TEST REPORT

Customer: C0275899
Tiso Maurizio
EUROSTANDARD S.p.A.
Zona Industriale Lago
Italy

Result PASS Report Date 31-MAY-2022

Customer Name EUROSTANDARD S.p.A.


Section Number 1180
Test Type 5 Year Audit
Job Number J-00427215
Work Order Number W0738481
Previous Approval Number 1709087
Manufacturing Status Production
Account Manager Martin Williams

Thank you for having your product tested by NSF Wales Ltd.
Please contact your Account Manager if you have any questions or concerns pertaining to this report.

Report Date 31-MAY-2022

Report Authorisation

Daniel Atkins - Operational Technician

0626

FI20220531082634 J-00427215 Page 1 of 29


This report is issued in accordance with the laboratory accreditation requirements of the United Kingdom Accreditation Service. It provides traceability of
measurement to the SI system of units and/or to units of measurement realised at the National Physical Laboratory or other recognised national metrology institutes.
This report shall not be reproduced, except in its entirety, without the written approval of NSF Wales Ltd. This report does not represent NSF Certification or
authorisation to use the NSF Mark. Authorisation to use the NSF Mark is limited to products appearing in the Company's Official NSF Listing (www.nsf.org). The
results relate only to those items tested, in the condition received at the laboratory.
Sample ID: S-0001909337 Model Number /Trade Designation: PE100 SDR7.4 pipe - 21.00.250020 (Socket)
connected to 21.36.250020 (End Cap)
Analysis Result
TCS 6001.1 (A) (Issue 7) Marking for Identification (All fittings) (Proc. 18703) Pass
TCS 1412.1 (Issue 3) Corrosion protection. (Proc. 18593) Pass
TCS 5011.1 (Issue 3) Measurement of linear dimensions (Proc. 18688) Pass
TCS 1315.2 (Issue 3) Torque (Connection and Disconnection) (Proc. 18586) Not Applicable
TCS 2114.2 (Issue 4) Opacity (Proc. 18632) Not Applicable
TCS 1112.1 (N) (Issue 3) Porosity – All Other Valves-Fittings (Proc. 28705) Pass
TCS 1312.9 (A) (Issue 2) Deformation – Non BS Fittings (Proc. 18556) Not Applicable
TCS 1113.2 (A) (Issue 2) Joint Effectiveness (Proc. 28708) Pass
TCS 2211.2 (Issue 2) Contamination (vacuum when submerged) (Proc. 18634) Pass
Tension Test (See below for test code used) Not Applicable

Sample ID: S-0001909338 Model Number /Trade Designation: PE100 SDR7.4 pipe: 21.00.250160 (Socket)
connected to 21.36.250160 (End Cap)
Analysis Result
TCS 6001.1 (A) (Issue 7) Marking for Identification (All fittings) (Proc. 18703) Pass
TCS 1412.1 (Issue 3) Corrosion protection. (Proc. 18593) Pass
TCS 5011.1 (Issue 3) Measurement of linear dimensions (Proc. 18688) Pass
TCS 1315.2 (Issue 3) Torque (Connection and Disconnection) (Proc. 18586) Not Applicable
TCS 2114.2 (Issue 4) Opacity (Proc. 18632) Not Applicable
TCS 1112.1 (N) (Issue 3) Porosity – All Other Valves-Fittings (Proc. 28705) Pass
TCS 1312.9 (A) (Issue 2) Deformation – Non BS Fittings (Proc. 18556) Not Applicable
TCS 1113.2 (A) (Issue 2) Joint Effectiveness (Proc. 28708) Pass
TCS 2211.2 (Issue 2) Contamination (vacuum when submerged) (Proc. 18634) Pass
Tension Test (See below for test code used) Not Applicable

Sample ID: S-0001909339 Model Number /Trade Designation: PE100 SDR7.4 pipe: 21.00.250315 (Socket)
connected to end cap (for testing purposes).
Analysis Result
TCS 6001.1 (A) (Issue 7) Marking for Identification (All fittings) (Proc. 18703) Pass
TCS 1412.1 (Issue 3) Corrosion protection. (Proc. 18593) Pass
TCS 5011.1 (Issue 3) Measurement of linear dimensions (Proc. 18688) Pass
TCS 1315.2 (Issue 3) Torque (Connection and Disconnection) (Proc. 18586) Not Applicable
TCS 2114.2 (Issue 4) Opacity (Proc. 18632) Not Applicable
TCS 1112.1 (N) (Issue 3) Porosity – All Other Valves-Fittings (Proc. 28705) Pass
TCS 1312.9 (A) (Issue 2) Deformation – Non BS Fittings (Proc. 18556) Not Applicable
TCS 1113.2 (A) (Issue 2) Joint Effectiveness (Proc. 28708) Pass
TCS 2211.2 (Issue 2) Contamination (vacuum when submerged) (Proc. 18634) Pass
Tension Test (See below for test code used) Not Applicable

