Download as pdf or txt
Download as pdf or txt
You are on page 1of 26

PRICE BID

FOR
66/11KV GIS SUBSTATION
ESIC MEDICAL COLLEGE FARIDABAD

U.P. RAJKIYA NIRMAN NIGAM LTD

ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 1
PROJECT : ESIC HOSPITAL AT FARIDABAD
66KV SUBSTATION ESTIMATE FOR 4 BAY

PART - A : 66KV GIS SUBSTATION


S.No. DESCRIPTION QTY. UNIT RATE AMOUNT

1.0 66 KV METERING SIDE EQUIPMENT

1.1 Supply, installation, testing and commissioning of outdoor type


60 kV, 10KA Lightning Surge Arrestor (1 Phase) complete in
everyway with outdoor junction boxes suitable, connectors,
hardware, accessories, terminals for LV wiring complete in
everyway. 3 Nos

1.2 Supply, installation, testing and commissioning of outdoor type


66kV (3 Phase) double Break Isolator .

a) 1250 A, 31.5kA, Isolator with one E/S complete in everyway


with outdoor junction boxes, terminals for LV wiring, all
suitable connectors, hardware, accessories complete in every
way. 1 No

1.3 Supply, installation, testing and commissioning of outdoor type


72 kV SF6 Circuit Breaker (3 phase) .

a) 1250A, 31.5kA SF6 CB complete in everyway with operating


kiosk, complete pedestal and mounting supports, terminals for
LV wiring inside kiosk, suitable connectors, hardware,
accessories complete in every way. 1 No

1.4 Supply, installation, testing and commissioning of outdoor type


66 kV (3 core) Current Transformer (1 Phase) .

a) 150/1 A, 31.5kA 10VA CT class 0.2 for metering class


complete in everyway with outdoor junction boxes, terminals for
LV wiring. (suitable for 12MVA), connectors, hardware,
accessories complete in every way. 3 Nos

b) 150/1+1+1+1 A, 30 VA 31.5kA CT 5P20 protection class for


main protection, PS class for differential, PS class for distance
protection, 5P20 class as spare complete in everyway with
outdoor junction boxes, terminals for LV wiring. (suitable for 12
MVA), suitable connectors, hardware, accesories complete in
every way. 3 Nos

1.5 Supply, installation, testing and commissioning of outdoor type


Potential Transformer (1 Phase).
a) 66 kV /√3/110v/√3/110v/√3 outdoor type single phase PT class
0.2/3P, 100 VA burden complete in everyway with outdoor
junction boxes, terminals for LV wiring, suitable connectors,
hardware, accessories complete in every way. 3 Nos

ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 2
S.No. DESCRIPTION QTY. UNIT RATE AMOUNT

1.6 Supply, installation, testing and commissioning of outdoor type


72kV Bus Post Insulator complete in everyway. 3 Nos

1.7 Supply, installation, testing and commissioning of 66kV


relay control panel for metering side breaker.

a 66 kV Line feeder control & relay protection panel with Mimic


Diagram, semaphore indication for isolator and breaker, TNC
switch for breaker operation, phase indication, breaker ON/OFF
status, breaker trip status, 1 no. numerical communicable over
current and earth fault relay with both IDMT and instantaneous
elements, under voltage and over voltage relay, under frequency,
over frequency relay, 1 no. numerical communicable differential
protection, 1 no. trip circuit supervision relay, 1 no. master trip
relay, 1 no. voltmeter with selector, 1 no. ammeter with selector,
1 no. trivector meter with max. demand controller, minimum 8
window annunciator and buzzer, complete in everyway inclusive
of making discrimination curve. This differential relay has to
communicate with differential relay on sending end. Necessary
communication system has to be inbuilt.
1 No

b Supply, installation, testing & commissioning of HF


communication cable between 2 nos. differential relay at
sending end and receiving end. 3500 Mtrs.

1.8 ERECTION HARDWARE MATERIAL

1.8.1 Supply, installation, testing and commissioning of ACSR


Leopard conductor & complete with all accessories, hardware,
connectors complete in everyway. 50 Mtrs

1.8.2 Supply, installation, testing and commissioning of Sundary


Items
a) Earth wire (16 SWG) 50 Mtrs
b) PG for E/W 4 Nos
c) Tension clamp for E/W 4 Nos
d) Pad type clamp for E/W 4 Nos
e) Cleat type clamp for E/W 4 Nos
f) Bay marshalling kiosk 1 No
g) 100mm Dia PVC Pipe 5 Mtrs

1.8.3 STRUCTURE

Supplying, galvanising, erection, making, grouting and


commissioning of galvanised steel structure for following items
mentioned below and structure shall be as per HVPN practice
(All foundation drg. will be given by contractor as per HVPN
specifications and same will be approved by structure &
electrical consultants). Steel structure drg. shall be given by
vendor for approval by structral consultants giving wind
pressure, bending moment etc. with proper drawings.

ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 3
S.No. DESCRIPTION QTY. UNIT RATE AMOUNT

- 2 sets of outdoor current transformers (3 nos. each set)

- 1 set outdoor potentioal transformer (3 nos.)

- 1 set outdoor isolators with earthing blades.

- 1 sets lightning arrestor

- 1 sets outdoor type SF6 insulated breaker.

- 1 set cable sealing end.

- Square fence as specified upto 2.4m high and covering top 0.3m
with chain link wire painted with silver colour paint. All fence &
gate shall be painted with galvanised paint.

- Gate at least 4m wide and painted with silver colour paint. 8000 Kg

Sub Total of 66KV Metering Side Equipment

2.0 66KV GIS EQUIPMENTS

2.1 FOUR BAY INDOOR TYPE DOUBLE BUS GAS


INSULATED SWITCHGEAR.

a Supply, installation, testing and commissioning of 66 kV indoor


GIS with double bus arrangement system with 4 nos bays
(One incomer and two outgoings and Bus coupler) as under and
conforming to specification enclosed & latest HVPN
specifications as applicable .

b 1 No. double bus line bay for 66KV, 1250 Amps, 31.5KA for 1
sec SF6 gas insulated line bay module comprising of 3 nos.
single phase gas insulated voltage tranformer (66KV /R3 /110
/R3 / 110 /R3, this will be equipped with integrated
disconnecting facility for GIS and power cable testing without
any additional dismantelling and gas handling) 100VA burden
class 0.2 / 3P, 1 no. high speed safety ground switch, 1 no. disc
connector switch with earthing switch, 1 no. 1250A 31.5KA
fixed type SF6 insulated circuit breaker, 1 no. isolator with
earthing switch, 3 nos. single phase current transformer
(150/1+1+1A) with 5P20 / 0.2 accuracy / 5P20, 2 nos. isolator
with earthing switch (this will connect to 2 different buses in gas
insulated double busbar system), local control & monitoring
system for complete bay showing density of SF6 gas,
interlocking between component, gas insulated female terminal
connection for connecting cable line with GIS through insulated
interconnection bus etc to complete feeder bay module.

ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 4
S.No. DESCRIPTION QTY. UNIT RATE AMOUNT

c 2 Nos. Double Bus Transformer Bay Module : 66KV, 1250A,


31.5KA for 1 sec. SF6 gas insulated each comprising of 2 nos.
isolator with earthing switch, 1 no. 1250A 66KV GIS, 3 nos.
single phase CT 120/1+1+1+1 having protection class as PS
/5P20/ 0.2/ PS 20VA burden, 1 no. isolator switch with earthing
along with female terminal connection for connecting cable with
GIS through insulated interconnection bus etc to complete
transformer bay module. This will have local control centre for
showing density of SF6 gas, interlocking between component,
monitoring gas and other parameters.

d Bus Coupler in Double Bus Bar Bay : 1 no. bus coupler bay
module comprising of 2 nos. isolator switch with earthing, 3
nos. single phase CT (150/1+1A) 15VA burden 5P20/ 5P20
protection class, 1 no. 1250A SF6 insulated circuit breaker. This
will have local control centre for showing density of SF6 gas,
interlocking between component, monitoring gas and other
parameters.

e Double Bus Bars : 66KV, 3 single phase (isolated) 31.5KA for


1 sec., SF6 gas insulated, metal enclosed 1250A bus bars each
enclosed in bus enclosures running along the length of the
switchgear to interconnect each of circuit breaker bay module.
1 Lot

2.2 Supply, installation, testing and commissioning of outdoor type


60 kV ,10KA Lightning Surge Arrestor (1 Phase) complete in
everyway with outdoor junction boxes, terminals for LV wiring.
6 Nos

2.3 Supply, installation, testing and commissioning of 50mm hollow


alm. tube & complete with all accessories, connectors,
hardwares.
30 Mtrs

Sub Total of 66KV GIS Equipments

3.0 TRANSFORMER

3.1 POWER TRANSFORMER

ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 5
S.No. DESCRIPTION QTY. UNIT RATE AMOUNT

3.1.1 Supply, installation, testing and commissioning of Outdoor type


8/8MVA, 66 KV/11KV, 50 cycle 3 phase delta/star, Oil filled
ONAF, double copper wound TRANSFORMER including
automatic and manual On Load Tap Changer with RTCC and
AVR, including all standard fittings, accessories and instruments
complete as per specifications and as required. Transformer
shall be provided with Open Air Bushing with Arching Horn on
66 KV suitable for Leopard conductor and 11KV side cable box
with alm. gland plate for 2 x 1c x 400sqmm alm armoured
XLPE (UE) cable . The transformer shall have 20% voltage
variation 16 steps with 4 taps on plus side & balance on minus
0 0
side. The temp. rise shall be 40 in oil 50 in winding.

The transformer shall have magnetic oil level guage with trip &
alarm contacts, air cell conservator, surge relay with trip &
alarm contacts, buckholz double float relay, winding temp.
meter with trip & alarm contacts, oil temp. meter with trip &
alarm contacts. The transformer losses shall be 10KW for NO
Load (max. guaranteed), 60KW for Load Losses (max.
guaranteed) and 2KW auxiliary losses for 8MVA rating during
ONAF condition. This shall have neutral CT on LV star side
with 2 neutral CT's ratio 200/1 PS class /5P20. The transformer
will have alm. gland plate on 11KV side for terminating single
core 11KV (UE) cables. This installation shall include all
supply, installation and termination of control cables between
transformer OLTC & RTCC along with incoming cable for
OLTC, lighting inside the marshalling box.
2 Nos

3.1.2 Supply, installation, testing & commissioning of 11 KV indoor


cubicle type neutral isolator cum NGR as per IEEE norms the
specification enclosed and shall be rated for 47ohms, 140A for
30 sec. with suitable space for 11KV (UE) cable terminations.
The NGR panel shall include 1 no. 400A load isolator, 1 no.
temp. meter to indicate enclosure temp., 1 no. CT, 1 no. earth
fault relay, NGR manufactured out of stainless steel punched
grid with overall temp. limit of 375 deg. The load isolator and
earth fault relay shall be wired upto relay control panel for
remote monitoring.
2 Nos

3.2 STATION TRANSFORMER

Supply, unloading, placing, erection on foundation, testing and


commissioning of 100KVA oil filled, 11KV/415V, copper
wound outdoor type, weather proof type transformer (impedence
4%-5%) with bushing / terminal on HT & LT side and with +5%
to -10% tap on HT side. HT side will have bushing and LT side
will have cable box. This shall have oil temperature guage along
with all safeties.
1 No

Sub Total of Transformer

ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 6
S.No. DESCRIPTION QTY. UNIT RATE AMOUNT

4.0 MECHANICAL AUXILIARIES & MANDATORY


SPARES

4.1 Supply, installation, testing and commissioning of Mechanical


auxiliaries which will include ventilation system, fire fighting
system, EOT crane 5 ton capacity as required complete in GIS
room. 1 No

4.2 Design, manufacture of nitrogen gas based protection system for


2X8MVA transformers. 1 Lot

4.3 Supply, installation, testing & commissioning of SF6 gas filling


and evacuating plant 5 kg. capacity. 2 Sets

4.4 Supply, installation, testing & commissioning of SF6 gas


leakage detector. 2 Sets

Sub Total of Electrical Operated Crane

5.0 RELAY CONTROL PANEL

5.1 Supply, installation, testing and commissioning of 66kV


relay control panel.

a 66 kV Line feeder control & relay protection panel with Mimic


Diagram, semaphore indication for isolator and breaker, TNC
switch for breaker operation, phase indication, breaker ON/OFF
status, breaker trip status, numerical over current and earth fault
relay with both IDMT and instantaneous elements, under voltage
and over voltage relay, under frequency, over frequency relay,
trip circuit supervision relay, master trip relay, 1 no. voltmeter
with selector, 1 no. ammeter with selector, 1 no. trivector meter
with max. demand controller, minimum 8 window annunciator
and buzzer, complete in everyway inclusive of making
discrimination curve for different upstream & down stream
breakers. 1 No

b 66 kV Transformer feeder control & relay protection panel with


mimic diagram, semaphore indication for isolator and breaker,
TNC switch for breaker operation, phase indication, breaker
ON/OFF status, breaker trip status, 1 no. numerical differntial
relay, 1 no. numerical over current and earth fault relay with
both IDMT and instantaneous elements, 1 no. numerical REF
relay, 1 no. numerical standby earth fault relay with definite
minimum time, 1 no. over excitation / over flux relay, 1 no. trip
circuit supervision relay, 1 no. master trip relay, 3 nos.
transformer auxiliary relays, 1 no. digital multifunction meter,
minimum 12 window annunciator and buzzer, complete in
everyway inclusive of making discrimination curve for up
stream & down stream breaker. 2 No

ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 7
S.No. DESCRIPTION QTY. UNIT RATE AMOUNT

c 66 kV bus coupler control & relay protection panel with Mimic


Diagram, semaphore indication for isolator and breaker, TNC
switch for breaker operation, phase indication, breaker ON/OFF
status, breaker trip status, numerical over current and earth fault
relay with both IDMT and instantaneous elements, trip circuit
supervision relay, master trip relay, minimum 8 window
annunciator and buzzer, complete in everyway inclusive of
making discrimination curve for different upstream & down
stream breakers. 1 No

Sub Total of Relay Control Panel

6.0 BATTERY & BATTERY CHARGER

6.1 Supply, assembling, installation electrolyte filling, carryuing out


the recommended cycles of charges and discharges before final
charging, connecting up, bank forming, testing, rectification and
commissioning of all the equipments for the 220V DC,
following battery bank and associated equipment conforming to
detailed specifications enclosed in this document. The other
details are as follows.

- The rated voltage output equals to 220V DC consisting of


required number of lead acid cell of 2V each with specific
gravity tester.

- Capacity will be 125 Amp hours.

- The supply to include treated wooden fabricated free standing


floor mounted rack with Acid resistant finished for housing the
batteries

- Complete with series connecting electrical leads an output


connection box, electrolyte for the batteries. 1 No

6.2 Supply, installation, testing and commissioning of the constan


current automatic separate float and float cum boost battery
charger, specified in this docment earlier and having the
following features.

- Input supply 230V AC single phase

- Output suitable to charge lead acid battery bank of 220V D.C

- Maximum current output will be 25Amps trickle charge.

- All necessary indication

- 1 No. of moving coil ammeter and voltmeter

- Indicating light for power On, battery undercharging and trickle


charging

- 1 No. D.C distribution board with 8 nos. DP outgoing MCB's.

- The charger to be housed in sheet steel enclosure with louvers


and cooling fans. 1 No
ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 8
S.No. DESCRIPTION QTY. UNIT RATE AMOUNT

Sub Total of Battery & Battery Charger

7.0 HT CABLES

7.1 Supply, laying, installation, testing & commissionig of 1C X


400sqmm alm. 11 KV (UE) XLPE alm. armoured cable for
phases. 120 Rmt

7.2 Supply, laying, installation, testing & commissionig of 1c X


300sqmm alm. 11 KV (UE) XLPE alm. armoured cable for
neutral earthing. 40 Rmt

7.3 Supply, installation, testing and commissioning of 11 kV


outdoor type cable termination kit for 1c X 400sqmm alm.
11KV (UE) alm. armoured cable for 8MVA Trafo, complete
with all accessories. (1 set means 3c on one side of cables).
2 Sets

7.4 Supply, installation, testing and commissioning of 11 kV indoor


cable termination kit for 1c X 400sqmm alm. 11KV (UE) alm.
armoured cable for 8MVA Trafo complete with all accessories.
(1 set means 3c on one side of cables).
2 Sets

7.5 Supply, laying, installation, testing & commissionig of 3c X


185sqmm alm. 11 KV (UE) armoured XLPE cable for 100KVA
station transformer. 40 Rmt

7.6 Supply, installation, testing and commissioning of 11 kV


outdoor type cable termination kit for 3c X 185sqmm alm.
11KV (UE) cable for 100KVA station transformer, complete
with all accessories. (1 set means 3c on one side of cables). 1 Sets

7.7 Supply, installation, testing and commissioning of 11 kV indoor


cable termination kit for 3c X 185sqmm alm. 11KV (UE) cable
for 100KVA station transformer, complete with all accessories.
1 Sets

7.8 Supply, laying, installation, testing & commissionig of 3c X


240sqmm 11 KV (UE) XLPE alm armoured cable conforming
to IS 7098 II 700 Rmt

7.9 Supply, laying, installation, testing & commissionig of 3c X


300sqmm 11 KV (UE) XLPE alm armoured cable conforming
to IS 7098 II 2800 Rmt

7.10 Supply, installation, testing and commissioning of 11 kV indoor


cable termination kit for 3c X 240sqmm 11KV (UE) cable
complete with all accessories. 2 Sets

ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 9
S.No. DESCRIPTION QTY. UNIT RATE AMOUNT

7.11 Supply, installation, testing and commissioning of 11 kV indoor


cable termination kit for 3c X 300sqmm 11KV (UE) alm
armoured cable complete with all accessories.
8 Sets

Sub Total of HT Cables

8.0 H.T. PANEL BOARD

(11 Panel 11 KV Expandable Type H.T. VCB Board


Comprising of 2 no. Incoming, 1 no. bus coupler , 8nos.
Outgoing feeder ).

Supply of 11 panels 11KV HT VCB Board. VCB panel shall


comprise of following items.

Note: All spare contacts of breaker or any other equipment


inside the breaker shall be wired upto the outgoing terminal strip
with appropriate ferrules / coding. The terminal strip rating shall
be suitable for connecting two wires of 2.5sqmm subjected to
providing minimum size strip suitable for 4/6 sqmm.

The bidder shall indicate battery Ah with supportive calculation


for each panel separately.The bidder shall submit calculation for
knee point & excitation current for different CT's.

8.1a Incomer : Two numbers of 11KV VCB feeder. Each incomer


will comprise of following :

- 1 number 1250 Amps 18 KA VCB circuit breaker horizontally


insulated horizontal drawout, electrical motor operated, spring
charged with facility of manual closing. Incomer feeder shall be
suitable to terminate 2X1cX400sq.mm cable per phase.

- 3nos CT 600/1+1+1+1+1 amps (PS class/PS class/5P20/0.2/PS


class) 20VA burden CT with 0.2 accuracy,PS class for
differential ,PS class for REF,5P20 for over current and earth
fault ,5P20 protection class for metering, one no PS class as
spare .

- 1 No. 3 phase 11KV / √3 /110V/√3/110V/√3 drawout PT with


100VA burden and class 0.2/3P accuracy.This shall be suitable
for resistively earthed system & PT shall with duty cycle of 1.9
times for 30sec.

- 1 no. digital MFM.


- One local / remote switch for operation.

- One emergency OFF push button outside.

- Spring charge status.

- Annunciator window with minimum 8 windows with hooter.

ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 10
S.No. DESCRIPTION QTY. UNIT RATE AMOUNT

- 1 set indicating light for breaker ON/OFF & indicating light for
D.C circuit healthy, indicating light for three phases along with
voltmeter & voltmeter selector switch.

