1.

I ACKNOWLEDGE THAT THE SPECIFICATION REQUIREMENTS HAVE BEEN MET AND THAT THE
DIMENSIONS, CONDITIONS, AND QUANTITIES HAVE BEEN VERIFIED, AS SHOWN OR MODIFIED IN
THE DRAWING.
2. ALL SIZES AND DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE SPECIFIED.
3. ALL CONDUITS FOR FIRE ALARM SYSTEM SHALL BE 20MM DIA.
4. ALL THE CONCEALED CONDUIT IN THE WALL OR FLOOR SHALL BE PVC TYPE WHILE THE EXPOSED
CONDUITS IN THE CEILING OR WALL SHALL BE EMT TYPE FOR LOW CURRENT SYSTEMS.
5. FIRE ALARM SYSTEM CABLE SHALL BE FIRE RATED 105°C, 2x1.5mm² (16AWG) FOR SLC &
2x2.5mm²(14AWG) FOR NAC/AUX POWER SUPPLY CIRCUITS.
6. SPACE BETWEEN ANY DETECTOR AND NEAREST DIFFUSER SHALL NOT BE LESS THAN 3FT
(914)MM.
7. THE CONDUIT ROUTES SHOWN IN THE DRAWINGS ARE INDICATIVE& FOR INFORMATION ONLY
WHERE AS THE ACTUAL ROUTING WILL VARY ACCORDING TO THE SITE CONDITION & IT WILL BE
CO-ORDINATED IN THE SITE TO MAKE PROPER INSTALLATION AND WITHOUT AFFECTING THE
STANDARDS.
8. FIRE DETECTION SYSTEM DESIGN & INSTALLED IN ACCORDANCE WITH NFPA-72 & CIVIL DEFENSE
REQUIRMENTS.
9. DIMENSIONS OF FIRE ALARM DEVICES ARE INDICATIVES ONLY, ACTUAL DIMENSIONS SHALL BE
AS PER SITE CONDITIONS.
10. ALL ABOVE GROUND CONDUITS SHALL BE EMT WHERE SEVERE PHYSICAL DAMAGE OR
HAZARDOUS ENVIRONMENTS AREA (e.g. ROOF, MECHANICAL ROOMS SHALL BE USED RGS
CONDUIT
11. ALL ALARMS AND SIGNALS GENERATED BY FIRE ALARM SYSTEM (CONTROL PANEL) SHALL BE
RECEIVED AND MONITORED BY 2 NO. FIRE ALARM WORKSTATION WITH LICENSED SOFTWARE
LOCATED IN THE RESPECTIVE ZONE OF FIRE FIGHTING STATION.
12. FOR INSTALLATION DETAILS REFER TO GENERAL DETAIL DRAWING NO.
13. FOR ABOVE CEILING DEVICES PROVIDE ACCESS PANEL 600mmx600mm FOR MAINTENANCE.

EXIT
UP

UP

F-256

EXIT EL

Close office
Close office

EL
EL
UP
12 11 10 9 8 7 6 5 4 3 2 1
25 24 23 22 21 20 19 18 17 16 15 14 13 TOI. 13
26 12
TOI. Waiting Area 16 17 18 19 20 21 22 23 24 25 26 27

EXIT
27 11
28 10 EXIT
29 9

Elec.Room 30 8
Copy area Copy area 31 1 2 3 4 5 6 7 TOI.
Close office Close office Close office Close office
32 TOI. Female
UP

EL
33 Waiting Area
34
Open Plan 35 TOI.
Copy area Copy area Copy area Copy area

EL
Toilets

Close office
3

Printer area
EXIT EXIT

EL
F-256
EL
TOI. Waiting Area EL

EXIT
EXIT
EL EL
EL
Close office

EXIT
TEA ROOM EL EL
EL
EXIT

EL
Access Control Equipment 35 34 33 32 31 30 29 28 27 26 25

Library

EL
24
23
22
2 21
MEETING
EXIT

ROOM 20
19
MAIN

EL
VIP ROOM 18
ENTRANCE
MEETING
17
16
REVISIONS
ROOM 15
1 14
13
NO. DATE DESCRIPTION DRAWN
12
11

Waiting Area 1 2 3 4 5 6 7 8 9 10

EL
UP

Access Control Equipment


LOBBY
UP
EXIT

EL

EL
EXIT
EL GRASS GRASS EL Close office

EXIT
EXIT
TOI. AUDITORIUM
Waiting Area

EL EL UP UP

EL
EL

Printer area
EXIT EXIT
Close office 4

EL
Open Plan
EL
Copy area Copy area Copy area Copy area

35
34
33
IT room UP
32
Close office Close office Close office Close office Close office Close office Close office 31 1 2 3 4 5 6 7
meeting room OPEN TO ABOVE
30 8
29 9 OPEN TO ABOVE
28 10
27 11
26 12

TOI.

TOI.

TOI.

TOI.

TOI.
15 14 13
25 24 23 22 21 20 19 18 17 16 15

EL
EXIT EL EL

EL EL

EXIT
UP

UP
UP EXIT
1
2
3

STORE STORE STORE STORE

MOB.NO.+966-501174991
TEL.NO:0114503725
FAX.NO:0114503731

PROJECT:

AGENCY BUILDING (1)

DRAWINGTITLE

FIRE ALARM LAYOUT


GROUND FLOOR PLAN

ALL DRAWINGS ARE THE SOLE PROPERTY OF SAUDI ICON DRAWINGS


SHALL NOT BE REPRODUCED IN ANYWAY KIND OR FORM WITHOUT
THEIR WRITTEN PERMISSION

0 1 2 3

SCALE DATE DRAWNBY CHECKEDBY APPROVEDBY

A1@1:150 17-OCT.

JOBREF DRAWINGNO. REV.

SI-BAE-GF-F1-SD-105 00

You might also like