I ACKNOWLEDGE THAT THE SPECIFICATION REQUIREMENTS HAVE BEEN MET AND THAT THE
DIMENSIONS, CONDITIONS, AND QUANTITIES HAVE BEEN VERIFIED, AS SHOWN OR MODIFIED IN
THE DRAWING.
2. ALL SIZES AND DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE SPECIFIED.
3. ALL CONDUITS FOR FIRE ALARM SYSTEM SHALL BE 20MM DIA.
4. ALL THE CONCEALED CONDUIT IN THE WALL OR FLOOR SHALL BE PVC TYPE WHILE THE EXPOSED
CONDUITS IN THE CEILING OR WALL SHALL BE EMT TYPE FOR LOW CURRENT SYSTEMS.
5. FIRE ALARM SYSTEM CABLE SHALL BE FIRE RATED 105°C, 2x1.5mm² (16AWG) FOR SLC &
2x2.5mm²(14AWG) FOR NAC/AUX POWER SUPPLY CIRCUITS.
6. SPACE BETWEEN ANY DETECTOR AND NEAREST DIFFUSER SHALL NOT BE LESS THAN 3FT
(914)MM.
7. THE CONDUIT ROUTES SHOWN IN THE DRAWINGS ARE INDICATIVE& FOR INFORMATION ONLY
WHERE AS THE ACTUAL ROUTING WILL VARY ACCORDING TO THE SITE CONDITION & IT WILL BE
CO-ORDINATED IN THE SITE TO MAKE PROPER INSTALLATION AND WITHOUT AFFECTING THE
STANDARDS.
8. FIRE DETECTION SYSTEM DESIGN & INSTALLED IN ACCORDANCE WITH NFPA-72 & CIVIL DEFENSE
REQUIRMENTS.
9. DIMENSIONS OF FIRE ALARM DEVICES ARE INDICATIVES ONLY, ACTUAL DIMENSIONS SHALL BE
AS PER SITE CONDITIONS.
10. ALL ABOVE GROUND CONDUITS SHALL BE EMT WHERE SEVERE PHYSICAL DAMAGE OR
HAZARDOUS ENVIRONMENTS AREA (e.g. ROOF, MECHANICAL ROOMS SHALL BE USED RGS
CONDUIT
11. ALL ALARMS AND SIGNALS GENERATED BY FIRE ALARM SYSTEM (CONTROL PANEL) SHALL BE
RECEIVED AND MONITORED BY 2 NO. FIRE ALARM WORKSTATION WITH LICENSED SOFTWARE
LOCATED IN THE RESPECTIVE ZONE OF FIRE FIGHTING STATION.
12. FOR INSTALLATION DETAILS REFER TO GENERAL DETAIL DRAWING NO.
13. FOR ABOVE CEILING DEVICES PROVIDE ACCESS PANEL 600mmx600mm FOR MAINTENANCE.
EL
UP
EL
13 14 15
15 16 17 18 19 20 21 22 23 24 25
38 37 36 35 34 33 32 31 30 29 28
26 12 TOI.
27 11 TOI. 16 17 18 19 20 21 22 23 24 25 26 27
28 10
29 9
30 8
Meeting room 31 1 2 3 4 5 6 7 TOI. EXIT
Close office Close office Close office Close office Close office Close office 32 TOI.
UP
EL 33
TOI. EXIT
HS
Copy area
EL
Copy area
Open Plan
3 Toilets
EL
EL
EXIT
EL EL
TOI. HALL WAY EL
EXIT
EXIT
EXIT
EXIT
TEA ROOM
OPEN TO
BELOW
EL
35 34 33 32 31 30 29 28 27 26 25
24
23
2 22
21
MEETING 20
OPEN TO ROOM 19
EL
BELOW 18
HS
MEETING
ROOM
17
51
REVISIONS
50
1 49
48
NO. DATE DESCRIPTION DRAWN
47
46
36 37 38 39 40 41 42 43 44 45
EL
OPEN TO UP
BELOW
EXIT
HALL WAY
EXIT
TOI.
EL EXIT EL
EL
Open Plan
UP UP
EL
EL
HS
Copy area Copy area
35
34
TOI.
EL 33
32
UP
Close office Close office Close office Close office Close office Close office Close office Close office 31 36 37 38 39 40 41 42
TOI.
30
TOI.
Close office
29 43
28 44
OPEN TO BELOW OPEN TO BELOW
27 45
26
TOI.
25 24 23 22 21 20 52 51 50 49 48 47 46 TOI.
EL
IT ROOM EL EL
EL
EXIT
UP
1
2
3
MOB.NO.+966-501174991
TEL.NO:0114503725
FAX.NO:0114503731
PROJECT:
DRAWINGTITLE
0 1 2 3
A1@1:150 17-OCT.
SI-BAE-1ST-F1-SD-106 00