REMOTE POWER

CONTROL (RPC) - DIRECT


MARKETING
Item No.: 557.100, 557.101, 557.102,
557.105, 557.110, 557.120, 557.121

Straightforward switching from EEG fixed remuneration to the market bonus


model by adding the Remote Power Control interface to your monitoring system
DESCRIPTION OF FUNCTIONS Remote Power Control (RPC) is ideal for the direct marketing of a PV system.
RPC is an open software interface from the blue’Log X-Series which communicates via the
physical Ethernet interface (RJ45) of the blue’Log. The communication protocol on which it is
based is Modbus TCP.

Via RPC, the feed-in power of a PV system can be remote controlled, e.g. for the purposes of
direct marketing. This occurs alongside the grid operator's grid feed-in management without
influencing its control commands. The data logger interprets the control signals, e.g. of the
direct marketer, via RPC and forwards these, prioritized accordingly, to the PV system. The
requirement having the lowest power level always has priority.

In addition, specific measured values and data can be retrieved via RPC, e.g. information
regarding the current specified target value and the specified target values of the grid operator
and the RPC interface. In accordance with legal requirements, meteocontrol also allows the
current actual feed-in figures to be called up via this interface for direct marketing.

YOUR BENEFITS + Simple switching to direct marketing through use of existing interfaces
+ Grid feed-in management and direct marketing combined in a single device
+ Users enjoy all the benefits of meteocontrol system monitoring
+ Additional system data can be retrieved
+ Compatible with many direct marketing providers
+ Secure data transmission with VPN encryption
+ Visualization and alarming in the safer’Sun Professional portal and VCOM

Information subject to change, errors and omissions excepted / As at 03-2017 1|5


COMPATIBLE DIRECT MARKETERS

Essentially, meteocontrol Remote Power Control is compatible with any direct marketer who
uses the direct marketing system of energy & meteo systems GmbH,
ENERTRAG AG or Next Kraftwerke GmbH.

Information subject to change, errors and omissions excepted / As at 03-2017 2|5


COMMUNICATION DIAGRAM

TECHNICAL DATA
Communication interface: Ethernet (RJ45)
Protocol: Modbus TCP
Slave address (Client ID): 10
Port: 502
Timeout: 3000 ms

Transferable commands
RPC_P_PERC Setting the inverter active power control value

Readable data
P_AC Currently produced system power
M_AC_P Currently fed-in system power (actual feed-in)
PC_P_PERC_ABS Current specified target value in percent
PC_P_PERC_GRIDOP Target value specified by the grid operator in percent
PC_P_PERC_RPC Remote Power Control specified target value in percent
P_MAX_GRIDOP Maximum possible feed-in power with regulation by grid operator
P_MAX_RPC Maximum possible feed-in power with regulation by Remote Power Control
P_AV Maximum allowed system feed-in power (agreed connection power)

Information subject to change, errors and omissions excepted / As at 03-2017 3|5


REQUIREMENTS
Licenses The Remote Power Control interface is enabled in the blue’Log via separate licenses which are
uploaded via the data logger's web pages.

The licenses are obtained on a one-off basis and are then permanently valid for the blue’Log
specified during the order procedure with its unique hardware serial number. Because these
licenses are allocated to specific devices, please ensure that you obtain a license for the
blue’Log configured as MASTER or STANDALONE on your system.

Licenses for various system sizes are available so that you can choose the right license for your
system power.

All licenses at a glance:

 557100 Remote Power Control X-Series license for up to 500 kWp


 557101 Remote Power Control X-Series license for up to 1 MWp
 557102 Remote Power Control X-Series license for up to 2 MWp
 557105 Remote Power Control X-Series license for up to 5 MWp
 557110 Remote Power Control X-Series license for up to 10 MWp
 557120 Remote Power Control X-Series license for up to 20 MWp
 557121 Remote Power Control X-Series license for over 20 MWp

Network The PV system needs to have its own telecommunications network.

Grid feed-in management Grid feed-in management in compliance with EEG 2014 and the BDEW Medium Voltage
Directive must be provided via meteocontrol hardware.

VPN router In order to use Remote Power Control as a remote interface for direct marketing, a VPN-
(only necessary for direct marketing) capable router for establishing a secure data connection to the direct marketer is needed in
addition to the blue’Log.

ACCESSORIES
VPN routers The following VPN routers for establishing the VPN tunnel to the direct marketer can be
(only necessary for direct marketing) obtained from meteocontrol:
 422.416: 2-port VPN Ethernet router EBW-E100
 422.440: VPN HSPA router EBW-H100 (incl. antenna)

VPN router configuration meteocontrol configures the VPN router according to the direct marketing system used:
(only necessary for direct marketing)
 426.024: energy & meteo systems router configuration for direct marketer interface
 426.025: Enertrag router configuration for direct marketer interface
 426.026: Next Kraftwerke router configuration for direct marketer interface

Information subject to change, errors and omissions excepted / As at 03-2017 4|5


WIRING DIAGRAM
Network with static IP addresses

meteocontrol GmbH | Spicherer Straße 48 | 86157 Augsburg | Telephone +49 (0)821 34666-0 | Fax +49 (0)821 34666-11
E-mail info@meteocontrol.com | Web www.meteocontrol.com

Information subject to change, errors and omissions excepted / As at 03-2017 5|5