1.

I ACKNOWLEDGE THAT THE SPECIFICATION REQUIREMENTS HAVE BEEN MET AND THAT THE
DIMENSIONS, CONDITIONS, AND QUANTITIES HAVE BEEN VERIFIED, AS SHOWN OR MODIFIED IN
THE DRAWING.
2. ALL SIZES AND DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE SPECIFIED.
3. ALL CONDUITS FOR FIRE ALARM SYSTEM SHALL BE 20MM DIA.
4. ALL THE CONCEALED CONDUIT IN THE WALL OR FLOOR SHALL BE PVC TYPE WHILE THE EXPOSED
CONDUITS IN THE CEILING OR WALL SHALL BE EMT TYPE FOR LOW CURRENT SYSTEMS.
5. FIRE ALARM SYSTEM CABLE SHALL BE FIRE RATED 105°C, 2x1.5mm² (16AWG) FOR SLC &
2x2.5mm²(14AWG) FOR NAC/AUX POWER SUPPLY CIRCUITS.
6. SPACE BETWEEN ANY DETECTOR AND NEAREST DIFFUSER SHALL NOT BE LESS THAN 3FT
(914)MM.
7. THE CONDUIT ROUTES SHOWN IN THE DRAWINGS ARE INDICATIVE& FOR INFORMATION ONLY
WHERE AS THE ACTUAL ROUTING WILL VARY ACCORDING TO THE SITE CONDITION & IT WILL BE
CO-ORDINATED IN THE SITE TO MAKE PROPER INSTALLATION AND WITHOUT AFFECTING THE
STANDARDS.
8. FIRE DETECTION SYSTEM DESIGN & INSTALLED IN ACCORDANCE WITH NFPA-72 & CIVIL DEFENSE
REQUIRMENTS.
9. DIMENSIONS OF FIRE ALARM DEVICES ARE INDICATIVES ONLY, ACTUAL DIMENSIONS SHALL BE
AS PER SITE CONDITIONS.
10. ALL ABOVE GROUND CONDUITS SHALL BE EMT WHERE SEVERE PHYSICAL DAMAGE OR
HAZARDOUS ENVIRONMENTS AREA (e.g. ROOF, MECHANICAL ROOMS SHALL BE USED RGS
CONDUIT
11. ALL ALARMS AND SIGNALS GENERATED BY FIRE ALARM SYSTEM (CONTROL PANEL) SHALL BE
RECEIVED AND MONITORED BY 2 NO. FIRE ALARM WORKSTATION WITH LICENSED SOFTWARE
LOCATED IN THE RESPECTIVE ZONE OF FIRE FIGHTING STATION.
12. FOR INSTALLATION DETAILS REFER TO GENERAL DETAIL DRAWING NO.
13. FOR ABOVE CEILING DEVICES PROVIDE ACCESS PANEL 600mmx600mm FOR MAINTENANCE.

Systems Room Systems Room


Close office Elec.Room

EL
UP

EL
13 14 15
15 16 17 18 19 20 21 22 23 24 25
38 37 36 35 34 33 32 31 30 29 28
26 12 TOI.
27 11 TOI. 16 17 18 19 20 21 22 23 24 25 26 27
28 10
29 9
30 8
Meeting room 31 1 2 3 4 5 6 7 TOI. EXIT
Close office Close office Close office Close office Close office Close office 32 TOI.
UP
EL 33

TOI. EXIT

HS
Copy area

EL
Copy area
Open Plan
3 Toilets

EL
EL

EXIT
EL EL
TOI. HALL WAY EL

EXIT
EXIT
EXIT
EXIT

TEA ROOM
OPEN TO
BELOW

EL
35 34 33 32 31 30 29 28 27 26 25

24
23
2 22
21
MEETING 20
OPEN TO ROOM 19

EL
BELOW 18
HS
MEETING
ROOM
17
51
REVISIONS
50
1 49
48
NO. DATE DESCRIPTION DRAWN
47
46

36 37 38 39 40 41 42 43 44 45

EL
OPEN TO UP
BELOW

EXIT

HALL WAY

EXIT
TOI.

EL EXIT EL
EL

Open Plan

UP UP
EL

EL

HS
Copy area Copy area
35
34
TOI.
EL 33
32
UP
Close office Close office Close office Close office Close office Close office Close office Close office 31 36 37 38 39 40 41 42
TOI.
30
TOI.
Close office
29 43
28 44
OPEN TO BELOW OPEN TO BELOW
27 45
26
TOI.
25 24 23 22 21 20 52 51 50 49 48 47 46 TOI.

EL
IT ROOM EL EL

EL

EXIT
UP
1
2
3

office office office office EL

MOB.NO.+966-501174991
TEL.NO:0114503725
FAX.NO:0114503731

PROJECT:

AGENCY BUILDING (1)

DRAWINGTITLE

FIRE ALARM LAYOUT


FIRST FLOOR PLAN

ALL DRAWINGS ARE THE SOLE PROPERTY OF SAUDI ICON DRAWINGS


SHALL NOT BE REPRODUCED IN ANYWAY KIND OR FORM WITHOUT
THEIR WRITTEN PERMISSION

0 1 2 3

SCALE DATE DRAWNBY CHECKEDBY APPROVEDBY

A1@1:150 17-OCT.

JOBREF DRAWINGNO. REV.

SI-BAE-1ST-F1-SD-106 00