Professional Documents
Culture Documents
Price Bid For 66 11kv Gis Substation
Price Bid For 66 11kv Gis Substation
FOR
66/11KV GIS SUBSTATION
ESIC MEDICAL COLLEGE FARIDABAD
ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 1
PROJECT : ESIC HOSPITAL AT FARIDABAD
66KV SUBSTATION ESTIMATE FOR 4 BAY
ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 2
S.No. DESCRIPTION QTY. UNIT RATE AMOUNT
1.8.3 STRUCTURE
ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 3
S.No. DESCRIPTION QTY. UNIT RATE AMOUNT
- Square fence as specified upto 2.4m high and covering top 0.3m
with chain link wire painted with silver colour paint. All fence &
gate shall be painted with galvanised paint.
- Gate at least 4m wide and painted with silver colour paint. 8000 Kg
b 1 No. double bus line bay for 66KV, 1250 Amps, 31.5KA for 1
sec SF6 gas insulated line bay module comprising of 3 nos.
single phase gas insulated voltage tranformer (66KV /R3 /110
/R3 / 110 /R3, this will be equipped with integrated
disconnecting facility for GIS and power cable testing without
any additional dismantelling and gas handling) 100VA burden
class 0.2 / 3P, 1 no. high speed safety ground switch, 1 no. disc
connector switch with earthing switch, 1 no. 1250A 31.5KA
fixed type SF6 insulated circuit breaker, 1 no. isolator with
earthing switch, 3 nos. single phase current transformer
(150/1+1+1A) with 5P20 / 0.2 accuracy / 5P20, 2 nos. isolator
with earthing switch (this will connect to 2 different buses in gas
insulated double busbar system), local control & monitoring
system for complete bay showing density of SF6 gas,
interlocking between component, gas insulated female terminal
connection for connecting cable line with GIS through insulated
interconnection bus etc to complete feeder bay module.
ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 4
S.No. DESCRIPTION QTY. UNIT RATE AMOUNT
d Bus Coupler in Double Bus Bar Bay : 1 no. bus coupler bay
module comprising of 2 nos. isolator switch with earthing, 3
nos. single phase CT (150/1+1A) 15VA burden 5P20/ 5P20
protection class, 1 no. 1250A SF6 insulated circuit breaker. This
will have local control centre for showing density of SF6 gas,
interlocking between component, monitoring gas and other
parameters.
3.0 TRANSFORMER
ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 5
S.No. DESCRIPTION QTY. UNIT RATE AMOUNT
The transformer shall have magnetic oil level guage with trip &
alarm contacts, air cell conservator, surge relay with trip &
alarm contacts, buckholz double float relay, winding temp.
meter with trip & alarm contacts, oil temp. meter with trip &
alarm contacts. The transformer losses shall be 10KW for NO
Load (max. guaranteed), 60KW for Load Losses (max.
guaranteed) and 2KW auxiliary losses for 8MVA rating during
ONAF condition. This shall have neutral CT on LV star side
with 2 neutral CT's ratio 200/1 PS class /5P20. The transformer
will have alm. gland plate on 11KV side for terminating single
core 11KV (UE) cables. This installation shall include all
supply, installation and termination of control cables between
transformer OLTC & RTCC along with incoming cable for
OLTC, lighting inside the marshalling box.
2 Nos
ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 6
S.No. DESCRIPTION QTY. UNIT RATE AMOUNT
ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 7
S.No. DESCRIPTION QTY. UNIT RATE AMOUNT
7.0 HT CABLES
ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 9
S.No. DESCRIPTION QTY. UNIT RATE AMOUNT
ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 10
S.No. DESCRIPTION QTY. UNIT RATE AMOUNT
- 1 set indicating light for breaker ON/OFF & indicating light for
D.C circuit healthy, indicating light for three phases along with
voltmeter & voltmeter selector switch.
- Buzzer.
