Download as pdf or txt
Download as pdf or txt
You are on page 1of 48

In this catalogue, can be found details of the insulator types developed by Sediver experts based on know-

how from years of research, development and field experience, and in partnership with the most well
known utilities in the world who have chosen toughened glass insulators for use on their overhead lines.

Designed to perform in all kind of environments and contaminated areas, SEDIVER offers toughened glass
insulators with different dielectric shells: standard profile, fog type profile and open profile which conform
to or exceed IEC, ANSI & BS standards.

For specific insulators not presented in this catalogue, or for specific applications such as Extreme
Pollution areas or Direct Current, please contact us.

Consult our on-line catalogue for:

IEC insulators
BS insulators
ANSI insulators

All Sediver Toughened Glass Insulators offer full TRANSPARENCY, nothing is hidden:

No ageing
Easy visual inspection
Safe live line working
Low life cycle cost

Confidence is a matter of TRANSPARENCY


IEC Toughened Glass
Suspension Insulator
Ball and Socket type
40 kN
Standard Fog Type
Profile Profile
UF040CA100 UF040CA110 UF040CJ110 UF040PA110
CATALOGUE N°
CC011NI CC011NI CC011NI CC011NI

IEC class (1) U40B U40BP


MECHANICAL CHARACTERISTICS
Minimum Mechanical Failing load kN 40 40 40 40
DIMENSIONS
Diameter mm 175 175 255 175
Spacing mm 100 110 110 110
Creepage distance mm 195 195 320 295
Metal fitting size (2) 11 11 11 11
ELECTRICAL CHARACTERISTICS (3)
Power frequency withstand voltage
-Dry one minute kV 45 45 70 50
-Wet one minute kV 32 32 40 32
Dry lightning impulse withstand voltage kV 70 70 100 80
Puncture withstand voltage kV 110 110 130 110
PACKING AND SHIPPING DATA
Approx. net weight kg 1.6 1.6 3.2 2.4
Nº of insulators per crate 9 9 6 9
Volume per crate m³ 0.025 0.025 0.05 0.027
Gross weight per crate kg 18.4 18.4 28 25.6
Nº of insulators per pallet 270 270 90 171
Volume per pallet m³ 1.08 1.08 1.26 0.96
Gross weight per pallet kg 580 580 430 510
Former designation 1508BF/100 1508BF/110 F4010/110

Insulators with specific protection against corrosion are also available

(1) in accordance with IEC publication 60305


(2) in accordance with IEC publication 60120
(3) in accordance with IEC publication 60383-1
Toughened Glass
IEC Suspension
Insulator
70 kN Ball and Socket type

Standard Fog Type Open


Profile Profile Profile
UF070CB127 UF070CB146 UF070PG146 UF70PB146 UF070AA127
CATALOGUE N°
CC16ANI CC16ANI CC16ANI CC16ANI CC16ANI

IEC class (1) U70BS U70BL U70BLP


MECHANICAL CHARACTERISTICS
Minimum Mechanical Failing load kN 70 70 70 70 70
DIMENSIONS
Diameter mm 255 255 255 280 380
Spacing mm 127 146 146 146 127
Creepage distance mm 320 320 390 445 350
Metal fitting size (2) 16A 16A 16A 16A 16A
ELECTRICAL CHARACTERISTICS (3)
Power frequency withstand voltage
-Dry one minute kV 70 70 72 80 55
-Wet one minute kV 40 40 42 50 45
Dry lightning impulse withstand voltage kV 100 100 110 125 85
Puncture withstand voltage kV 130 130 130 130 130
PACKING AND SHIPPING DATA
Approx. net weight kg 4 4 4.6 5.8 5.6
Nº of insulators per crate 6 6 6 6 6
Volume per crate m³ 0.058 0.064 0.067 0.079 0.121
Gross weight per crate kg 28 28 31.6 38.8 37.6
Nº of insulators per pallet 90 90 90 ???? 90
Volume per pallet m³ 1.26 1.31 1.31 1.24 2.08
Gross weight per pallet kg 450 450 500 490 590
Former designation F70/127 F70/146 F70P/146 F70D/127

