAINT SPECIFICATIONS P : 80 µm P8 : 50 µm mini P : 80 µm
(Mean dry thickness in F : 60 µm
microns)
SYSTEM STANDARDS ß HEMPADUR 45880 or ß HEMPEL’S SILICONE ß HEMPADUR 45880 or
47200 ZINC 16900 47200
ß HEMPATHANE 55910
TYPE D E H
PROTECTED All external surfaces of All external surfaces of Internal surfaces of fuel
SURFACES equipment exposed to a equipment exposed to a or oil tanks
mild or medium very aggressive
aggressive environment environment
(Maritimes, industrials,
corrosive)
PAINT SPECIFICATIONS P : 110 µm P : 140 µm P4 : 100 µm
(Mean dry thickness in F : 80 µm F : 100 µm F4 : 100 µm
microns)
SYSTEM STANDARDS ß HEMPADUR 45880 or ß HEMPADUR 45880 or ß HEMPADUR 15500
47200 47200 ß HEMPADUR 15500
ß HEMPATHANE 55910 ß HEMPATHANE 55910
TYPE L M N
PROTECTED Very hot surfaces GT External surfaces of Inlet Belmouth air flow
SURFACES (150°C < T° < 500°C), casing surfaces
except GT casing
PAINT SPECIFICATIONS P8 : 40 µm P2 : 75 µm P2 : 75 µm
(Mean dry thickness in F8 : 25 µm F8 : 25 µm P : 20 µm
microns)
F : 80 µm (mist coat technic)
SYSTEM STANDARDS ß HEMPEL’S SILICONE ß HEMPEL’S GALVOSIL ß HEMPEL’S GALVOSIL
ZINC 16900 15700 15700
ß HEMPEL’S SILICONE ß HEMPEL’S SILICONE ß HEMPATHANE 55910
ALUMINIUM 56910 ALUMINIUM 56910
TYPE S S1 S2
PROTECTED Internal surfaces of External surfaces of Surfaces of cheked plates
SURFACES exhaust duct exhaust duct
PAINT SPECIFICATIONS P9 : 65 µm P9 : 65 µm F : 60 mm
(Mean dry thickness in F9 : 50 µm F10 : 0.1kg/m²
microns)
F : 60 mm
SYSTEM STANDARDS ß AMERON ß AMERON DIMECOTE 9 ß HEMPATHANE 55910
DIMECOTE 9 ß AMERON PSX 892 HS ß HEMPEL’S ANTI-SLINT
67500
ß HEMPATHANE 55910
IMPORTANT REMARK:
-1-
When hot dip galvanized steel to be painted: before applying the GEEPE system (D, E …) add a primer coat
(50 µm) of HEMPADUR 15550 (P10A)
When zinc plated sheet on external surfaces to be painted: before applying the GEEPE system (D, E …) add a
primer coat (50 µm) of HEMPADUR 15550 (P10A)
When stainless steel, aluminium or copper to be painted: before applying the GEEPE system (D, E …) add a
primer coat (50 µm) of Hempadur 4508H or Hempadur 15302 (P10B)
When the final coat colour shade is pale (white or cream) use a primer coat of Grey 11480 instead of Red
50630
-2-
FINAL PAINT ON SITE TO BE SUPPLIED BY CUSTOMER.NOT IN GE SCOPE OF SUPPLY
SUMMARY
1 GAS TURBINE WITH ASSOCIATED MODULES................................................................................. 9
100 GAS TURBINE and direct auxiliaries .............................................................................................................9
Item 1605 GT UNIT OFF-BASE ACOUSTICAL ENCLOSURE........................................................................9
Item 1605 TURBINE EXHAUST FRAME COOLING FANS (TK) ACOUSTICAL ENCLOSURE ............10
Item 1605 WATER INJECTION SKID OFF-BASE ACOUSTICAL ENCLOSURE......................................12
Item 1605 GAS COMPARTMENT VENTILATION SKID...............................................................................13
Item 1617 LOAD COMPARTMENT....................................................................................................................13
Item 1643 GAS COMPARTMENT VENTILATION SKID...............................................................................13
Item A014 TURBINE CONTROL PANEL..........................................................................................................14
Item A016 GENERATOR CONTROL PANEL ..................................................................................................14
Item A035 WATER INJECTION SKID...............................................................................................................14
Item A040 SELF CLEANING AIR FILTER .......................................................................................................14
Item A041 VERTICAL INLET DUCT .................................................................................................................15
Item A098 OIL MIST ELIMINATOR SKID.......................................................................................................15
Item A108 EQUIPMENT network tOpology ......................................................................................................16
Item A124 CONTROL SKID.................................................................................................................................16
Item A980 INLET SUPPORTING STRUCTURES ............................................................................................16