8.1b Bus Coupler: One numbers 1250 Amps 18KA VCB circuit
breaker horizontal insulated horizontal drawout, electrical motor
operated, spring charged with facility of manual closing as bus
coupler with protections of over current and earth fault.
- 1 set indicating light for breaker ON/OFF & indicating light for
D.C circuit healthy, indicating light for three phases.
- 1 set indicating light for breaker ON/OFF & indicating light for
D.C circuit healthy, indicating light for three phases.
ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 12
S.No. DESCRIPTION QTY. UNIT RATE AMOUNT
- 1 set indicating light for breaker ON/OFF & indicating light for
D.C circuit healthy, indicating light for three phases.
One set of TPN, Al. bus bar rated 250 Amps (after considering
necessary deratings of 75%) for phases and neutral for half
capacity of phases.
ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 14
S.No. DESCRIPTION QTY. UNIT RATE AMOUNT
11.0 EARTHING
Design, taking out earth resistivity at site and working out
detailed earthing mat design, calculation of net earth
resistance, step potential and touch potential for approval of
consultant.
11.1 COPPER PLATE EARTHING STATION
ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 16
S.No. DESCRIPTION QTY. UNIT RATE AMOUNT
ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 17
S.No. DESCRIPTION QTY. UNIT RATE AMOUNT
12.2 FOUNDATION
CIVIL WORK AS PER DSR 2007 INCLUDING COST
INDEX 51%
12.2.1 Earth work in excavation by mechanical means (Hydralic
excavator)/ manual means over areas (exceeding 30 cm in depth,
1.5m in width as well as 10 sqm on plan) including disposal of
excavated earth, lead up to 50 m and lift upto 1.5m, disposed
earth to be levelled neatly dressed.
a All kinds of soil 926.1 cum
12.2.3 Extra for every additional lift of 1.5 m or part thereof in. All
kinds of soil.
a from 1.5 to 3.0 m 216.4 cum
b from 3.0 to 3.60m 52.14 cum
ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 18
S.No. DESCRIPTION QTY. UNIT RATE AMOUNT
FORM WORK
12.2.8 Centering and shuttering including strutting, propping etc. and
removal of form for :
a Foundations, footings, bases of columns, etc. for mass concrete.
16.42 sqm
STEEL REINFORCEMENT
12.2.9 Reinforcement for R.C.C. work including straightening, cutting,
bending, placing in position and binding all complete.
ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 19
S.No. DESCRIPTION QTY. UNIT RATE AMOUNT
(a) The single rebat fire door frame is constructed out of treated
hardwood of section 130mm x 70mm.
(b) The frame has heat activated intumescent strip of size 10mm x
4mm use to fill the gap between board & internal wooden
lipping on all side the frame except bottom.
(c ) The door frame is fixed by 8 nos. MS fastner of size 10x 125.
ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 20
S.No. DESCRIPTION QTY. UNIT RATE AMOUNT
(d) The door frame is finished with one coat of anti- termite fire
retardant primer.
Hardwares for Fire Door
(i) S S Ball Bearing Hinges of Size 100 x 75 x 3 mm (Suzu/Garg
make or equivalent as per Engineer-in-charge)
( ii ) Door Closer (modle-TS 68) (Dorma/IR make or equivalent as
per Engineer-in-charge)
( iii ) Panic Exit Device for Single Leaf Door (PCHR-1000)
( iv ) Stainless Steel D Type Pull Handle of Size 300mm Long
(Dorset/Indobrass make or equivalent as per Engineer-in-charge)
12.2.17 Providing and fixing ball bearing for rolling shutters 4 each
12.2.18 Extra for providing mechanical device chain and crank operation
for operating rolling shutters.
a Exceeding 10 sqm and upto 16.80 sqm in the area 18 sqm
12.2.30 Finishing with Epoxy paint (two or more coats) at all locations
prepared and applied as per manufacturer's specifications
including appropriate priming coat, preparation of surface, etc.