Insulators with specific protection against corrosion are also available

(1) in accordance with IEC publication 60305


(2) in accordance with IEC publication 60120
(3) in accordance with IEC publication 60383-1
Toughened
Glass
IEC Suspension
Insulator
100 kN Ball and Socket
type
Standard Fog Type Open
Profile Profile Profile
UF100CB127 UF100CB146 UF100PG146 UF100PB146 UF100AA127
CATALOGUE N°
CC16ANI CC16ANI CC16ANI CC16ANI CC16ANI

IEC class (1) U100BS U100BL U100BLP


MECHANICAL CHARACTERISTICS
Minimum Mechanical Failing load kN 100 100 100 100 100
DIMENSIONS
Diameter mm 255 255 255 280 380
Spacing mm 127 146 146 146 127
Creepage distance mm 320 320 390 445 350
Metal fitting size (2) 16A 16A 16A 16A 16A
ELECTRICAL CHARACTERISTICS (3)
Power frequency withstand voltage
-Dry one minute kV 70 70 72 80 55
-Wet one minute kV 40 40 42 50 45
Dry lightning impulse withstand voltage kV 100 100 110 125 85
Puncture withstand voltage kV 130 130 130 130 130
PACKING AND SHIPPING DATA
Approx. net weight kg 3.9 4 4.6 5.8 5.6
Nº of insulators per crate 6 6 6 6 6
Volume per crate m³ 0.058 0.064 0.067 0.079 0.121
Gross weight per crate kg 27.4 28 31.6 38.8 37.6
Nº of insulators per pallet 90 90 90 72 90
Volume per pallet m³ 1.26 1.31 1.31 1.24 2.08
Gross weight per pallet kg 440 450 500 490 590
Former designation F100/127 F100/146 F9P/146 F100P/146 F100D/127

Insulators with specific protection against corrosion are also available

(1) in accordance with IEC publication 60305


(2) in accordance with IEC publication 60120
(3) in accordance with IEC publication 60383-1
Toughened Glass
IEC Suspension
Insulator
Ball and Socket
120 kN type

Standard Fog Type Open


Profile Profile Profile
UF120CB127 UF120CB146 UF120PG146 UF120PB146 UF120AB127
CATALOGUE N°
CC16ANI CC16ANI CC16ANI CC16ANI CC16ANI

IEC class (1) U120B U120BLP


MECHANICAL CHARACTERISTICS
Minimum Mechanical Failing load kN 120 120 120 120 120
DIMENSIONS
Diameter mm 255 255 255 280 380
Spacing mm 127 146 146 146 127
Creepage distance mm 320 320 390 445 365
Metal fitting size (2) 16A 16A 16A 16A 16A
ELECTRICAL CHARACTERISTICS (3)
Power frequency withstand voltage
-Dry one minute kV 70 70 72 80 60
-Wet one minute kV 40 40 42 50 50
Dry lightning impulse withstand voltage kV 100 100 110 125 90
Puncture withstand voltage kV 130 130 130 130 130
PACKING AND SHIPPING DATA
Approx. net weight kg 4 4 4.6 5.8 5.6
Nº of insulators per crate 6 6 6 6 6
Volume per crate m³ 0.058 0.064 0.067 0.079 0.121
Gross weight per crate kg 28 28 31.6 38.8 37.6
Nº of insulators per pallet 90 90 90 72 90
Volume per pallet m³ 1.31 1.31 1.31 1.24 2.08
Gross weight per pallet kg 450 450 500 490 590
Former designation F12/127 F12/146 F12P/146 F120P/146 F12D/127

Insulators with specific protection against corrosion are also available

(1) in accordance with IEC publication 60305


(2) in accordance with IEC publication 60120
(3) in accordance with IEC publication 60383-1

<
Toughened Glass
IEC Suspension
Insulator
Ball and Socket
160 kN type

Standard Fog Type Open


Profile Profile Profile
UF160CK146 UF160CK170 UF160PF146 UF160PF170 UF160AD146
CATALOGUE N°
CC020NI CC020NI CC020NI CC020NI CC020NI