Item MS99 EXHAUST PLENUM MODULE ......................................................................................................16
2 TURBINE AUXILIARIES ....................................................................................................................... 16
240 GT UNIT FIRE FIGHTING SYSTEM..........................................................................................................16
266 COUPLING BARRIER WALL......................................................................................................................17
280 TURBINE WASHING.....................................................................................................................................17
2F6 WALKWAYS...................................................................................................................................................17
2G0 GT GAS FUEL SUPPLY ...............................................................................................................................18
2JO COMPRESSED AIR SYSTEM (with container).........................................................................................18
4 EXHAUST SYSTEM ................................................................................................................................ 19
422– LATERAL EXHAUST ..................................................................................................................................19
423 INSULATION UNDER EXHAUST...............................................................................................................19
425 ELBOW AND DOWNSTREAM DUCTING ................................................................................................19
432 EXHAUST STACK ON SIDE EXHAUST ....................................................................................................19
460 GRID AT GT EXHAUST FOR PERSONNAL PROTECTION................................................................20
5 GENERATOR & ENERGY EVACUATION .......................................................................................... 20
ESTIMATED
SYSTEM SURFACE FINAL
ITEM EQUIPMENT SHOP SITE REMARKS
TYPE FOR FINAL COLOUR
COAT IN M²
(4) Colour of lacquered sheets shall be selected in supplier standard restricted colour range
(5) The duct casing will be internally painted (after grid-blasting) on. All carbon steel areas which are not
internally covered by insulation (for example, silencer duct areas where baffles are put on) and a width of
100 mm at the inlet and the outlet borders of the duct casing.
Reference : 168A6553 Rev. : D Section : 01 Page : 9/ 23
Ce document, propriété exclusive de GE Energy Products France SNC This document, exclusive property of GE Energy Products France SNC
est strictement confidentiel. Il ne peut être communiqué, is strictly confidential. It must not be communicated,
copié ou reproduit sans notre autorisation écrite. copied or reproduced without our prior written consent.
GE Energy Products - Europe GENERAL PAINTING SPECIFICATION
ESTIMATED
SYSTEM SURFACE FINAL
ITEM EQUIPMENT SHOP SITE REMARKS
TYPE FOR FINAL COLOUR
COAT IN M²
H DOORS HATCH A P / / Red 50630 Sand blasted SA2.5
Internal surfaces or zinc plated sheet
under acoustical
treatment
I DOORS HATCH E P F 30 (2) Sand blasted SA2.5
External surfaces and or zinc plated sheet
edges
J Miscellaneous B P / / Grey Zinc plated sheet
(partition …) F RAL 7035
K ∑ Fan / X / / / Supplier standard
∑ Electrical motor
L Manutention and / / / / / See at the end of
maintenance tools the specification
VENTILATION
A Internal surfaces for B P / / Grey (1)
air ventilation duct F RAL 7035
(T<150°C) without
acoustical treatment
Item 1605 TURBINE EXHAUST FRAME COOLING FANS (TK) ACOUSTICAL ENCLOSURE
A PANELS OF ROOF / X / / Grey Galvanised and
AND WALL RAL 9002 lacquered sheets
Internal perforated
sheets
(4) Colour of lacquered sheets shall be selected in supplier standard restricted colour range
(5) The duct casing will be internally painted (after grid-blasting) on. All carbon steel areas which are not
internally covered by insulation (for example, silencer duct areas where baffles are put on) and a width of
100 mm at the inlet and the outlet borders of the duct casing.
Reference : 168A6553 Rev. : D Section : 01 Page : 10/ 23
Ce document, propriété exclusive de GE Energy Products France SNC This document, exclusive property of GE Energy Products France SNC
est strictement confidentiel. Il ne peut être communiqué, is strictly confidential. It must not be communicated,
copié ou reproduit sans notre autorisation écrite. copied or reproduced without our prior written consent.
