RE: MIT for R-064 W.H

From: ROO Projects Field Coordinator (rooprojectsfieldcoordinator@roobasra.com)

To: arif.alnubalaa@yahoo.com

Cc: salman.ahmadov@roobasra.com
Date: Thursday, 22 September 2022 at 10:58 GMT+3

Dear Arif,
 
Which QA/QC needs approval? Issued flange A694-F46 has higher grade than A105N, also for 2-1/16”, 3000# and 5000# is same.
 
Please see attached engineering e-mail confirms that.
 
 
Kind regards,
Burak Ozgumus
Material Coordinator
Emails:
roompfc@roobasra.com
 
 

From: ALNUBALAA COORDINATOR <arif.alnubalaa@yahoo.com>

Sent: Thursday, September 22, 2022 10:26 AM

To: ROO Projects Field Coordinator <ROOProjectsFieldCoordinator@roobasra.com>


Subject: Fw: MIT for R-064 W.H

Dear Burak
 
The approved MIT 5005 have FLANGE,PIPE:WELDNECK,2-1/16",3000 PSI,RTJ,CS,A694-F46,SCH
160,API 6A TYPE
6B,EE,PR2,NACE MR0175 
 
but the requested is FLANGE,PIPE:WELDNECK,2-1/16",3000/5000 PSI,RTJ,A105N,SCH
160,API 6A,TYPE 6B

1/11
9/22/22, 11:09 AM Yahoo Mail - RE: MIT for R-064 W.H

 
The existing valve is 5000# class so now QA/QC team need approval to use the approved flange.
 
Is there any approval?
 
 
 

Best Regards 
 

Arif Albarghothy
Al-Nubalaa Project Coordinator 
Mobile # 00964 7834964598
Website: www.alnubalaa.com
Abdul-Kahar Building – 14 - July St.

Mannawi Basha - Basrah - Iraq 

 
 
 
 
----- Forwarded message -----

From: ALNUBALAA COORDINATOR <arif.alnubalaa@yahoo.com>

To: Salman Ahmadov {Petrofac} <salman.ahmadov@roobasra.com>

Sent: Thursday, 22 September 2022 at 10:23:54 GMT+3

Subject: Fw: MIT for R-064 W.H

2/11
9/22/22, 11:09 AM Yahoo Mail - RE: MIT for R-064 W.H

Hi Salman
 
 
The approved MIT 5005 have FLANGE,PIPE:WELDNECK,2-1/16",3000
PSI,RTJ,CS,A694-F46,SCH 160,API 6A TYPE
6B,EE,PR2,NACE MR0175 
 
but the requested is FLANGE,PIPE:WELDNECK,2-1/16",3000/5000
PSI,RTJ,A105N,SCH 160,API 6A,TYPE 6B
 
The existing valve is 5000# class so now QA/QC team need approval to use the approved flange.
 
Is there any approval?
 
 

Best Regards 
 

Arif Albarghothy
Al-Nubalaa Project Coordinator 
Mobile # 00964
7834964598
Website: www.alnubalaa.com
Abdul-Kahar Building – 14 - July St.

Mannawi Basha - Basrah - Iraq 

 
 
 
 

3/11
9/22/22, 11:09 AM Yahoo Mail - RE: MIT for R-064 W.H

----- Forwarded message -----

From: Mohammed Noori Naser Al-Bseeri <mohammednoori.naser@kentplc.com>

To: ALNUBALAA COORDINATOR <arif.alnubalaa@yahoo.com>

Cc: GCMC Construction Manager <GCMCCM@kentplc.com>; roodevprojectcontrol@roobasra.com


<roodevprojectcontrol@roobasra.com>; Sameer
Abdalrasool <sameer.abdalrasool@roobasra.com>

Sent: Wednesday, 11 May 2022 at 13:15:19 GMT+3

Subject: FW: MIT for R-064 W.H

PSA

Yours sincerely

Mohammed Noori
Constructon Team Lead

GCMC Developments

Phone NO:07801538386

Email:
MohammedNoori.naser@kentplc.com

From: Salman Ahmadov


{Petrofac} <Salman.Ahmadov@roobasra.com>
Sent: 11 May 2022 13:05

To: Mohammed Noori Naser


Al-Bseeri <MohammedNoori.Naser@kentplc.com>

Cc: ROO Projects Field Coordinator <ROOProjectsFieldCoordinator@roobasra.com>; roodevprojectcontrol@roobasra.com; Sameer Abdalrasool


<Sameer.Abdalrasool@roobasra.com>; GCMC Construction Manager <GCMCCM@kentplc.com>; ROO PSCM Inventory Manager
<ROOPSCMIM@roobasra.com>;
ROO PSCM Materials Coordinator Projects <ROOPSCMMMT3@roobasra.com>
Subject: RE: MIT for R-064 W.H

  This message is originated outside of Kent.

4/11
9/22/22, 11:09 AM Yahoo Mail - RE: MIT for R-064 W.H

Do not open attachments, click links or respond to requests for information unless you recognize the sender or know the email and the contents are safe.
 