IEC class (1) U160BS U160BL U160BSP U160BLP


MECHANICAL CHARACTERISTICS
Minimum Mechanical Failing load kN 160 160 160 160 160
DIMENSIONS
Diameter mm 280 280 330 330 420
Spacing mm 146 170 146 170 146
Creepage distance mm 390 390 545 545 375
Metal fitting size (2) 20 20 20 20 20
ELECTRICAL CHARACTERISTICS (3)
Power frequency withstand voltage
-Dry one minute kV 75 75 90 90 90
-Wet one minute kV 45 45 55 55 50
Dry lightning impulse withstand voltage kV 110 110 140 140 90
Puncture withstand voltage kV 130 130 130 130 130
PACKING AND SHIPPING DATA
Approx. net weight kg 6 6.5 8.8 8.9 8
Nº of insulators per crate 6 6 6 6 6
Volume per crate m³ 0.079 0.090 0.108 0.122 0.166
Gross weight per crate kg 41 44 57.8 58.4 53
Nº of insulators per pallet 72 72 54 54 72
Volume per pallet m³ 1.24 1.39 1.22 1.50 2.45
Gross weight per pallet kg 520 550 550 550 660
Former designation F160/146 F160/170 F160P/146 F160P/170 F160D/146

Insulators with specific protection against corrosion are also available

(1) in accordance with IEC publication 60305


(2) in accordance with IEC publication 60120
(3) in accordance with IEC publication 60383-1
Toughened Glass
IEC Suspension
Insulator
Ball and Socket
210 kN type

Standard Fog Type Open


Profile Profile Profile
UF210CZ170 UF210PP170 UF210AC170
CATALOGUE N°
CC020NI CC020NI CC020NI

IEC class (1) U210B U210BP


MECHANICAL CHARACTERISTICS
Minimum Mechanical Failing load kN 210 210 210
DIMENSIONS
Diameter mm 280 330 420
Spacing mm 170 170 170
Creepage distance mm 380 550 375
Metal fitting size (2) 20 20 20
ELECTRICAL CHARACTERISTICS (3)
Power frequency withstand voltage
-Dry one minute kV 75 90 60
-Wet one minute kV 45 55 50
Dry lightning impulse withstand
kV 110 140 90
voltage
Puncture withstand voltage kV 130 130 130
PACKING AND SHIPPING DATA
Approx. net weight kg 7.2 10.2 8.9
No. of insulators per crate 6 6 6
Volume per crate m3 0.090 0.122 0.166
Gross weight per crate kg 48.2 66.2 58.4
No of insulators per pallet 72 54 72
Volume per pallet m3 1.39 1.50 2.45
Gross weight per pallet kg 600 620 720
Former designation F21/170 F210P/170 F21D/170

Insulators with specific protection against corrosion are also available

(1) in accordance with IEC publication 60305


(2) in accordance with IEC publication 60120
(3) in accordance with IEC publication 60383-1
IEC Toughened Glass
Suspension Insulator
Ball and Socket type
240 kN
Standard
Profile
UF240CZ170
CATALOGUE N°
CC024NI

IEC class (1)


MECHANICAL CHARACTERISTICS
Minimum Mechanical Failing load kN 240
DIMENSIONS
Diameter mm 280
Spacing mm 170
Creepage distance mm 380
Metal fitting size (2) 24
ELECTRICAL CHARACTERISTICS (3)
Power frequency withstand voltage
-Dry one minute kV 75
-Wet one minute kV 45
Dry lightning impulse withstand voltage kV 110
Puncture withstand voltage kV 130
PACKING AND SHIPPING DATA
Approx. net weight kg 7.5
Nº of insulators per crate 6
Volume per crate m³ 0.090
Gross weight per crate kg 50
Nº of insulators per pallet 72
Volume per pallet m³ 1.39
Gross weight per pallet kg 630
Former designation F24/170

Insulators with specific protection against corrosion are also available

(1) in accordance with IEC publication 60305


(2) in accordance with IEC publication 60120
(3) in accordance with IEC publication 60383-1
IEC Toughened Glass
Suspension Insulator
Ball and Socket type
300 kN
Standard Fog Type
Profile Profile
UF300CH195 UF300PK195 UF300PJ195
CATALOGUE N°
CC024NI CC024NI CC024NI

