DA Damper Actuator Edition:B/1

DA Damper Actuator Operation Manual

Applications & Features Spindle Die:


 Special designed for damper or ball valve control in Circular axial Square axial Shortest
Torque
HVAC system diameter dimension axial length
 Assembling: Easily connect damper or ball valve and 5Nm 6-18mm 4.5-12.5mm 50mm
actuator with allen screw 10Nm 8-20mm 5.8-14.0mm 54mm
 Long life: The design makes the actuator get longer life
 Manual: It can be manual operated with the button 20Nm 8-20mm 5.8-14.0mm 50mm
 Safety: The actuator has overload protection design and 40Nm 14-26mm 10.0-18.2mm 62mm
does not need any limit switch
 High-level protection and low noise: up to IP65
General parameters:
Noise Running Suggest
Specifications Torque Weight
level time damper area
<30dB <0.8m
2
Torque:5/10/20/40Nm 5 Nm 0.8kg 120s
Direction of rotation:set by switch <40dB <1.5 m
2
10 Nm 1.1kg 120s
Position indicator:mechanical
<40dB <3.5 m
2
20 Nm 1.2kg 150s
Manual override:set by push button
<45dB <7.0 m
2
Angle of rotation: max. 95° 40 Nm 1.75kg 150s
Power:24VAC/DC: Re:Suggest damper area is for general application,Torque calculation
should be different according to specific damper structure, installation
19.2~28.8V AC/DC
and air flow condition
power 3W, hold 1W
protection: class III-low voltage safe
110~220VAC:
Models
95~265V, 50/60Hz Model DA Damper Actuator
power 3.5W, hold 1W 05 5Nm
protection:class II-totally insulated 10 10Nm
Control Signal: on/off, 3 pos Torque
20 20Nm
0~10VDC (input impedance 250KΩ) 40 40Nm
4~20 mA (input impedance 200Ω) 0 24VAC/DC
Feedback Signal: SPDT/250V, 3A Power
1 110/220VAC
0~10VDC (Max. 1mA) 0 on/off,3pos
4~20mA (Max. 500Ω) Control
1 0~10VDC
Connecting:cable, 1m 3 x 0.75mm²or 4 x 0.5mm² signal
2 4~20mA
Mode of operation: Type1 to EN60730-1 1 0~10VDC
Work temp.: -30~+50°C, 95%RH, no condensing Feedback 2 4~20mA
Storage temp.: -40~+80°C signal 3 1 SPDT/250V,3A
Protection: up to IP65(IP54 – DA05) 4 2 SPDT/250V,3A
Approval: CE Re:If control signal is 0,feedback may be 3 or 4,
If control signal is 1, feedback may be 1,
If control signal is 2, feedback may be 2.

1
DA Damper Actuator Edition:B/1
Wiring diagrams
Different models have different electrical terminals. Please wire specific model according to the wiring diagram of the products.

~ ~

Switching control Floating point control SPDT feedback

Analog control/feedback(24V) Analog control/feedback(110/220V)

Installation
Direction set
Direct action: Clockwise rotation means open.
Counter clockwise rotation means close
Indirect Reaction: Clockwise rotation means close.
Counter clockwise rotation means open

1. As Pic01, turn the damper(value) to close position(ccw end);


2. As Pic01, fix the installation plate according to the position in the drawing
3. As Pic02, buckle the device on the corresponding position of the installation plate
4. As Pic02, push in the connector(5Nm series connector is fixed on the actuator)
5. As Pic03, push the manual override button
6. As Pic03, turn the actuator to close position(ccw end)
7. As Pic03, screw to fix the connector with the spindle of damper(value)
8. As Pic04, if the spindle’s length is less than Ho(show in size drawing), the reverse way could be applied. The step is
1,2,4,6,7,5,3. 5Nm series don’t have this function
9. As Pic05, when apply the free connection, use a straight screw driver to push the terminals and install the cable into the hole.
5Nm series don’t have the field terminals.
10. As Pic06, open the blue rubber cover. When POWER OFF, push the inside manual button to operate the actuator manually.
After releasing the button and restoring the power, the actuator will restore to electrically drive. When POWER OFF, turn
the button to change between direct and indirect operation.

2
DA Damper Actuator Edition:B/1

Cautions
1. The damper actuator cannot be used in the places which are not the specified application, especially in aircraft and its related
fields.
2. Assembly must be carried out by trained and experienced technician.
3. The device can only be opened by the manufacturer. The product does not contain any parts which can be replaced or
repaired by any user.
4. The cable can not be removed from the device.
5. When calculating the required torque, the specifications supplied by manufacturers (cross section, design & installation site)
& the air flow conditions must be observed.
6. The device contains electrical & electronic components which are not allowed to be disposed as household refuse.
7. The assemble surface should NOT be sprayed.
8. Manual/AUTO operation and rotation direction change, should be operated when POWER OFF. Otherwise it will