GE Energy Products - Europe GENERAL PAINTING SPECIFICATION
ESTIMATED
SYSTEM SURFACE FINAL
ITEM EQUIPMENT SHOP SITE REMARKS
TYPE FOR FINAL COLOUR
COAT IN M²
B PANELS OF ROOF A P / / Red 50630 Sand blasted SA2.5
AND WALL or zinc plated sheets
Internal surfaces
under acoustical
treatment
C PANELS OF ROOF B P / Grey RAL Sand blasted SA2.5
AND WALL F 9002 or zinc plated sheets
Internal surfaces
D PANELS OF ROOF E P F 40 (2) Sand blasted SA 2.5
AND WALL or zinc plated sheets
External surfaces and
edges
E DOORS HATCH / X / / Grey Galvanised and
Internal perforated RAL 9002 lacquered sheets
sheets
F DOORS HATCH A P / / Red 50630 Sand blasted SA2.5
Internal surfaces or zinc plated sheet
under acoustical
treatment
G DOORS HATCH E P F 4 (2) Sand blasted SA2.5
External surfaces and or zinc plated sheet
edges
H Miscellaneous B P / / Grey Zinc plated sheet
F RAL 7035
VENTILATION
A Internal surfaces for B P / / Grey (1)
air ventilation duct F RAL 7035
(T<150°C) without
acoustical treatment
(4) Colour of lacquered sheets shall be selected in supplier standard restricted colour range
(5) The duct casing will be internally painted (after grid-blasting) on. All carbon steel areas which are not
internally covered by insulation (for example, silencer duct areas where baffles are put on) and a width of
100 mm at the inlet and the outlet borders of the duct casing.
Reference : 168A6553 Rev. : D Section : 01 Page : 11/ 23
Ce document, propriété exclusive de GE Energy Products France SNC This document, exclusive property of GE Energy Products France SNC
est strictement confidentiel. Il ne peut être communiqué, is strictly confidential. It must not be communicated,
copié ou reproduit sans notre autorisation écrite. copied or reproduced without our prior written consent.
GE Energy Products - Europe GENERAL PAINTING SPECIFICATION
ESTIMATED
SYSTEM SURFACE FINAL
ITEM EQUIPMENT SHOP SITE REMARKS
TYPE FOR FINAL COLOUR
COAT IN M²
C External and internal A' P8 / / Grey (1)
surfaces for air 19840
ventilation duct
(T≥150°C) with or
without acoustical
treatment
(4) Colour of lacquered sheets shall be selected in supplier standard restricted colour range
(5) The duct casing will be internally painted (after grid-blasting) on. All carbon steel areas which are not
internally covered by insulation (for example, silencer duct areas where baffles are put on) and a width of
100 mm at the inlet and the outlet borders of the duct casing.
Reference : 168A6553 Rev. : D Section : 01 Page : 12/ 23
Ce document, propriété exclusive de GE Energy Products France SNC This document, exclusive property of GE Energy Products France SNC
est strictement confidentiel. Il ne peut être communiqué, is strictly confidential. It must not be communicated,
copié ou reproduit sans notre autorisation écrite. copied or reproduced without our prior written consent.
GE Energy Products - Europe GENERAL PAINTING SPECIFICATION
ESTIMATED
SYSTEM SURFACE FINAL
ITEM EQUIPMENT SHOP SITE REMARKS
TYPE FOR FINAL COLOUR
COAT IN M²
J Miscellaneous B P / / Grey Zinc plated sheet
(partition …) F RAL 7035
K ∑ Fan / X / / / Supplier standard
∑ Electrical motor
L Manutention and / / / / / See at the end of
maintenance tools the specification
VENTILATION
A Internal surfaces for B P / / Grey (1)
air ventilation duct F RAL 7035
(T<150°C) without
acoustical treatment
(4) Colour of lacquered sheets shall be selected in supplier standard restricted colour range
(5) The duct casing will be internally painted (after grid-blasting) on. All carbon steel areas which are not
internally covered by insulation (for example, silencer duct areas where baffles are put on) and a width of
100 mm at the inlet and the outlet borders of the duct casing.
Reference : 168A6553 Rev. : D Section : 01 Page : 13/ 23
Ce document, propriété exclusive de GE Energy Products France SNC This document, exclusive property of GE Energy Products France SNC
est strictement confidentiel. Il ne peut être communiqué, is strictly confidential. It must not be communicated,
copié ou reproduit sans notre autorisation écrite. copied or reproduced without our prior written consent.