IEC class (1) U300B U300BP U300BP


MECHANICAL CHARACTERISTICS
Minimum Mechanical Failing load kN 300 300 300
DIMENSIONS
Diameter mm 330 380 320
Spacing mm 195 195 195
Creepage distance mm 485 690 595
Metal fitting size (2) 24 24 24
ELECTRICAL CHARACTERISTICS (3)
Power frequency withstand voltage
-Dry one minute kV 85 100 85
-Wet one minute kV 50 55 50
Dry lightning impulse withstand
kV 130 150 130
voltage
Puncture withstand voltage kV 130 130 130
PACKING AND SHIPPING DATA
Approx. net weight kg 10.9 15.3 11.1
No. of insulators per crate 5 3 5
Volume per crate m3 0.11 0.9 0.11
Gross weight per crate kg 57.5 48 58.5
No of insulators per pallet 45 54 45
Volume per pallet m3 1.34 2.1 1.34
Gross weight per pallet kg 555 950 551
Former designation F300/195 F300P/195

Insulators with specific protection against corrosion are also available

(1) in accordance with IEC publication 60305


(2) in accordance with IEC publication 60120
(3) in accordance with IEC publication 60383-1
Toughened Glass
IEC Suspension
Insulator
Ball and Socket
400 kN type

Standard
Profile
UF400CX205
CATALOGUE N°
CC028NI

IEC class (1) U400B


MECHANICAL CHARACTERISTICS
Minimum Mechanical Failing load kN 400
DIMENSIONS
Diameter mm 360
Spacing mm 205
Creepage distance mm 550
Metal fitting size (2) 28
ELECTRICAL CHARACTERISTICS (3)
Power frequency withstand voltage
-Dry one minute kV 90
-Wet one minute kV 55
Dry lightning impulse withstand voltage kV 140
Puncture withstand voltage kV 130
PACKING AND SHIPPING DATA
Approx. net weight kg 14
Nº of insulators per crate 2
Volume per crate m³ 0.8
Gross weight per crate kg 33
Nº of insulators per pallet 48
Volume per pallet m³ 2
Gross weight per pallet kg 840
Former designation F400/205

Insulators with specific protection against corrosion are also available

(1) in accordance with IEC publication 60305


(2) in accordance with IEC publication 60120
(3) in accordance with IEC publication 60383-1
IEC Toughened Glass
Suspension Insulator
Ball and Socket type
530 kN
Standard
Profile
UF530CM240
CATALOGUE N°
CC032NI

IEC class (1)


MECHANICAL CHARACTERISTICS
Minimum Mechanical Failing load kN 530
DIMENSIONS
Diameter mm 330
Spacing mm 240
Creepage distance mm 460
Metal fitting size (2) 32
ELECTRICAL CHARACTERISTICS (3)
Power frequency withstand voltage
-Dry one minute kV 85
-Wet one minute kV 45
Dry lightning impulse withstand voltage kV 125
Puncture withstand voltage kV 130
PACKING AND SHIPPING DATA
Approx. net weight kg 17.6
Nº of insulators per crate 2
Volume per crate m³ 0.1
Gross weight per crate kg 48
Nº of insulators per pallet 48
Volume per pallet m³ 1.6
Gross weight per pallet kg 932
Former designation F530/240

Insulators with specific protection against corrosion are also available

(1) in accordance with IEC publication 60305


(2) in accordance with IEC publication 60120
(3) in accordance with IEC publication 60383-1
Toughened Glass
ANSI Suspension Insulator
Clevis - Tongue type
70 kN Ball Socket type

Standard Standard
Profile Profile
CT070CJ146 NN070CB146
CATALOGUE N°
CC004NI CC03BNI