- One no. numerical microprocessor based separate three phase


over current with earth fault relay having IDMT and
instantaneous elements, 1no. trip circuit supervision relay, 1no.
master trip relay, ON / OFF / TRIP indications. Only master trip
relay, trip supervision relay are electro mechanical. All the
indicating lamps should be brought to terminal strip for remote
indication.

- Auto / Manual switch. In Manual mode it shall have local TNC


switch for operation.

- Separate indication for each electrical fault.

- 1 number 220V DC shunt trip coil and 220V DC closing coil .

- 1 number circuit for remote tripping & closing of the breaker


through a potential free contact.

- 1 Set of HRC fuses, control wiring, protection wiring, and other


item required for the desired operation of the unit selector switch
to indicate the currents.

- Minimum 8 window annunciator for all electrical fault.

- Buzzer.

8.1b Bus Coupler: One numbers 1250 Amps 18KA VCB circuit
breaker horizontal insulated horizontal drawout, electrical motor
operated, spring charged with facility of manual closing as bus
coupler with protections of over current and earth fault.

8.1c Outgoing : Three numbers of 11KV VCB feeders. ( outgoing


breaker feeder shall comprise of :

- 1 number 630 Amps 18KA VCB circuit breaker horizontally


insulated horizontal drawout, electrical motor operated, spring
charged with facility of manual closing.

- 3 number combined 500/1+1A current transformers. Cast resin


class 1.0 accuracy 15 VA minimum burden for metering class &
5P20 of 15VA burden for protection. The CT shall have shorting
links.

- 1 No. digital MFM.


- One local / remote switch for operation.

- One emergency OFF push button outside.


ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 11
S.No. DESCRIPTION QTY. UNIT RATE AMOUNT

- Spring charge status.

- Annunciator window with minimum 8 windows with hooter.

- 1 set indicating light for breaker ON/OFF & indicating light for
D.C circuit healthy, indicating light for three phases.

- One no. numerical microprocessor based separate three phase


over current with earth fault relay having IDMT and
instantaneous elements, 1no. trip circuit supervision relay, 1no.
master trip relay, ON / OFF / TRIP indications. Only master trip
relay, trip supervision relay is electro mechanical. All the
indicating lamps should be brought to terminal strip for remote
indication.

- Auto / Manual switch. In manual mode it shall have local TNC


switch for operation.

- Separate indication for each electrical fault.

- 1 number 220V DC shunt trip coil and 220V DC closing coil .

- 1 number circuit for remote tripping & closing of the breaker


through a potential free contact.

- 1 Set of HRC fuses, control wiring, protection wiring, and other


item required for the desired operation of the unit selector switch
to indicate the currents.

- Annunciator window for all electrical fault.

8.1d Outgoing : Four numbers of 11KV VCB feeders. ( outgoing


breaker feeder shall comprise of :

- 1 number 630 Amps 18KA VCB circuit breaker horizontally


insulated horizontal drawout, electrical motor operated, spring
charged with facility of manual closing.

- 3 number combined 150/1+1A current transformers. Cast resin


class 1.0 accuracy 15 VA minimum burden for metering class &
5P20 of 15VA burden for protection. The CT shall have shorting
links.

- 1 No. digital MFM.

- One local / remote switch for operation.

- One emergency OFF push button outside.

- Spring charge status.

- Annunciator window with minimum 8 windows with hooter.

- 1 set indicating light for breaker ON/OFF & indicating light for
D.C circuit healthy, indicating light for three phases.

ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 12
S.No. DESCRIPTION QTY. UNIT RATE AMOUNT

- One no. numerical microprocessor based separate three phase


over current with earth fault relay having IDMT and
instantaneous elements, 1no. trip circuit supervision relay, 1no.
master trip relay, ON / OFF / TRIP indications. Only master trip
relay, trip supervision relay is electro mechanical. All the
indicating lamps should be brought to terminal strip for remote
indication.

- Auto / Manual switch. In manual mode it shall have local TNC


switch for operation.

- Separate indication for each electrical fault.

- 1 number 220V DC shunt trip coil and 220V DC closing coil .

- 1 number circuit for remote tripping & closing of the breaker


through a potential free contact.
- 1 Set of HRC fuses, control wiring, protection wiring, and other
item required for the desired operation of the unit selector switch
to indicate the currents.

- Annunciator window for all electrical fault.

8.1d Outgoing : One number of 11KV VCB feeders. ( outgoing


breaker feeder shall comprise of :

- 1 number 630 Amps 18KA VCB circuit breaker horizontally


insulated horizontal drawout, electrical motor operated, spring
charged with facility of manual closing.

- 3 number combined 20/1+1A current transformers. Cast resin


class 1.0 accuracy 15 VA minimum burden for metering class &
5P20 of 15VA burden for protection. The CT shall have shorting
links.

- 1 No. digital MFM.


- One local / remote switch for operation.

- One emergency OFF push button outside.

- Spring charge status.


- Annunciator window with minimum 8 windows with hooter.

- 1 set indicating light for breaker ON/OFF & indicating light for
D.C circuit healthy, indicating light for three phases.

- One no. numerical microprocessor based separate three phase


over current with earth fault relay having IDMT and
instantaneous elements, 1no. trip circuit supervision relay, 1no.
master trip relay, 2nos. trafo auxilary relay with three elements,
1no. separate single pole definate time earth fault relay, ON /
OFF / TRIP indications. Only master trip relay, trip supervision
relay, transformer auxiliary relay, single pole earth fault relay is
electro mechanical. All the indicating lamps should be brought
to terminal strip for remote indication.
ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 13
S.No. DESCRIPTION QTY. UNIT RATE AMOUNT

Auto / Manual switch. In manual mode it shall have local TNC


switch for operation.

- Separate indication for each electrical fault.


- 1 number 220 VDC shunt trip coil and 220V DC closing coil .
- 1 number circuit for remote tripping & closing of the breaker
through a potential free contact.

- 1 Set of HRC fuses, control wiring, protection wiring, and other


item required for the desired operation of the unit selector switch
to indicate the currents.

- Annunciator window for all electrical and transformer fault.


- Buzzer.

8.1e All interconnected control wiring. 1 No

Sub Total of HT Panel Board

9.0 LT PANEL FOR STATION TRANSFORMER

Supply, testing & commissioning of Main LT Panel. This will


be floor mounted, free standing, indoor duty, dust proof, vermin
proof, front operated, electrical panel fabricated as per
specifications laid in this document and will be complete with
the main and auxiliary bus bars, interconnection, earth bus and
will be powder coated finish with 70 micron thickness. The
Main LT Panel shall suitable for 415 V AC, 3 phase, 50 Hz, 3
phase 4 wire supply system. Each incoming & outgoing breaker
will have microprocessor based releases. The Panel will be made
as per detailed specifications & drawings forming part of this
document.