GE Energy Products - Europe GENERAL PAINTING SPECIFICATION
ESTIMATED
SYSTEM SURFACE FINAL
ITEM EQUIPMENT SHOP SITE REMARKS
TYPE FOR FINAL COLOUR
COAT IN M²
P Grey
B Miscellaneous E / / Zinc plated sheet
F RAL 9002
Fan
C / X / / / Supplier standard
Electrical motor
VENTILATION
Internal surfaces for
air ventilation duct P Grey
A B / / (1)
(T<150°C) without F RAL 7035
acoustical treatment
Internal surfaces for
air ventilation duct
B A P / / Red 50630 (1)
(T<150°C) with
acoustical treatment
External surfaces P
C E F (50) (2)
(T<150°C)
Item A014 TURBINE CONTROL PANEL
A Speedtronic / X / / Innovation
Graphite
Item A016 GENERATOR CONTROL PANEL
A Generator control / X / / Grey
panel RAL 7032
Item A035 WATER INJECTION SKID
A Frame D P / / Grey (1)
F RAL 7035
B Steam piping L P8 / / Alu 19000 Stainless steel
F8 piping is not painted
C Trunnion lifting base E P / / Yellow (1)
F RAL 1028
C Water piping D P / / Grey Stainless steel
F RAL 7035 piping is not painted
Item A040 SELF CLEANING AIR FILTER
A Internal surfaces D P / / Grey (1)
clean air side: F RAL 7038
∑ Clean air housing
sheets
∑ Transition duct
sheets
∑ Internal structure
(4) Colour of lacquered sheets shall be selected in supplier standard restricted colour range
(5) The duct casing will be internally painted (after grid-blasting) on. All carbon steel areas which are not
internally covered by insulation (for example, silencer duct areas where baffles are put on) and a width of
100 mm at the inlet and the outlet borders of the duct casing.
Reference : 168A6553 Rev. : D Section : 01 Page : 14/ 23
Ce document, propriété exclusive de GE Energy Products France SNC This document, exclusive property of GE Energy Products France SNC
est strictement confidentiel. Il ne peut être communiqué, is strictly confidential. It must not be communicated,
copié ou reproduit sans notre autorisation écrite. copied or reproduced without our prior written consent.
GE Energy Products - Europe GENERAL PAINTING SPECIFICATION
ESTIMATED
SYSTEM SURFACE FINAL
ITEM EQUIPMENT SHOP SITE REMARKS
TYPE FOR FINAL COLOUR
COAT IN M²
B Dirty air side: D P / / Grey
∑ Internal structure F RAL 7038
C External surfaces E P F (250) (2) Duckboard in hot dip
∑ steel structure galvanised steel are
∑ Clean air housing not painted
sheets
∑ Transition duct
sheets
D Handrails, gangways, E P F (50) (2) Steps are
walkways, ladders galvanised
E SELF CLEANING AIR / X / / / Galvanised
FILTER ACCESS
Gratings
F SELF CLEANING AIR / X / / / Supplier standard
FILTER
Local control panel
G COMPRESSED AIR
PIPEWORK
∑ Piping / X / / / Galvanised steel
∑ Blow pipes / / / / / Aluminium
H EVAPORATIVE E P / / (2) Ladders are
COOLER F galvanised steel
Internal and external
surfaces
Item A041 VERTICAL INLET DUCT
A Internal surfaces D P / / Grey (1)
without noise F RAL 7038
insulation parts
B Paint under noise A P / / Red 50630 (1)
insulation parts
C All external surfaces E P F (120) (2) Duckboard in hot dip
galvanised steel are
not painted
Item A098 OIL MIST ELIMINATOR SKID
A ∑ Motor / X / / RAL 5000 GE Energy Products
∑ Fan Blue France approved
supplier's standard
(4) Colour of lacquered sheets shall be selected in supplier standard restricted colour range
(5) The duct casing will be internally painted (after grid-blasting) on. All carbon steel areas which are not
internally covered by insulation (for example, silencer duct areas where baffles are put on) and a width of
100 mm at the inlet and the outlet borders of the duct casing.
Reference : 168A6553 Rev. : D Section : 01 Page : 15/ 23
Ce document, propriété exclusive de GE Energy Products France SNC This document, exclusive property of GE Energy Products France SNC
est strictement confidentiel. Il ne peut être communiqué, is strictly confidential. It must not be communicated,
copié ou reproduit sans notre autorisation écrite. copied or reproduced without our prior written consent.
