1.

I ACKNOWLEDGE THAT THE SPECIFICATION REQUIREMENTS HAVE BEEN MET AND THAT THE
DIMENSIONS, CONDITIONS, AND QUANTITIES HAVE BEEN VERIFIED, AS SHOWN OR MODIFIED IN
THE DRAWING.
2. ALL SIZES AND DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE SPECIFIED.
3. ALL CONDUITS FOR FIRE ALARM SYSTEM SHALL BE 20MM DIA.
4. ALL THE CONCEALED CONDUIT IN THE WALL OR FLOOR SHALL BE PVC TYPE WHILE THE EXPOSED
CONDUITS IN THE CEILING OR WALL SHALL BE EMT TYPE FOR LOW CURRENT SYSTEMS.
5. FIRE ALARM SYSTEM CABLE SHALL BE FIRE RATED 105°C, 2x1.5mm² (16AWG) FOR SLC &
2x2.5mm²(14AWG) FOR NAC/AUX POWER SUPPLY CIRCUITS.
6. SPACE BETWEEN ANY DETECTOR AND NEAREST DIFFUSER SHALL NOT BE LESS THAN 3FT
(914)MM.
7. THE CONDUIT ROUTES SHOWN IN THE DRAWINGS ARE INDICATIVE& FOR INFORMATION ONLY
WHERE AS THE ACTUAL ROUTING WILL VARY ACCORDING TO THE SITE CONDITION & IT WILL BE
CO-ORDINATED IN THE SITE TO MAKE PROPER INSTALLATION AND WITHOUT AFFECTING THE
STANDARDS.
8. FIRE DETECTION SYSTEM DESIGN & INSTALLED IN ACCORDANCE WITH NFPA-72 & CIVIL DEFENSE
REQUIRMENTS.
9. DIMENSIONS OF FIRE ALARM DEVICES ARE INDICATIVES ONLY, ACTUAL DIMENSIONS SHALL BE
AS PER SITE CONDITIONS.
10. ALL ABOVE GROUND CONDUITS SHALL BE EMT WHERE SEVERE PHYSICAL DAMAGE OR
HAZARDOUS ENVIRONMENTS AREA (e.g. ROOF, MECHANICAL ROOMS SHALL BE USED RGS
CONDUIT
11. ALL ALARMS AND SIGNALS GENERATED BY FIRE ALARM SYSTEM (CONTROL PANEL) SHALL BE
RECEIVED AND MONITORED BY 2 NO. FIRE ALARM WORKSTATION WITH LICENSED SOFTWARE
LOCATED IN THE RESPECTIVE ZONE OF FIRE FIGHTING STATION.
12. FOR INSTALLATION DETAILS REFER TO GENERAL DETAIL DRAWING NO.
13. FOR ABOVE CEILING DEVICES PROVIDE ACCESS PANEL 600mmx600mm FOR MAINTENANCE.

STORE Prayer Area STORAGE


Close office Waiting Area
‫ىلصم‬

EL
86 85 84 83 82 81 106 105 104 103 102 101 TOI.
87 TOI.
88
89
90
91
94 95 96 97 98 99 100 TOI.
Close office Close office Close office Close office Close office Meeting room
92
UP TOI.
93
94 BUFFET
TOI.
COPY AREA COPY AREA COPY AREA

EL
EL

Elevator 3 Open Plan

EXIT EL EL EL
Toilet
HALL WAY
Open Plan
EL

EXIT
EXIT
EL EXIT

Open Plan
EL EL
Close office

TEA ROOM

DN

EL
93 92 91 90 89 88 87 86 85 84 83

Open Plan

Elevator 2
82
81
ELEVATOR

EL
Close office 106
LOBBY 105
REVISIONS

EL
Close office 104

Elevator 1
NO. DATE DESCRIPTION DRAWN
OPEN TO
94 95 96 97 98 99 100101102 103
BELOW

EL
UP
Close office

STORE

EXIT EL
EL EL HALL WAY

Toilet
EXIT

EL EL EXIT EL
Close office

EL
Waiting Area
Elevator 4
Close office

94
TOI.
93
92 UP
91 TOI.
90
94 95 96 97 98 99 100 TOI.
Close office
89
88
87
TOI.
86 85 84 83 82 81 106 105 104 103 102 101 15 TOI.

EL
Close office IT ROOM
Meeting Room STORE
Close office Conference Room

MOB.NO.+966-501174991
TEL.NO:0114503725
FAX.NO:0114503731

PROJECT:

AGENCY BUILDING (1)

DRAWINGTITLE

FIRE ALARM LAYOUT


THIRD FLOOR PLAN

ALL DRAWINGS ARE THE SOLE PROPERTY OF SAUDI ICON DRAWINGS


SHALL NOT BE REPRODUCED IN ANYWAY KIND OR FORM WITHOUT
THEIR WRITTEN PERMISSION

0 1 2 3

SCALE DATE DRAWNBY CHECKEDBY APPROVEDBY

A1@1:150 17-OCT.

JOBREF DRAWINGNO. REV.

SI-BAE-3RD-F1-SD-108 00