ANSI class (1) 52.4 52.3


MECHANICAL CHARACTERISTIC
Combined M&E Strength kN 70 70
lbs 15000 15000
Impact strength m.N 45 45
inch-pounds 400 400
Tension proof kN 35 35
lbs 7500 7500
Time load kN 45 45
lbs 10000 10000
DIMENSIONS
Diameter mm 255 255
Inches 10 10
Spacing mm 146 146
Inches 5 3/4 5 3/4
Leakage distance mm 320 320
Inches 12 5/8 12 5/8
Metal fitting type (1) Clevis type BS type B
ELECTRICAL CHARACTERISTICS (1) (2)
Low frequency dry flashover kV 80 80
Low frequency wet flashover kV 50 50
Critical impulse flashover pos. kV 125 125
Critical impulse flashover neg. kV 130 130
Low frequency puncture voltage kV 130 130
R.I.V Low frequency test voltage kV 10 10
Max. RIV at 1 MHz µV 50 50
PACKING AND SHIPPING DATA
Approx. net weight kg 3.6 4
Nº of insulators per crate 6 6
Volume per crate m³ 0.064 0.064
Gross weight per crate kg 25.6 28
Nº of insulators per pallet 90 90
Volume per pallet m³ 1.31 1.31
Gross weight per pallet kg 430 450
Former designation CT70/146 N70/146

Insulators with specific protection against corrosion are also available


(1) in accordance with ANSI C29.2
(2) in accordance with ANSI C29.1

We also supply a range of custom products which are not shown here, for example insulators with different spacing.
Please contact our sales department for more details.
ANSI Toughened Glass
Suspension Insulator
Ball &Socket type
100 kN
Standard Fog Type
Profile Profile
NN100CB146 NN100PB146
CATALOGUE N°
CC03BNI CC03BNI
ANSI class (1)
MECHANICAL CHARACTERISTIC
Combined M&E Strength kN 100 100
lbs 22000 22000
Impact strength m.N 45 45
inch-pounds 400 400
Tension proof kN 50 50
lbs 11000 11000
Time load kN 70 70
lbs 15000 15000
DIMENSIONS
Diameter mm 255 280
Inches 10 11
Spacing mm 146 146
Inches 5 3/4 5 3/4
Leakage distance mm 320 445
Inches 12 5/8 17 1/2
Metal fitting type (1) BS type B BS type B
ELECTRICAL CHARACTERISTICS (1, 2)
Low frequency dry flashover kV 80 100
Low frequency wet flashover kV 50 60
Critical impulse flashover pos. kV 125 140
Critical impulse flashover neg. kV 130 140
Low frequency puncture voltage kV 130 130
R.I.V Low frequency test voltage kV 10 10
Max. RIV at 1 MHz µV 50 50
PACKING AND SHIPPING DATA
Approx. net weight kg 4 5.8
Nº of insulators per crate 6 6
Volume per crate m³ 0.064 0.079
Gross weight per crate kg 28 38.8
Nº of insulators per pallet 90 72
Volume per pallet m³ 1.31 1.24
Gross weight per pallet kg 450 490
Former designation N100/146 N100P/146
Insulators with specific protection against corrosion are also available
(1) in accordance with ANSI C29.2
(2) in accordance with ANSI C29.1

For insulators with different spacing, please contact us


Toughened Glass
ANSI Suspension Insulator
Clevis - Tongue type
120 kN Ball &Socket type

Standard Standard Fog Type


Profile Profile Profile
CT120CB146 NN120CB146 NN120PB146
CATALOGUE N°
CC006NI CC05JNI CC05JNI

ANSI class (1) 52-6 52-5


MECHANICAL CHARACTERISTIC
Combined M&E Strength kN 120 120 120
lbs 25000 25000 25000
Impact strength m.N 45 45 45
inch-pounds 400 400 400
Tension proof kN 60 60 60
lbs 12500 12500 12500
Time load kN 70 70 70
lbs 15000 15000 15000
DIMENSIONS
Diameter mm 255 255 280
Inches 10 10 11
Spacing mm 146 146 146
Inches 5 3/4 5 3/4 5 3/4
Leakage distance mm 320 320 445
Inches 12 5/8 12 5/8 17 1/2
Metal fitting type (1) Clevis type BS type J BS type J
ELECTRICAL CHARACTERISTICS (1) (2)
Low frequency dry flashover kV 80 80 100
Low frequency wet flashover kV 50 50 60
Critical impulse flashover pos. kV 125 125 140
Critical impulse flashover neg. kV 130 130 140
Low frequency puncture voltage kV 130 130 130
R.I.V Low frequency test voltage kV 10 10 10
Max. RIV at 1 MHz µV 50 50 50
PACKING AND SHIPPING DATA
Approx. net weight kg 4 4 5.8
No. of insulators per crate 6 6 6
Volume per crate m³ 0.064 0.064 0.079
Gross weight per crate kg 28.9 28 38.8
No of insulators per pallet 90 90 72
Volume per pallet m³ 1.31 1.31 1.24
Gross weight per pallet kg 450 450 490
Former designation CT12/146 N12/146 N120P/146