GE Energy Products - Europe GENERAL PAINTING SPECIFICATION
ESTIMATED
SYSTEM SURFACE FINAL
ITEM EQUIPMENT SHOP SITE REMARKS
TYPE FOR FINAL COLOUR
COAT IN M²
B ∑ Support legs and B P / / Grey
maintenance F RAL 7035
platform
∑ Silencer
∑ Buffer box
Item A108 EQUIPMENT NETWORK TOPOLOGY
A Equipment network / X / / Grey
topology RAL 7032
Item A124 CONTROL SKID
A Gt local control / X / / Grey Supplier standard
equipment RAL 7032
Item A980 INLET SUPPORTING STRUCTURES
A Steel structure E P F (250) (2)
2 TURBINE AUXILIARIES
240 GT UNIT FIRE FIGHTING SYSTEM
A CO2 bottles / X / / Red Supplier standard
RAL 3000 (100µm mini )
B CO2 rack / X / / / Galvanised steel
not painted
C CO2 piping / X / / / Hot dip galvanised
steel is not painted
D CO2 container E P / / Red (1)
External surfaces F RAL 3000
E CO2 container B P / / White (1)
Internal surfaces F
(4) Colour of lacquered sheets shall be selected in supplier standard restricted colour range
(5) The duct casing will be internally painted (after grid-blasting) on. All carbon steel areas which are not
internally covered by insulation (for example, silencer duct areas where baffles are put on) and a width of
100 mm at the inlet and the outlet borders of the duct casing.
Reference : 168A6553 Rev. : D Section : 01 Page : 16/ 23
Ce document, propriété exclusive de GE Energy Products France SNC This document, exclusive property of GE Energy Products France SNC
est strictement confidentiel. Il ne peut être communiqué, is strictly confidential. It must not be communicated,
copié ou reproduit sans notre autorisation écrite. copied or reproduced without our prior written consent.
GE Energy Products - Europe GENERAL PAINTING SPECIFICATION
ESTIMATED
SYSTEM SURFACE FINAL
ITEM EQUIPMENT SHOP SITE REMARKS
TYPE FOR FINAL COLOUR
COAT IN M²
F Unit fire panel / X / / Light Grey Supplier standard
RAL 7032
262 EXHAUST ACOUSTIC WALL
P Grey
A Steelwork structure E / /
F RAL 7035
PANELS OF WALL
AND ACCES OR
Grey Galvanised and
B DOOR HATCH / X / /
RAL 9002 lacquered sheets
Internal perforated
sheets
PANELS OF WALL
AND ACCES OR
DOOR HATCH Sand blasted SA2.5
C A P / / Red 50630
Internal surfaces or zinc plated sheets
under acoustical
treatment
PANELS OF WALL
AND ACCES OR
P Grey Sand blasted SA 2.5
D DOOR HATCH E / (50)
F RAL 7035 or zinc plated sheets
External surfaces and
edges
P Grey
E Miscellaneous E / / Zinc plated sheet
F RAL 9002
266 COUPLING BARRIER WALL
A ( 1ST External surfaces on E P F (150) (2)
CASE )
cladding
B Internal perforated / X / / Grey Lacquered sheets
sheets RAL 9002
C ( 2ND Steelwork structure E P / / Grey
CASE )
(outside configuration) F RAL 7035
280 TURBINE WASHING
A All external surfaces E P / (30) Grey
without insulated F RAL 7035
parts
B Washing tank internal / / / / / Stainless steel
surfaces
C Washing tank external / / / / / Stainless steel
surfaces
2F6 WALKWAYS
(1) GE Energy Products France SNC Standard
(2) Final colour shall be selected by the customer according to one of the following colour range charts :
AFNOR, RAL840HR, BS4800 or 381C or MUNSELL
(3) Total surfaces shall be given later
(4) Colour of lacquered sheets shall be selected in supplier standard restricted colour range
(5) The duct casing will be internally painted (after grid-blasting) on. All carbon steel areas which are not
internally covered by insulation (for example, silencer duct areas where baffles are put on) and a width of
100 mm at the inlet and the outlet borders of the duct casing.
Reference : 168A6553 Rev. : D Section : 01 Page : 17/ 23
Ce document, propriété exclusive de GE Energy Products France SNC This document, exclusive property of GE Energy Products France SNC
est strictement confidentiel. Il ne peut être communiqué, is strictly confidential. It must not be communicated,
copié ou reproduit sans notre autorisation écrite. copied or reproduced without our prior written consent.