Sample ID: S-0001909340 Model Number /Trade Designation: PE100 SDR7.4 pipe: 21.51.164020 (Socket)
21.20.160040 (Spigot saddle) connected to end cap
(for testing purposes).
Analysis Result
TCS 6001.1 (A) (Issue 7) Marking for Identification (All fittings) (Proc. 18703) Pass
TCS 1412.1 (Issue 3) Corrosion protection. (Proc. 18593) Pass
TCS 5011.1 (Issue 3) Measurement of linear dimensions (Proc. 18688) Pass
TCS 1315.2 (Issue 3) Torque (Connection and Disconnection) (Proc. 18586) Not Applicable
TCS 2114.2 (Issue 4) Opacity (Proc. 18632) Not Applicable

FI20220531082634 J-00427215 Page 2 of 29


TCS 1112.1 (N) (Issue 3) Porosity – All Other Valves-Fittings (Proc. 28705) Pass
TCS 1312.9 (A) (Issue 2) Deformation – Non BS Fittings (Proc. 18556) Not Applicable
TCS 1113.2 (A) (Issue 2) Joint Effectiveness (Proc. 28708) Pass
TCS 2211.2 (Issue 2) Contamination (vacuum when submerged) (Proc. 18634) Pass
Tension Test (See below for test code used) Not Applicable

Sample ID: S-0001909341 Model Number /Trade Designation: PE100 SDR11 pipe: 21.00.160075 (Socket)
21.20.160075 (Spigot saddle) 21.36.160075 (End
cap).
Analysis Result
TCS 6001.1 (A) (Issue 7) Marking for Identification (All fittings) (Proc. 18703) Pass
TCS 1412.1 (Issue 3) Corrosion protection. (Proc. 18593) Pass
TCS 5011.1 (Issue 3) Measurement of linear dimensions (Proc. 18688) Pass
TCS 1315.2 (Issue 3) Torque (Connection and Disconnection) (Proc. 18586) Not Applicable
TCS 2114.2 (Issue 4) Opacity (Proc. 18632) Not Applicable
TCS 1112.1 (N) (Issue 3) Porosity – All Other Valves-Fittings (Proc. 28705) Pass
TCS 1312.9 (A) (Issue 2) Deformation – Non BS Fittings (Proc. 18556) Not Applicable
TCS 1113.2 (A) (Issue 2) Joint Effectiveness (Proc. 28708) Pass
TCS 2211.2 (Issue 2) Contamination (vacuum when submerged) (Proc. 18634) Pass
Tension Test (See below for test code used) Not Applicable

Sample ID: S-0001909342 Model Number /Trade Designation: PE100 SDR11 pipe: 21.00.160160 (Socket)
21.20.160160 (spigot saddle) 21.36.160160 (End
cap)
Analysis Result
TCS 6001.1 (A) (Issue 7) Marking for Identification (All fittings) (Proc. 18703) Pass
TCS 1412.1 (Issue 3) Corrosion protection. (Proc. 18593) Pass
TCS 5011.1 (Issue 3) Measurement of linear dimensions (Proc. 18688) Pass
TCS 1315.2 (Issue 3) Torque (Connection and Disconnection) (Proc. 18586) Not Applicable
TCS 2114.2 (Issue 4) Opacity (Proc. 18632) Not Applicable
TCS 1112.1 (N) (Issue 3) Porosity – All Other Valves-Fittings (Proc. 28705) Pass
TCS 1312.9 (A) (Issue 2) Deformation – Non BS Fittings (Proc. 18556) Not Applicable
TCS 1113.2 (A) (Issue 2) Joint Effectiveness (Proc. 28708) Pass
TCS 2211.2 (Issue 2) Contamination (vacuum when submerged) (Proc. 18634) Pass
Tension Test (See below for test code used) Not Applicable