Insulators with specific protection against corrosion are also available


(1) in accordance with ANSI C29.2
(2) in accordance with ANSI C29.1

We also supply a range of custom products which are not shown here, for example insulators with different spacing.
Please contact our sales department for more details.
ANSI Toughened Glass
Suspension Insulator

160/ Clevis - Tongue type


Ball &Socket type
180 kN
Standard Standard Fog Type
Profile Profile Profile
CT160CK165 NN160CK146 NN160PF171
CATALOGUE N°
CC010NI CC08KNI CC08KNI

ANSI class (1) 52-10 52-8


MECHANICAL CHARACTERISTICS
Combined M&E Strength kN 180 160 160
lbs 36000 36000 36000
Impact strength m.N 45 45 45
inch-pounds 400 400 400
Tension proof load kN 80 80 80
lbs 18000 18000 18000
Time load kN 110 110 110
lbs 24000 24000 24000
DIMENSIONS
Diameter mm 280 280 330
Inches 11 11 13
Spacing mm 165 146 171
Inches 6 1/2 5 3/4 6 3/4
Leakage distance mm 380 380 545
Inches 15 15 211/2
Metal fitting type (1) Clevis BS type K BS type K
ELECTRICAL CHARACTERISTICS (1) (2)
Low frequency dry flashover kV 85 80 105
Low frequency wet flashover kV 55 50 65
Critical impulse flashover pos. kV 130 125 170
Critical impulse flashover neg. kV 135 130 160
Low frequency puncture voltage kV 130 130 130
R.I.V Low frequency test voltage kV 10 10 10
Max. RIV at 1 MHz µV 50 50 50
PACKING AND SHIPPING DATA
Approx. net weight kg 6.1 6 8.8
No. of insulators per crate 6 6 6
Volume per crate m³ 0.085 0.079 0.108
Gross weight per crate kg 41 41 57.8
No of insulators per pallet 72 72 54
Volume per pallet m³ 1.24 1.24 1.22
Gross weight per pallet kg 520 520 550
Former designation CT160/165 N160/146 N160P/171

Insulators with specific protection against corrosion are also available


(1) in accordance with ANSI C29.2
(2) in accordance with ANSI C29.1

We also supply a range of custom products which are not shown here, for example insulators with different spacing.
Please contact our sales department for more details.
ANSI Toughened Glass
Suspension Insulator
Ball Socket type
220 kN
Standard
Profile
NN220CZ156
CATALOGUE N°
C11KNI

ANSI class (1) 52-11


MECHANICAL CHARACTERISTIC
Combined M&E Strength kN 220
lbs 50000
Impact strength m.N 45
inch-pounds 400
Tension proof kN 110
lbs 25000
Time load kN 135
lbs 30000
DIMENSIONS
Diameter mm 280
Inches 11
Spacing mm 156
Inches 6 1/8
Leakage distance mm 380
Inches 15
Metal fitting type (1) BS type K
ELECTRICAL CHARACTERISTICS (1) (2)
Low frequency dry flashover kV 80
Low frequency wet flashover kV 50
Critical impulse flashover pos. kV 140
Critical impulse flashover neg. kV 140
Low frequency puncture voltage kV 130
R.I.V Low frequency test voltage kV 10
Max. RIV at 1 MHz µV 50
PACKING AND SHIPPING DATA
Approx. net weight kg 7.2
No. of insulators per crate 6
Volume per crate m³ 0.090
Gross weight per crate kg 49
No of insulators per pallet 72
Volume per pallet m³ 1.39
Gross weight per pallet kg 600
Former designation N21/156