GE Energy Products - Europe GENERAL PAINTING SPECIFICATION
ESTIMATED
SYSTEM SURFACE FINAL
ITEM EQUIPMENT SHOP SITE REMARKS
TYPE FOR FINAL COLOUR
COAT IN M²
A HANDRAILS E P F (25) (2)
(4) Colour of lacquered sheets shall be selected in supplier standard restricted colour range
(5) The duct casing will be internally painted (after grid-blasting) on. All carbon steel areas which are not
internally covered by insulation (for example, silencer duct areas where baffles are put on) and a width of
100 mm at the inlet and the outlet borders of the duct casing.
Reference : 168A6553 Rev. : D Section : 01 Page : 18/ 23
Ce document, propriété exclusive de GE Energy Products France SNC This document, exclusive property of GE Energy Products France SNC
est strictement confidentiel. Il ne peut être communiqué, is strictly confidential. It must not be communicated,
copié ou reproduit sans notre autorisation écrite. copied or reproduced without our prior written consent.
GE Energy Products - Europe GENERAL PAINTING SPECIFICATION
ESTIMATED
SYSTEM SURFACE FINAL
ITEM EQUIPMENT SHOP SITE REMARKS
TYPE FOR FINAL COLOUR
COAT IN M²
4 EXHAUST SYSTEM
422– LATERAL EXHAUST
A Internal surfaces S P9 / / Grey Zinc Perforated sheets of
the silencer are in
stainless steel
(1) / (5)
B External surfaces S1 P9 / / Aluminium (1)
without cladding and F9
insulation
C Structure support for E P F (80) (2)
duct
423 INSULATION UNDER EXHAUST
A External surfaces E P F (80) (2)
(4) Colour of lacquered sheets shall be selected in supplier standard restricted colour range
(5) The duct casing will be internally painted (after grid-blasting) on. All carbon steel areas which are not
internally covered by insulation (for example, silencer duct areas where baffles are put on) and a width of
100 mm at the inlet and the outlet borders of the duct casing.
Reference : 168A6553 Rev. : D Section : 01 Page : 19/ 23
Ce document, propriété exclusive de GE Energy Products France SNC This document, exclusive property of GE Energy Products France SNC
est strictement confidentiel. Il ne peut être communiqué, is strictly confidential. It must not be communicated,
copié ou reproduit sans notre autorisation écrite. copied or reproduced without our prior written consent.
GE Energy Products - Europe GENERAL PAINTING SPECIFICATION
ESTIMATED
SYSTEM SURFACE FINAL
ITEM EQUIPMENT SHOP SITE REMARKS
TYPE FOR FINAL COLOUR
COAT IN M²
G Ladder bars S2 F / / Light Grey
F10 RAL 7035
F
H Structure support of E P F (100) (2)
chimney
460 GRID AT GT EXHAUST FOR PERSONNAL PROTECTION
A Wire netting / X / / / Supplier standard
B Structure support E P F (50) (2)
Or / X / / / Aluminium 5754 or
Stainless Steel 316
Other Aluminium or
Stainless Steel
Or B P F (70) (2) quality (add 50 µm
of 15550, 4508H or
15302 before
applying system B)
(4) Colour of lacquered sheets shall be selected in supplier standard restricted colour range
(5) The duct casing will be internally painted (after grid-blasting) on. All carbon steel areas which are not
internally covered by insulation (for example, silencer duct areas where baffles are put on) and a width of
100 mm at the inlet and the outlet borders of the duct casing.
Reference : 168A6553 Rev. : D Section : 01 Page : 20/ 23
Ce document, propriété exclusive de GE Energy Products France SNC This document, exclusive property of GE Energy Products France SNC
est strictement confidentiel. Il ne peut être communiqué, is strictly confidential. It must not be communicated,
copié ou reproduit sans notre autorisation écrite. copied or reproduced without our prior written consent.