(Each MCCB will be variable current setting from front, with


front extended lockable handle, pad lockable in off position,
indication light for ON, shrouding on incomer side, termination
shall be suitable for aluminium bus bars.)

1 No. Incomer 200Amps TP MCCB unit having 3 No. phase


indicating lamps to show the incoming power with control fuses,
1 no. ON indication, 1 no. voltmeter, voltage selector switch,
ammeter, ammeter selector switch with matching cast resin CTs,
1 no. KW meter. 1 No. 3 phase and neutral, neutral to earth
(minimum 4 mode) surge suppresor for 50KA along with
necessary fuses.

One set of TPN, Al. bus bar rated 250 Amps (after considering
necessary deratings of 75%) for phases and neutral for half
capacity of phases.

ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 14
S.No. DESCRIPTION QTY. UNIT RATE AMOUNT

The outgoing feeders are as follows :

- 8 Nos. 63 Amps TPN feeder each having one number 63 Amps


TP MCCB with isolable neutral and ON indication.

1 set of complete wiring


1 No

Sub Total of LT Panel Board

10.0 CABLES ALONG WITH ASSOCIATED ACCESSORIES


LIKE CABLE TRAYS, CLAMPS, GLANDS, LUGS AND
STRAIGHT THROUGH JOINTS ETC.

10.1 Supply, installation, testing and commissioning of Power


Cables (PVC) for 66 kV Switchyard
a) 2CX6.0 mm sq. Al. Arm. cable 200 Mtrs.
b) 4CX6.0 mm sq. Al Arm. Cable 200 Mtrs.
c) 4CX25 mm sq. Al Arm. Cable 200 Mtrs.
c) 4CX16 mm sq. Al Arm. Cable 200 Mtrs.
d) 3.5CX95 mm sq. Al Arm. Cable 100 Mtrs.

10.2 Supply, installation, testing and commissioning of Control


Cables (PVC) for 66 kV Switchyard
a) 4CX2.5 mm sq. Cu. Arm. cable 800 Mtrs.
b) 4CX4 mm sq. Cu. Arm. Cable 200 Mtrs.
c) 7CX2.5 mm sq. Cu. Arm. Cable 100 Mtrs.
d) 12CX2.5 mm sq. Cu. Arm. Cable 250 Mtrs.
e) 19Cx2.5 mm sq. Cu. Arm. Cable 100 Mtrs.

10.3 CABLE TRAY

10.3.1 Supply, installation of G.I built in ladder type cable trays of


various width in two tier/three tier fashion either on one side of
the wall or on two sides of the wall or at other places and paint
with one coat of red oxide primer and two coats of synthetic
enamel paint grey afterward.

a) 450 mm tray, main channel:20x75x20x2.0 mm thick, rungs


20x35x20x2.0 mm thick @ 250 mm c/c 100 Mtrs

10.3.2 Supply, installation of G.I built in perforated type cable trays of


various width in two tier/three tier fashion either on one side of
the wall or on two sides of the wall or at other places and paint
afterward if required.
a) 450 mm tray , 2.0mm thick, 50mm collar 50 Mtrs
b) 300 mm tray , 2.0mm thick, 50mm collar 100 Mtrs
c) 150 mm tray , 2.0mm thick, 50mm collar 50 Mtrs

Sub Total of Cables Along With Accessories


ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 15
S.No. DESCRIPTION QTY. UNIT RATE AMOUNT

11.0 EARTHING
Design, taking out earth resistivity at site and working out
detailed earthing mat design, calculation of net earth
resistance, step potential and touch potential for approval of
consultant.
11.1 COPPER PLATE EARTHING STATION

Supply, assembling, installing, testing and commissioning all the


items for constructing Cu plate earthing station comprises of one
number Cu. earthing plate 600 x 600 x 6mm thick, 40 mm dia
medium class GI watering pipe, (minimum 4.5 m deep) GI
funnel with stainless steel wire mesh strainer, concrete watering
chamber, steel hinged door on a steel frame to cover up the
watering pit, 50 Kg of common salt, 100 Kgs of fine charcoal
powder, earthing conductor size 2 x 75 x 10 mm copper from
the plate to the ground level as per the revised IS 3043 standard,
required hardwares and miscellaneous items. The work involves
digging pit in the soil, burying the earth electrode in the mixture
of common salt and charcoal, connecting earthing conductor to
plate, installing the watering pipe, back filling the soil and
constructing the watering pit at the site, details contained in this
document and sketch attached. 4 Nos

11.2 G.I PLATE EARTHING STATION:

Supply, assembling, installing, testing and commissioning all the


items for constructing GI plate earthing station at the locations.
The earthing station comprises of one number GI earthing plate
600 x 600 x 6 mm thick, 40mm dia medium class GI watering
pipe, (minimum 4.5 m deep) GI funnel with stainless steel wire
mesh strainer, concrete watering chamber, steel hinged door on a
steel frame to cover up the watering pit, 50 Kg of common salt,
100 Kg of fine charcoal powder, earthing conductor size 2x75 x
10 mm GI from the plate to the ground level as per the revised
IS 3043 standard, required hardware and miscellaneous items.
The work involves digging pit in the soil, burying the earth
electrode in the mixture of common salt and charcoal,
connecting earthing conductor to plate, installing the watering
pipe, back filling the soil and constructing the watering pit at the
site as specified, details contained in this document and sketch
attached.
26 Nos.

11.3 PIPE EARTHING STATION

ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 16
S.No. DESCRIPTION QTY. UNIT RATE AMOUNT

Supply, assembling & installing all the items for constructing GI


pipe earthing station. The earthing station comprises of one
number B class GI earthing pipe size 40mm dia, (minimum
4.5m deep) GI funnel with stainless steel hinged door on steel
frame (300 x 300mm) to cover up the watering pit, 100 Kg of
common salt, 200Kgs of fine charcoal powder, earthing
conductor size 25mm x 3mm GI flat from the pipe to the ground
level, required hardwares & miscellaneous items. The work
involves digging pit in the soil, burying the earth electrode in the
mixture of common salt & charcoal, connecting earthing
conductor to earthing electrode back filling the soil &
constructing the watering pit at the site as specified & details
contained in this document. 2 Nos.

11.4 EARTHING CONDUCTORS


Supply, straightening, shaping, laying under ground/ laying on a
cable tray/ laying in cement concrete trench the following sizes
of hot dipped galvanised iron conductor. The work is inclusive
of providing clamping with the trays/ on the sides of the
trenches, making joints where ever required (All joints of
Earthinfg Except machine end shall be properly welded .There
should not be any nut bolts to be used) and providing the
hardware and the terminating the hardware and the termination
to the equipment/ earthing station/ etc.