Insulators with specific protection against corrosion are also available


(1) in accordance with ANSI C29.2
(2) in accordance with ANSI C29.1

We also supply a range of custom products which are not shown here, for example insulators with different spacing.
Please contact our sales department for more details.
BS
Toughened Glass
Suspension Insulator
80/ Ball and Socket type

120 kN
Standard Fog Type Open
Profile Profile Profile
BW080CB140 BW120CB 146 BW080PG146 BW080PB140 BW080AA146
CATALOGUE N°
CC16BNI CC16BNI CC16BNI CC16BNI CC16BNI

MECHANICAL CHARACTERISTICS
Minimum Mechanical Failing load kN 80 120 80 80 80
DIMENSIONS
Diameter mm 255 255 255 280 380
Spacing mm 140 146 146 140 146
Creepage distance mm 320 320 390 445 350
Metal fitting size (1) 16B 16B 16B 16B 16B
Locking device designation W W W W W
ELECTRICAL CHARACTERISTICS (2)
Power frequency withstand voltage
-Dry one minute kV 70 70 72 80 55
-Wet one minute kV 40 40 42 50 45
Dry lightning impulse withstand voltage kV 100 100 110 125 85
Puncture withstand voltage kV 130 130 130 130 130
PACKING AND SHIPPING DATA
Approx. net weight kg 4 4 5 5.8 5.6
Nº of insulators per crate 6 6 6 6 6
Volume per crate m³ 0.064 0.064 0.067 0.079 0.122
Gross weight per crate kg 28 28 34 38.8 37.6
Nº of insulators per pallet 90 90 90 72 90
Volume per pallet m³ 1.31 1.31 1.31 1.24 2.08
Gross weight per pallet kg 450 450 500 490 590
Former designation B8/140 B12/146 B8P/146 B80P/140 B80D/146

Insulators with specific protection against corrosion are also available


(1) in accordance with IEC publication 60120 & BS 3288
(2) in accordance with IEC publication 60383-1 & BS 60383-1

For specific markets we also supply a range of custom products which are not shown here.
Please contact our sales department for more details.
Toughened Glass
BS Suspension
Insulator
Ball and Socket
125 kN type

Standard Fog Type Open


Profile Profile Profile
BW125CB140 BW125CB178 BW125PB146 BW125AA140
CATALOGUE N°
CC020NI CC020NI CC020NI CC020NI

MECHANICAL CHARACTERISTICS
Minimum Mechanical Failing load kN 125 125 125 125
DIMENSIONS
Diameter mm 255 255 280 380
Spacing mm 140 178 146 140
Creepage distance mm 320 320 445 350
Metal fitting size (1) 20 20 20 20
Locking device designation W W W W
ELECTRICAL CHARACTERISTICS (2)
Power frequency withstand voltage
-Dry one minute kV 70 70 80 55
-Wet one minute kV 40 40 50 45
Dry lightning impulse withstand voltage kV 100 100 125 85
Puncture withstand voltage kV 130 130 130 130
PACKING AND SHIPPING DATA
Approx. net weight kg 4.4 4.4 5.8 5.6
Nº of insulators per crate 6 6 6 6
Volume per crate m³ 0.061 0.063 0.079 0.122
Gross weight per crate kg 29.9 29.9 38.8 37.6
Nº of insulators per pallet 90 90 72 90
Volume per pallet m³ 1.31 1.35 1.24 2.08
Gross weight per pallet kg 450 450 490 590
Former designation B13/140 B130/178 B130P/146 B13D/140

Insulators with specific protection against corrosion are also available


(1) in accordance with IEC 60120 & BS 3288
(2) in accordance with IEC 60383-1 & BS 60383-1

For specific markets we also supply a range of custom products which are not shown here.
Toughened Glass
BS Suspension
Insulator
Ball and Socket
160 kN type

Standard Fog Type Open


Profile Profile Profile
BW160CK146 BW160PF170 BW160AD146
CATALOGUE N°
CC020NI CC020NI CC020NI

