I N S TA L L AT I O N 1/19

01

Special applications

Use of direct current apparatus


Variation in magnetic tripping
The thermal-magnetic trip units of the SACE Tmax XT circuit-breakers are suitable for use in direct cur-
rent applications. For the protection thresholds against short-circuits, correction values (Km) must be
used, according to the type of distribution network and to the number of poles to be connected in series
(the thermal threshold does not undergo any alteration).
The correction value to be used can be found in the following tables.

Connection diagrams of poles in an insulated network


Insulated network
Un
+ – + – + – + – + –
insulation function
Protection +

LOAD LOAD LOAD LOAD LOAD

Connection diagrams of poles in a network with one grounded polarity


Network with one grounded polarity
Un
+ – + – + –
insulation function
Protection +

LOAD
LOAD LOAD

+ – + – –
Protection function

LOAD LOAD LOAD

Note: in the considered connections, the earthed polarity is the negative one.
1/20 SACE TMAX XT LOW VOLTAGE MOLDED CASE CIRCUIT-BREAKERS


Special applications

Connection diagrams of poles in switch-disconnectors


Switch-disconnectors
Un
+ – + – + – + – + – + –
insulation function
Protection +

LOAD LOAD LOAD LOAD LOAD LOAD