- 75 mm x 10 mm GI flat 400 Mtrs

- 65 mm x 10 mm GI flat 200 Mtrs


- 50 mm x 6 mm GI flat 400 Mtrs
- 40 mm x 5 mm GI flat 200 Mtrs
- 25 mm x 6 mm GI flat 200 Mtrs
- 25 mm x 3 mm GI flat 100 Mtrs
- 75 mm x 10 mm copper flat 100 Mtrs
- 65 mm x 10 mm copper flat 100 Mtrs
- 50 mm x 6 mm copper flat 20 Mtrs

- 25 mm x 6 mm copper flat 100 Mtrs


- 25 mm x 3 mm copper flat 100 Mtrs

Sub Total of Earthing

12.0 FABRICATION STRUCTURE & FOUNDATION

12.1 FABRICATION STRUCTURE

ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 17
S.No. DESCRIPTION QTY. UNIT RATE AMOUNT

Supplying, galvanising, erection, making, grouting and


commissioning of galvanised steel structure for following items
mentioned below and structure shall be as per HVPN practice
(All fabrication structure drg. will be given by contractor as per
HVPN specifications and same will be approved by structure &
electrical consultants).

- 2 sets lightning arrestor

- 2 set cable sealing end. 3000 Kg

12.2 FOUNDATION
CIVIL WORK AS PER DSR 2007 INCLUDING COST
INDEX 51%
12.2.1 Earth work in excavation by mechanical means (Hydralic
excavator)/ manual means over areas (exceeding 30 cm in depth,
1.5m in width as well as 10 sqm on plan) including disposal of
excavated earth, lead up to 50 m and lift upto 1.5m, disposed
earth to be levelled neatly dressed.
a All kinds of soil 926.1 cum

12.2.2 Filling available excavated earth (excluding rock) in trenches,


plinth, sides of foundations etc. in layers not exceeding 20cm in
depth: consolidating each deposited layer by ramming and
watering, lead upto 50m and lift upto 1.5m 92.61 cum

ADD EXTRA FOR EXCAVATION IN EXCESS OF 1.5 M

12.2.3 Extra for every additional lift of 1.5 m or part thereof in. All
kinds of soil.
a from 1.5 to 3.0 m 216.4 cum
b from 3.0 to 3.60m 52.14 cum

12.2.4 Disposal of surplus earth upto a distance of 30 km


a upto 5 km 833.5 cum
b 5 km to 10 km 833.5 cum
c 10 km to 20 km 833.5 cum
d 20 km to 30 km 833.5 cum

12.2.5 Providing and laying in position cement concrete of specified


grade excluding the cost of centering and shuttering - All work
up to plinth level :
a 1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 40
mm nominal size). 367.3 cum

ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 18
S.No. DESCRIPTION QTY. UNIT RATE AMOUNT

12.2.6 Providing and laying in position machine batched, machine


mixed and machine vibrated design mix cement concrete of
specified grade for reinforced cement concrete work including
pumping of concrete to site of laying but excluding the cost of
centring and shuttering, finishing and reinforcement, including
admixture in recommended proportions as per IS 9103 to
accelerate, retard setting of concrete, improve workability
without impairing strength and durability as per direction of
Engineer in charge. M-25 grade reinforced cement concrete by
using 380 kg of cement per cum of concrete. - All work upto
plinth level. 189.7 cum

12.2.7 Providing and laying in position machine batched, machine


mixed and machine vibrated design mix cement concrete of
specified grade for reinforced cement concrete work including
pumping of concrete to site of laying but excluding the cost of
centring and shuttering, finishing and reinforcement, including
admixture in recommended proportions as per IS 9103 to
accelerate, retard setting of concrete, improve workability
without impairing strength and durability as per direction of
Engineer in charge. M-25 grade reinforced cement concrete by
using 380 kg of cement per cum of concrete. - All work above
plinth level upto floor V level. 106.8 cum

FORM WORK
12.2.8 Centering and shuttering including strutting, propping etc. and
removal of form for :
a Foundations, footings, bases of columns, etc. for mass concrete.
16.42 sqm

b Suspended floors, roofs, landings, balconies and access


platform. 167.7 sqm

c Columns, pillars, piers, Abutments, Posts and Struts. 244.1 sqm

d Walls (any thickness) including attached pilasters, butteresses,


plinth and string courses etc. 1263 sqm

STEEL REINFORCEMENT
12.2.9 Reinforcement for R.C.C. work including straightening, cutting,
bending, placing in position and binding all complete.

a Thermo-mechanically treated bars 44483 kg

12.2.10 Brick work with F.P.S. bricks of class designation 100 in


foundation and plinth in , Cement mortar 1:6 (1 cement : 6
coarse sand) 32.96 cum

12.2.11 Brick work with F.P.S. bricks of class designation 75 in


superstructure above plinth level up to floor V level in all shapes
and sizes in, Cement mortar 1:5 ( 1 cement : 5 coarse sand)
120.9 cum

ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 19
S.No. DESCRIPTION QTY. UNIT RATE AMOUNT

12.2.12 Structural steel work in single section fixed with or without


connecting plate including cutting, hoisting, fixing in position
and applying a priming coat of approved steel primer all
complete. 11000 Kg

12.2.13 Steel work welded in built up sections/framed work including


cutting hoisting, fixing in position, grinding, sanding and
applying 2 priming coats of approved steel primer using steel
sections, built up, hollow and solid elements as specified in
drawings etc. as required .
a In gratings, frames, guard bar, ladder, railings, brackets, gates,
and similar works. 4301 kg

12.2.14 Fencing with angle iron post placed at required distance


embedded in cement concrete blocks, every 15th post, last
but one end post and corner post shall be strutted on both
sides and end post on one side only and provided with
horizontal lines and two diagonals interwoven with
horizontal wires, of barbed wire 9.38 kg per 100 m (minimum)
between the two posts fitted and fixed with G.I. staples, turn
buckles etc. complete. (Cost of posts, struts, earth work and
concrete work to be paid for separately) :- Payment to be
made per metre cost of total length of barbed wire used.

a With G.I. barbed wire


221.3 metre
Wooden Fire Door
12.2.15 Providing and fixing 55 MM Thick asbestor free Wooden Fire
Door Shutter With 3 MM Commercial Ply Facing .The fire
shutter check door shutter of 120minutes fire rating conferming
to BS 476 part 20 and 22- & IS 3809 & 3614 part–II.
Construction is proprietary by using 2 nos of 10 mm thick non
combustable calcium silicate board and 100% with out asbestor
having density not less than ≤ 900kg/m3, and thermal conductive
0.15 w/m*k and thermal resistance 0.06 m*k/w sandwiching 27
mm thick fire resistance insulation filler mineral (glass wool)
coated with fire proof sealant and 4 mm thick commercial ply on
both faces and hard wood (red merranti) lipping all around the
shutter with heat activated intumescent fire strips (imported
from U.K) of size 10mm x 4mm is use to fills the gaps between
board & internal wooden lipping on all side the shutter except
bottom. Manufactured and fixed strictly in accordance with the
manufacture’s specifications comprising of the following:

(a) The single rebat fire door frame is constructed out of treated
hardwood of section 130mm x 70mm.
(b) The frame has heat activated intumescent strip of size 10mm x
4mm use to fill the gap between board & internal wooden
lipping on all side the frame except bottom.
(c ) The door frame is fixed by 8 nos. MS fastner of size 10x 125.
ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 20
S.No. DESCRIPTION QTY. UNIT RATE AMOUNT

(d) The door frame is finished with one coat of anti- termite fire
retardant primer.
Hardwares for Fire Door
(i) S S Ball Bearing Hinges of Size 100 x 75 x 3 mm (Suzu/Garg
make or equivalent as per Engineer-in-charge)
( ii ) Door Closer (modle-TS 68) (Dorma/IR make or equivalent as
per Engineer-in-charge)
( iii ) Panic Exit Device for Single Leaf Door (PCHR-1000)
( iv ) Stainless Steel D Type Pull Handle of Size 300mm Long
(Dorset/Indobrass make or equivalent as per Engineer-in-charge)

(v) Mortise Lock with Lever Handle and Cylender


( vi ) Dead Lock With Cylender (INDOBRASS make or equivalent as
per Engineer-in-charge)
( vii ) 6 mm Thick Vision Panel of Size = (300 x 300 MM) (Central
Japan make or equivalent as per Engineer-in-charge) 4 sqm

12.2.16 Supplying and fixing rolling shutters of approved make, made of


required size MS laths interlocked together theire entire length
and jointed together at the end by end locks mounted on
specially designated pipe shaft with brackets, side guides and
arrangements for inside and out side locking with push and pull
operation complete including the cost of providing and fixing
necessary 27. 5 cm long wire springs grade no 2 and MS top
cover of required thickness for rolling shutters.
a 80 x1.25 mm MS laths with 1.25 mm thick top cover. 18 sqm

12.2.17 Providing and fixing ball bearing for rolling shutters 4 each

12.2.18 Extra for providing mechanical device chain and crank operation
for operating rolling shutters.
a Exceeding 10 sqm and upto 16.80 sqm in the area 18 sqm

12.2.19 Extra for providing grilled rolling shutters manufactured out of 8


mm dia MS bar instead of laths as per design approved by
Engineer -in Charge (area of grill to be measured). 9 sqm

12.2.20 Providing & Fixing of 25 mm thick Kota stone slab flooring


over 20mm (average) thick base laid over and jointed with grey
cement slurry mixed with pigment to match the shade of the slab
with 1:4 (1 cement :4 coarse sand ) as per design pattern
including rubbing , mirror polishing complete . (one full piece
of kota stone shall be used in steps unless otherwise indicated in
drawings). 211.9 sqm

12.2.21 Kota stone slabs 25 mm thick in risers of steps, skirting, dado


and pillars laid on 12 mm (average) thick cement mortar 1:3 (1
cement 3 coarse sand) and jointed with grey cement slurry
mixed with pigment to match the shade of the slabs, including
rubbing and polishing complete. 16.95 sqm
ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 21
S.No. DESCRIPTION QTY. UNIT RATE AMOUNT

12.2.23 12mm cement plaster of mix :


a 1:6 (1 cement : 6 fine sand) 525.8 sqm

12.2.24 18 mm cement plaster in two coats under layer 12 mm thick


cement plaster 1:5 (1 cement: 5 coarse sand) and a top
layer 6mm thick cement plaster 1:3 (1 cement: 3 coarse
sand) finished rough with sponge. 525.8 sqm

12.2.25 6mm cement plaster to ceiling of mix :


a 1:3 (1 cement : 3 fine sand) 211.9 sqm

12.2.26 Providing and applying plaster of paris putty of 2 mm thickness


over plastered surface to prepare the surface even and smooth
complete 525.8 sqm

12.2.27 Distempering with 1st quality acrylic washable distemper (ready


mixed) of approved manufacturer and of required shade and
colour complete. as per manufacturer's specification.

a Two or more coats on new work. 525.8 sqm

12.2.28 Applying one coat of cement primer of approved brand and


manufacture on wall surface :
a Cement primer. 525.8 sqm

12.2.29 Finishing walls with Acrylic Smooth exterior paint of required


shade :
a New work (Two or more coat applied @1.67 ltr/10 sqm over
and including base coat of water proofing cement paint applied
@ 2.20 kg/ 10 sqm). 525.8 sqm

12.2.30 Finishing with Epoxy paint (two or more coats) at all locations
prepared and applied as per manufacturer's specifications
including appropriate priming coat, preparation of surface, etc.
complete.
a On steel work 598.6 sqm

Sub Total of Structure & Foundation

13.0 MISCELLANEOUS ITEMS

13.1 YARD EXTERNAL LIGHTING

13.1.1 SINGLE ARM POLE

ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 22
S.No. DESCRIPTION QTY. UNIT RATE AMOUNT

13.1.1a Supply of 8.5 m long single arm pole as per IS 410, SP-16
provided with 600 X 600 X 10mm thick MS base plates & cable
looping box recessed in pedestal and fabricated from 1.6 mm
thick MS sheets and provided with terminal block for incoming
and outgoing 6 sq.mm cables, 10 amp SP MCB and an earthed
stud and provided with hinged gasketted lockable door duly
painted and including the cost of PVC sleeves embedded in the
foundation for incoming and outgoing cable etc. and including
the cost of painting the embedded portion of the pole with one
coat of bituminus paint over primer and exposed portion with 2
coats of synthetic enamel paint of approved color over portion
complete as required.
2 Nos

DSR ITEMS :
13.1.1b Erection of metallic pole of following length in cement concrete
1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40
DSR No. mm nominal size) foundation including excavation and refilling
11.3.3 etc.
as required.

a) Above 8.0 metre and upto 10.0 metre 2 Nos

13.1.1c Supplying and fixing of 32 mm dia X 2.00 metres long G.I. pipe
(medium class) bracket for mounting of HPMV / HPSV street
DSR No. light fitting on pole including bending the pipe to the required
12.34 shape, 2 nos 40 mm X 3 mm flat iron clamps with nuts, bolts
and washer, painting the flat iron with primer and finish paint
etc. as required.
2 Nos

13.1.1d Supplying and drawing following sizes of 3 x 1.5 sq. mm FR


PVC insulated copper conductor, single core cable in the
DSR No. existing surface/ recessed steel/ PVC conduit as required.
1.17.3
20 Mtr.