MECHANICAL CHARACTERISTICS
Minimum Mechanical Failing load kN 160 160 160
DIMENSIONS
Diameter mm 280 330 420
Spacing mm 146 170 146
Creepage distance mm 390 545 375
Metal fitting size (1) 20 20 20
Locking device designation W W W
ELECTRICAL CHARACTERISTICS (2)
Power frequency withstand voltage
-Dry one minute kV 75 90 60
-Wet one minute kV 45 55 50
Dry lightning impulse withstand voltage kV 110 140 90
Puncture withstand voltage kV 130 130 130
PACKING AND SHIPPING DATA
Approx. net weight kg 6 8.8 8
Nº of insulators per crate 6 6 6
Volume per crate m³ 0.079 0.108 0.166
Gross weight per crate kg 41 57.8 52
Nº of insulators per pallet 72 54 72
Volume per pallet m³ 1.24 1.22 2.45
Gross weight per pallet kg 520 550 660
Former designation B160/146 B160P/170 B160D/146

Insulators with specific protection against corrosion are also available


(1) in accordance with IEC publication 60120 & BS 3288
(2) in accordance with IEC publication 60383-1 & BS 60383-1

For specific markets we also supply a range of custom products which are not shown here.
Please contact our sales department for more details.
Toughened Glass
BS Suspension
Insulator
190 kN Ball and Socket type
Standard Fog Type
Profile Profile
BW190CZ200 BW190PP170
CATALOGUE N°
CC024NB CC024NB

MECHANICAL CHARACTERISTICS
Minimum Mechanical Failing load kN 190 190
DIMENSIONS
Diameter mm 280 330
Spacing mm 200 170
Creepage distance mm 382 550
Metal fitting size (1) 24 24
Locking device designation W W
ELECTRICAL CHARACTERISTICS (2)
Power frequency withstand voltage
-Dry one minute kV 75 90
-Wet one minute kV 45 55
Dry lightning impulse withstand voltage kV 110 140
Puncture withstand voltage kV 130 130
PACKING AND SHIPPING DATA
Approx. net weight kg 7.2 10.2
Nº of insulators per crate 6 6
Volume per crate m³ 0.090 0.122
Gross weight per crate kg 48.2 66.2
Nº of insulators per pallet 72 54
Volume per pallet m³ 1.39 1.50
Gross weight per pallet kg 600 620
Former designation B190P/170

Insulators with specific protection against corrosion are also available


(1) in accordance with IEC publication 60120 & BS 3288
(2) in accordance with IEC publication 60383-1 & BS 60383-1

For specific markets we also supply a range of custom products which are not shown here.
Please contact our sales department for more details.
Standard
Profile

Fog Type
Profile

Open
Profile

Standard
Profile

Fog Type
Profile
The packing and palletizing methods employed by SEDIVER are the result of experience gained from having
shipped hundreds of millions of its toughened glass Insulators to user warehouses and construction sites in 120
countries worldwide, and from extensive tests performed by packing research organizations. The packing
methods described and illustrated below have been developed expressly to minimize any possible damage
during shipment and storage.

The wood used for packing is either standard or treated against insects according to country regulations or/and
customer specification.

- Factory-assembled strings of - External wire bindings are - Crates are evenly stacked on a
SEDIVER Insulators are packed in designed to keep crates firmly sturdy four-way wooden pallet.
wooden crates, which are closed, and to allow easy and This assembly is held tightly in
reinforced and held closed by rapid opening at time of place with either steel or plastic
external wire bindings. A crate is installation with no need for bands, and is protected against
shown here in the open position, special tools. moisture by a complete covering
and is internally braced to permit of polyethylene film.
stacking.
Sediver is proposing a wide range of products for different applications in the field of insulation and
protection for transmission & distribution networks, and railways.
For further details, please contact us.

Armourlite ® EPDM or
Armoursil ® Silicone composite
long rod insulator for
heavy polluted area and
severe vandalism application

Braced line post, line post,


and jumper loop for compact line
application in urban areas and
for lower impact on environment

Light weight composite insulators Composite surge arrester


for phase spacer application for HV & EHV lines protection
Toughened glass station post Composite station post Composite station surge arrester,
Class II & III

Composite or
toughened glass
strut & top tie insulator
for railway application

Composite tie top insulator


for distribution application

Toughened glass pin type insulator


for distribution application

You might also like