Mohammed,

Please find attached

Regards,

Salman Ahmadov

From: ROO Projects


Field Coordinator <ROOProjectsFieldCoordinator@roobasra.com>

Sent: Wednesday, May 11, 2022 12:15 PM

To: Salman Ahmadov {Petrofac} <Salman.Ahmadov@roobasra.com>


Subject: FW: MIT for R-064 W.H

From: Mohammed Noori Naser Al-Bseeri


Sent: 11 May 2022 11:14:23 (UTC+03:00)
Baghdad
To: ROO Projects Field Coordinator

Cc: GCMC Construction Manager; ROO


Developments Project Control; Sameer Abdalrasool
Subject: FW: MIT for R-064 W.H

Dear Salman,

For your kind approval please

Yours sincerely

Mohammed Noori
Constructon Team Lead

GCMC Developments

Phone NO:07801538386

5/11
9/22/22, 11:09 AM Yahoo Mail - RE: MIT for R-064 W.H

Email:
MohammedNoori.naser@kentplc.com

From: ALNUBALAA
COORDINATOR <arif.alnubalaa@yahoo.com>

Sent: 09 May 2022 11:10

To: Mohammed Noori Naser


Al-Bseeri <MohammedNoori.Naser@kentplc.com>

Cc: Azhar Al Hamadany < pmnubalaa@yahoo.com>;


Sameer Abdalrasool <sameer.abdalrasool@roobasra.com>;
GCMC Construction Manager
<GCMCCM@kentplc.com>;
roodevprojectcontrol@roobasra.com
Subject: MIT for R-064 W.H

This message is originated outside of Kent.


 

Do not open attachments, click links or respond to requests for information unless you recognize the sender or know the
email and the contents are safe.
 

Hi Mohammed

Please find attached MIT for R-064  W.H for approval.

Thanks & Regards,

Arif Albarghothy

Alnubalaa Project Coordinator

+9647834964598
arif.alnubalaa@yahoo.com

6/11
9/22/22, 11:09 AM Yahoo Mail - RE: MIT for R-064 W.H

www.alnubalaa.com
Mannawi Basha - Basra – Iraq

This e-mail (and any attachments) is confidential, it may also be privileged and it is intended for the addressee
only. If you are not the addressee or the
intended recipient, you must not copy, disclose or distribute its contents to any other person. Any liability (in negligence of otherwise) arising from a third
party acting or refraining from acting on any information
contained in this document is expressly excluded. Any views expressed in this email may not
reflect those of any Company or affiliate of the Kent. If you have received this email in error, please notify by return and delete this email from your system

______________________________________________________________________

This email has been scanned by the Symantec Email Security.cloud service.

For more information please visit http://www.symanteccloud.com

______________________________________________________________________

______________________________________________________________________
This email has been scanned by the Symantec Email Security.cloud service.

For more information please visit http://www.symanteccloud.com

______________________________________________________________________

This e-mail (and any attachments) is confidential, it may also be privileged and it is intended for the addressee only. If you are not the addressee or the
intended recipient, you must not copy, disclose or distribute its contents to any other person. Any liability (in negligence of otherwise) arising from a third
party acting or refraining from acting on any information contained in this document is expressly
excluded. Any views expressed in this email may not
reflect those of any Company or affiliate of the Kent. If you have received this email in error, please notify by return and delete this email from your system

Ravi 

Thank you so we will continue with the same flange.

Cheers 
Mustafa
From: Ravi K. Muppavarapu {HQCEC} <ravi.muppavarapu@roobasra.com>
Sent: Tuesday, 12 January 2021, 19:48

To: ROO Projects Field Coordinator; Al Turaihi, Mustafa Amjed; ROO Developments Project Control
Cc: Akat, Batuhan; ROO OPS Lead Mechanical Engineer

Subject: Re: TAAM : R-383 OIL WH - MIT (Pipes ,Fittings ,Skid , Grating &PG)

Mustafa,

I hope TQ is not required for using SC-123186..

7/11
9/22/22, 11:09 AM Yahoo Mail - RE: MIT for R-064 W.H

Regards,
Ravi

From: ROO Projects Field Coordinator


Sent: Tuesday, January 12, 2021 11:46 AM
To: Al Turaihi, Mustafa Amjed; ROO Developments Project Control; Ravi K. Muppavarapu {HQCEC}
Cc: Akat, Batuhan
Subject: RE: TAAM : R-383 OIL WH - MIT (Pipes ,Fittings ,Skid , Grating &PG)
 
Hi Mustafa,
 
SC-123186 was reserved for in stock and ordered for all Wellheads as SPEC item and we don’t have SC-103059 you requested.
 
Hi Mr Guo / Ravi,
 
Could you confirm if we need any TQ for using SC-123186 instead of SC-103059?
Below table shows all 3 items that can be used, but only SC-123186 was ordered for Wellheads.
 