13.1.2 BRACKET LIGHT AT BUILIDING

13.1.2a Supplying and fixing of 32 mm dia X 2.00 metres long G.I. pipe
(medium class) bracket for mounting of HPMV / HPSV street
DSR No. light fitting on pole/ wall including bending the pipe to the
12.34 required shape, 2 nos 40 mm X 3 mm flat iron clamps with nuts,
bolts and washer, painting the flat iron with primer and finish
paint etc. as required. 8 Nos

13.1.2b Supplying, installation, testing & commissioning of Flood Light


fitting with 250 watt MH lamp (Bajaj BJFL 250 MH) 8 Nos

13.1.3 Supplying of following sizes of 1.1 KV grade multicore


aluminium conductor XLPE insulated armoured cable
conforming to IS:7098 (Part - I) complete with all amendments
etc. as required.
ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 23
S.No. DESCRIPTION QTY. UNIT RATE AMOUNT

a 4 x 4sqmm AL AR 100 Mtrs.


b 4 x 6sqmm AL AR 200 Mtrs.

13.1.4 Supply and making end termination with brass compression


glands and aluminium lugs for PVC insulated and PVC sheathed
aluminium / copper conductor cable of 1.1 KV grade of the
following sizes as required:-

a 4 x 4sqmm AL AR 4 Nos.
b 4 x 6sqmm AL AR 10 Nos.

13.1.5 Laying of one number PVC insulated and PVC sheathed / XLPE
power cable 1.1 KV grade of following sizes direct in ground
including excavation, sand cushoning protective covering and
refilling the trench etc. as required:-

DSR Upto 35 sq. mm


7.1.1 300 Mtrs.

13.2 SUB STATION EQUIPMENTS

Supply and erection of the following equipment at suitable place


in the sub-station building as required and as per detailed
specifications.

13.2a Carbon dioxide (CO2) type fire extinguisher with suitable base
pipe & horn (conforming to IS 2876 with cylinders fully charged
of capacity 9.0 Kgm). 2 Nos

13.2b 4 nos. G.I buckets of followings capacity paint and written with
white paint Fire and mounted on M.S. angle iron bracket of sizes
50 mm x 50 mm x 6 mm thick and 500 mm long including
grouting in wall etc. as required including filling with dry sand 9
ltr capacity. 2 Sets

13.2c First aid box as approved by St. John Ambulance Brigade/Indian


Red Cross Conforming to IS:2217 - 1963
1 Nos

13.2d Shock treatment chart at least in three languages duly mounted


ona wooden frame with glass as required. 1 Nos

13.2e Elastomeric mat 914.4mm wide and 12mm thick to withstand


1.1 KV dielectric strength as per IS 15652-2006. 2 Mtrs

13.2f Elastomeric mat 914.4 mm wide and conforming to IS15652-


2006 withstand 11 KV dielectric strength.
10 Mtr

13.2g Providing and fixing Medium Voltage Danger Notice Plate


200mm x 150mm made of M.S. Steel at least 2mm thick and
vitreous enamelled white on both sides and with inscription in
single red colour on front side as required. 2 Nos

ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 24
S.No. DESCRIPTION QTY. UNIT RATE AMOUNT

13.2h Providing and fixing High Voltage Danger Notice Plate 250mm
x 200mm made of M.S. Steel at least 2mm thick and vireous
enameled white on both sides and with inscription in single red
colour on front side as required. 1 No

Sub Total of Miscellaneous Items

GRAND TOTAL

PROJECT : ESIC HOSPITAL AT FARIDABAD


66KV SUBSTATION ESTIMATE FOR 4 BAY

PART - B : 66KV CABLES & TERMINATION


S.No. DESCRIPTION QTY. UNIT RATE AMOUNT

1.0 66KV XLPE CABLE ALM. CORRUGATED

1.1 Supply, installation, testing & commissioning of following :


38/66 KV cable having stranded compacted circular aluminium
conductor semiconducting tape, conductor screened by a layer of
extruded semiconducting cross linkable compound, XLPE
insulated, insulation screened by a layer of extruded
semiconducting cross linkable compound, semiconducting water
blocking tape, corrugated aluminium sheath, (aluminium sheath
shall be with stand fault current 31.5 Kamp for 1.0 seconds) and
overall HDPE type (ST-7) outer sheath with graphite coating
unarmoured cable general cofirming to IEC:60840. Vendor has
to give calculation for voltage drop in cross bonding boxes as
well as for complete 66KV cable length.

1.1a 1c X 400 sq.mm alm. cable. 13000 Mtrs.


1.1b Earthing Cable 240 sq.mm Cu. / EPR insulated cable 150 Mtrs.
1.1c Co-axial cable 240 /240 sq.mm, Cu./XLPE/Cu. Screen/HDPE 120 Mtrs.
1.1d Outdoor termination (premoulded porcelain type) for 66KV for
400 sq.mm cable complete in everyway for 25mm/KV creepage
distance. 13 Nos
1.1e Indoor GIS termination for 400 sq.mm alm. Cable alm.
Corrugated sheath. 9 Nos
1.1f 3 phase link boxes with SVL 1 Nos
1.1g 3 phase link boxes without SVL 2 Mtrs.
1.1h 1 phse link boxes with SVL 6 Nos.
1.1i 1 phse link boxes without SVL 6 Nos.
1.1j Insulated joints for cross bonding 12 Nos.

Sub Total of 66KV XLPE Cable Alm. Corrugated

DSR ITEMS :
2.0 R.C.C. PIPES :

ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 25
S.No. DESCRIPTION QTY. UNIT RATE AMOUNT

DSR Providing and laying non-pressure NP2 class (light duty) R.C.C.
Item No. pipes with collars jointed with stiff mixture of cement mortar in
19.6 the proportion of 1:2 (1 cement : 2 fine sand) including testing
of joints etc. complete.
a) 300mm dia R.C.C. pipe (DSR Item No. 19.6.4) 300 Mtrs.
b) 450mm dia R.C.C. pipe (DSR Item No. 19.6.5) 300 Mtrs.
c) 500mm dia R.C.C. pipe (DSR Item No. 19.6.6) 300 Mtrs.

Sub Total of R.C.C. Pipe

GRAND TOTAL

PROJECT : ESIC HOSPITAL AT FARIDABAD


66KV SUBSTATION ESTIMATE FOR 4 BAY

PART - C : COMPREHENSIVE ANNUAL MAINTENANCE CHARGES


S.No. DESCRIPTION QTY. UNIT RATE AMOUNT

1.0 COMPREHENSIVE ANNUAL MAINTENANCE


CHARGES

Comprehensive AMC for 7 years (after 1 year warranty from


second year to 8th year) for complete 66KV Switchyard with
GIS, CT , PT, isolator , breakers, relay control panel, cables,
yard lighting, DC battery charger, DC batteries, transformer,
earthing, 11KV panels, station transformer etc. complete in
everyway. 1 Lot

Sub Total of Comprehensive Annual Maintenance Charges

GRAND TOTAL

ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 26