complete.
a On steel work 598.6 sqm
ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 22
S.No. DESCRIPTION QTY. UNIT RATE AMOUNT
13.1.1a Supply of 8.5 m long single arm pole as per IS 410, SP-16
provided with 600 X 600 X 10mm thick MS base plates & cable
looping box recessed in pedestal and fabricated from 1.6 mm
thick MS sheets and provided with terminal block for incoming
and outgoing 6 sq.mm cables, 10 amp SP MCB and an earthed
stud and provided with hinged gasketted lockable door duly
painted and including the cost of PVC sleeves embedded in the
foundation for incoming and outgoing cable etc. and including
the cost of painting the embedded portion of the pole with one
coat of bituminus paint over primer and exposed portion with 2
coats of synthetic enamel paint of approved color over portion
complete as required.
2 Nos
DSR ITEMS :
13.1.1b Erection of metallic pole of following length in cement concrete
1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40
DSR No. mm nominal size) foundation including excavation and refilling
11.3.3 etc.
as required.
13.1.1c Supplying and fixing of 32 mm dia X 2.00 metres long G.I. pipe
(medium class) bracket for mounting of HPMV / HPSV street
DSR No. light fitting on pole including bending the pipe to the required
12.34 shape, 2 nos 40 mm X 3 mm flat iron clamps with nuts, bolts
and washer, painting the flat iron with primer and finish paint
etc. as required.
2 Nos
13.1.2a Supplying and fixing of 32 mm dia X 2.00 metres long G.I. pipe
(medium class) bracket for mounting of HPMV / HPSV street
DSR No. light fitting on pole/ wall including bending the pipe to the
12.34 required shape, 2 nos 40 mm X 3 mm flat iron clamps with nuts,
bolts and washer, painting the flat iron with primer and finish
paint etc. as required. 8 Nos
a 4 x 4sqmm AL AR 4 Nos.
b 4 x 6sqmm AL AR 10 Nos.
13.1.5 Laying of one number PVC insulated and PVC sheathed / XLPE
power cable 1.1 KV grade of following sizes direct in ground
including excavation, sand cushoning protective covering and
refilling the trench etc. as required:-
13.2a Carbon dioxide (CO2) type fire extinguisher with suitable base
pipe & horn (conforming to IS 2876 with cylinders fully charged
of capacity 9.0 Kgm). 2 Nos
13.2b 4 nos. G.I buckets of followings capacity paint and written with
white paint Fire and mounted on M.S. angle iron bracket of sizes
50 mm x 50 mm x 6 mm thick and 500 mm long including
grouting in wall etc. as required including filling with dry sand 9
ltr capacity. 2 Sets
ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 24
S.No. DESCRIPTION QTY. UNIT RATE AMOUNT
13.2h Providing and fixing High Voltage Danger Notice Plate 250mm
x 200mm made of M.S. Steel at least 2mm thick and vireous
enameled white on both sides and with inscription in single red
colour on front side as required. 1 No
GRAND TOTAL
DSR ITEMS :
2.0 R.C.C. PIPES :
ESIC 66KV GIS Faridabad : Priced BOQ of 66KVA Substation for 4 Bay Page - 25
S.No. DESCRIPTION QTY. UNIT RATE AMOUNT
DSR Providing and laying non-pressure NP2 class (light duty) R.C.C.
Item No. pipes with collars jointed with stiff mixture of cement mortar in
19.6 the proportion of 1:2 (1 cement : 2 fine sand) including testing
of joints etc. complete.
a) 300mm dia R.C.C. pipe (DSR Item No. 19.6.4) 300 Mtrs.
b) 450mm dia R.C.C. pipe (DSR Item No. 19.6.5) 300 Mtrs.
c) 500mm dia R.C.C. pipe (DSR Item No. 19.6.6) 300 Mtrs.
GRAND TOTAL
GRAND TOTAL