FLANGE,PIPE:WELDNECK,2-1/16",3000
123186 PSI,RTJ,CS,A694-F46,SCH 160,API 6A TYPE SPEC ITEM
6B,EE,PR2,NACE MR0175
FLANGE,PIPE:WELDNECK,2",900/1500 APPROVED
LB,RTJ,CS,A694-F60,SCH 160,ASME BY
106602
B16.5,NACE MR0175 DILEEP/MER
ZHANG
FLANGE,PIPE:WELDNECK,2-  
103059 1/16",3000/5000 LB,RTJ,A105N,SCH
160,API 6A,TYPE 6B
 
 
Regards,

8/11
9/22/22, 11:09 AM Yahoo Mail - RE: MIT for R-064 W.H

Salman
 
From: Al Turaihi, Mustafa Amjed <MustafaAmjed.AlTuraihi@snclavalin.com>

Sent: Tuesday, January 12, 2021 12:01 PM

To: ROO Projects Field Coordinator <ROOProjectsFieldCoordinator@roobasra.com>


Subject: Re: TAAM : R-383 OIL WH - MIT (Pipes ,Fittings ,Skid , Grating &PG)

 
Salman
 
 
For 2 1/16 flange on site its 5000 and as per MIT its 3000 can you please send me tq if there is.
 
Cheers 
Mustafa

From: ROO Projects Field Coordinator <ROOProjectsFieldCoordinator@roobasra.com>


Sent: Monday, December 28, 2020 8:05:29 PM

To: Al Turaihi, Mustafa Amjed <MustafaAmjed.AlTuraihi@snclavalin.com>


Cc: Keskin, Orhan <Orhan.Keskin@snclavalin.com>; Sameer Abdalrasool <Sameer.Abdalrasool@roobasra.com>;


ROO PSCM Rumaila Supply
Base Manager <ROOPSCMRSBM@roobasra.com>; ROO PSCM Materials Coordinator Projects <ROOPSCMMMT3@roobasra.com>
Subject: RE: TAAM : R-383 OIL WH - MIT (Pipes ,Fittings ,Skid , Grating &PG)

 
Hi Mustafa,
Please find attached MIT’s
 
Regards,
Salman
 
From: Al Turaihi, Mustafa Amjed <MustafaAmjed.AlTuraihi@snclavalin.com>

Sent: Monday, December 28, 2020 5:01 PM

To: ROO Projects Field Coordinator <ROOProjectsFieldCoordinator@roobasra.com>


Cc: Keskin, Orhan <Orhan.Keskin@snclavalin.com>; ROO Projects Field Coordinator
<ROOProjectsFieldCoordinator@roobasra.com>;
Sameer
Abdalrasool <Sameer.Abdalrasool@roobasra.com>

Subject: FW: TAAM : R-383 OIL WH - MIT (Pipes ,Fittings ,Skid , Grating &PG)
 
Salman

9/11
9/22/22, 11:09 AM Yahoo Mail - RE: MIT for R-064 W.H

 
For your approval please.
 
Cheers
Mustafa
 
From: Saif Ashour <saif.ashour@taamgroup.com>

Sent: 21 December 2020 11:19

To: Al Turaihi, Mustafa Amjed <MustafaAmjed.AlTuraihi@snclavalin.com>


Cc: Keskin, Orhan <Orhan.Keskin@snclavalin.com>; Sameer Abdalrasool <Sameer.Abdalrasool@roobasra.com>;


ROO Developments Project
Control <ROODevProjectControl@roobasra.com>; Ayman Ajeel - TAAM <ayman.ajeel@taamgroup.com>;
Saif Talib
<saif.talib@taamgroup.com>; TAAM HSE Manager (ROO Project) <Maisar.hse@taamgroup.com>;
Mohammed Haloob
<moh@taamgroup.com>; Hussein A. ALAli <Hussein.Alali@roobasra.com>
Subject: TAAM : R-383 OIL WH - MIT (Pipes ,Fittings ,Skid , Grating &PG)

 
Dear Mr. Mustafa, 
 
Kindly find the attached MIT for R-383 wellhead for your review and approval. 
 
Best Regards. 
 

 
--
Saifaldeen Abdulkareem 
     
Project Engineer
TAAM
ENGINEERING CO.
 
Mobile: +964-7822981934
Mobile: +964-7834469267
E-Mail: saif.ashour@taamgroup.com
Website: www.taamgroup.com
Address: Albrjsuh, Basra, Iraq.
 
 
 

10/11
9/22/22, 11:09 AM Yahoo Mail - RE: MIT for R-064 W.H

______________________________________________________________________
This email has been scanned by the Symantec Email Security.cloud
service.
For more information please visit http://www.symanteccloud.com
______________________________________________________________________

______________________________________________________________________
This email has been scanned by the Symantec Email Security.cloud service.
For more information please visit http://www.symanteccloud.com
______________________________________________________________________

______________________________________________________________________
This email has been scanned by the Symantec Email Security.cloud service.
For more information please visit http://www.symanteccloud.com
______________________________________________________________________
______________________________________________________________________
This email has been scanned by the Symantec Email Security.cloud service.
For more information please visit http://www.symanteccloud.com
______________________________________________________________________

______________________________________________________________________
This email has been scanned by the Symantec Email Security.cloud service.
For more information please visit http://www.symanteccloud.com
______________________________________________________________________

Untitled
44.6kB

11/11

You might also like