GE Energy Products - Europe GENERAL PAINTING SPECIFICATION
ESTIMATED
SYSTEM SURFACE FINAL
ITEM EQUIPMENT SHOP SITE REMARKS
TYPE FOR FINAL COLOUR
COAT IN M²
C External surfaces E P F (50) (2) Carbon Steel
(GLAC & GNAC Bus
Duct)
Or / X / / / Aluminium 5754 or
Stainless Steel 316
Other Aluminium or
Stainless Steel
Or B P F (50) (2) quality (add 50 µm
of 15550, 4508H or
15302 before
applying system B)
D Supporting structure / X / / / Galvanised steel
(100 µm mini)
560 MV BUS DUCTS
A All surfaces / X / / Grey Supplier standard
RAL 7032
B Supporting structure / X / / / Galvanised steel
(100 µm mini)
8 COOLING SYSTEM
811 FIN FAN COOLERS
A Internal surfaces E P / / Light grey (1)
| silencers F RAL 7035
| fans or same as
| plenum external
surfaces
B All external surfaces E P F (200) (2)
| silencers
| fans
| plenum
| water-box
C Expansion tank H P4 / / White
| internal surface F4 11630
D Expansion tank E P F (10) (2)
| external surface
E | Steel structure E P F (30) (2)
F | Pumping skid E P F (10) (2)
(4) Colour of lacquered sheets shall be selected in supplier standard restricted colour range
(5) The duct casing will be internally painted (after grid-blasting) on. All carbon steel areas which are not
internally covered by insulation (for example, silencer duct areas where baffles are put on) and a width of
100 mm at the inlet and the outlet borders of the duct casing.
Reference : 168A6553 Rev. : D Section : 01 Page : 21/ 23
Ce document, propriété exclusive de GE Energy Products France SNC This document, exclusive property of GE Energy Products France SNC
est strictement confidentiel. Il ne peut être communiqué, is strictly confidential. It must not be communicated,
copié ou reproduit sans notre autorisation écrite. copied or reproduced without our prior written consent.
GE Energy Products - Europe GENERAL PAINTING SPECIFICATION
ESTIMATED
SYSTEM SURFACE FINAL
ITEM EQUIPMENT SHOP SITE REMARKS
TYPE FOR FINAL COLOUR
COAT IN M²
G Ladder bars S2 F / / Light Grey
F10 RAL 7035
F
9 PIPING SYSTEM
910 PIPING
A Insulated pipes fluid A P / / Red 50630 Stainless steel and
temperature T°< galvanised steel
150°C piping are not
painted
B insulated pipes fluid A' P8 / / Grey Stainless steel and
temperature T° > 19840 galvanised steel
150°C piping are not
painted
C Not insulated pipes E P F (200) (2) Stainless steel and
galvanised steel
piping are not
painted
D Piping supports E P F (50) (2)
E Underground pipes (1) X / / / GE Energy Products
France approved
Supplier standard
* Cold wrapping tape
consisting of a
combinated anti-
corrosive mastic and
pressure sensitive
adhesive laminated to
a robust and flexible
plastic backing
(4) Colour of lacquered sheets shall be selected in supplier standard restricted colour range
(5) The duct casing will be internally painted (after grid-blasting) on. All carbon steel areas which are not
internally covered by insulation (for example, silencer duct areas where baffles are put on) and a width of
100 mm at the inlet and the outlet borders of the duct casing.
Reference : 168A6553 Rev. : D Section : 01 Page : 22/ 23
Ce document, propriété exclusive de GE Energy Products France SNC This document, exclusive property of GE Energy Products France SNC
est strictement confidentiel. Il ne peut être communiqué, is strictly confidential. It must not be communicated,
copié ou reproduit sans notre autorisation écrite. copied or reproduced without our prior written consent.
GE Energy Products - Europe GENERAL PAINTING SPECIFICATION
ESTIMATED
SYSTEM SURFACE FINAL
ITEM EQUIPMENT SHOP SITE REMARKS
TYPE FOR FINAL COLOUR
COAT IN M²
A Gt & generator / X / / Grey Supplier standard
auxiliaries lv RAL 7032
distribution (mcc)
B52 125 V DC BATTERY CHARGER CUBICLE
A 125 v dc battery / X / / Grey Supplier standard
charger cubicle RAL 7032
(4) Colour of lacquered sheets shall be selected in supplier standard restricted colour range
(5) The duct casing will be internally painted (after grid-blasting) on. All carbon steel areas which are not
internally covered by insulation (for example, silencer duct areas where baffles are put on) and a width of
100 mm at the inlet and the outlet borders of the duct casing.
Reference : 168A6553 Rev. : D Section : 01 Page : 23/ 23
Ce document, propriété exclusive de GE Energy Products France SNC This document, exclusive property of GE Energy Products France SNC
est strictement confidentiel. Il ne peut être communiqué, is strictly confidential. It must not be communicated,
copié ou reproduit sans notre autorisation écrite. copied or reproduced without our prior written consent.