Sample ID: S-0001909343 Model Number /Trade Designation: PE100 SDR11 pipe: 21.20.160250 (spigot saddle)
connected to end cap (for testing purposes).
Analysis Result
TCS 6001.1 (A) (Issue 7) Marking for Identification (All fittings) (Proc. 18703) Pass
TCS 1412.1 (Issue 3) Corrosion protection. (Proc. 18593) Pass
TCS 5011.1 (Issue 3) Measurement of linear dimensions (Proc. 18688) Pass
TCS 1315.2 (Issue 3) Torque (Connection and Disconnection) (Proc. 18586) Not Applicable
TCS 2114.2 (Issue 4) Opacity (Proc. 18632) Not Applicable
TCS 1112.1 (N) (Issue 3) Porosity – All Other Valves-Fittings (Proc. 28705) Pass
TCS 1312.9 (A) (Issue 2) Deformation – Non BS Fittings (Proc. 18556) Not Applicable
TCS 1113.2 (A) (Issue 2) Joint Effectiveness (Proc. 28708) Pass
TCS 2211.2 (Issue 2) Contamination (vacuum when submerged) (Proc. 18634) Pass
Tension Test (See below for test code used) Not Applicable

Model Number /Trade Designation: PE100 SDR17 pipe: 21.00.100400 (Socket)


FI20220531082634 J-00427215 Page 3 of 29
Sample ID: S-0001909344 connected to an end cap (for testing purposes).
Analysis Result
TCS 6001.1 (A) (Issue 7) Marking for Identification (All fittings) (Proc. 18703) Pass
TCS 1412.1 (Issue 3) Corrosion protection. (Proc. 18593) Pass
TCS 5011.1 (Issue 3) Measurement of linear dimensions (Proc. 18688) Pass
TCS 1315.2 (Issue 3) Torque (Connection and Disconnection) (Proc. 18586) Not Applicable
TCS 2114.2 (Issue 4) Opacity (Proc. 18632) Not Applicable
TCS 1112.1 (N) (Issue 3) Porosity – All Other Valves-Fittings (Proc. 28705) Pass
TCS 1312.9 (A) (Issue 2) Deformation – Non BS Fittings (Proc. 18556) Not Applicable
TCS 1113.2 (A) (Issue 2) Joint Effectiveness (Proc. 28708) Pass
TCS 2211.2 (Issue 2) Contamination (vacuum when submerged) (Proc. 18634) Pass
Tension Test (See below for test code used) Not Applicable

FI20220531082634 J-00427215 Page 4 of 29


Sample ID: S-0001909337
Sample Name: DN20 25bar
Sample Description: PE100 SDR7.4 pipe - 21.00.250020 Socket connected to 21.36.250020 Cap electrofusion fittings
Sample Received: 18-MAY-2022

Product Type: Polyethylene electrofusion fittings for use with polyetheylene pipe ( EN 12201-3)
Model Number/Trade Designation: PE100 SDR7.4 pipe - 21.00.250020 (Socket) connected to 21.36.250020 (End
Cap)
Maximum Working Pressure: 25 Bar
Maximum Operating Temperature: 20 deg C
Comments: Cold Water Use Only. Tested and for use with PE100 Pipe (EN 12201-2)

<< Results >>

TCS 6001.1 (A) (Issue 7) Marking for Identification (All fittings) (Proc. 18703) (WP1355)
Technician ID BBOWEN
Date Analysed 18-05-2022
Product Marking and location EURO, PE100, size, SDR, PN and date of
manufacture (MM/YY) on the fitting
TCS Clause (A, A+B, A+C, A+D, A+E, A+F) A
Permanence of Marking Yes
Marking for Identification (P/F) Pass

TCS 1412.1 (Issue 3) Corrosion protection. (Proc. 18593) (WP1343)


Technician ID RLACEY
Date Analysed 27-05-2022
List Metals in Contact No metals in contact
Coating Irregularities (None Reqd) None
Electrochem Test Result Pass

TCS 2111.1 (Issue 3) Effect upon water quality (non-metallic materials) (Proc. 18629) (WP1385)
Technician ID RLACEY
Date Analysed 27-05-2022
Non Metallic Materials Please see attached declaration

TCS 5011.1 (Issue 3) Measurement of linear dimensions (Proc. 18688) (WP1354)


Technician ID RLACEY
Date Analysed 27-05-2022
Linear Dimensions 21.00.250020 Socket (DN20 x DN20) with
21.36.250020 Cap (DN20)
Linear Dimension Result (P/F) Pass

TCS 1315.2 (Issue 3) Torque (Connection and Disconnection) (Proc. 18586) (WP1374)
Technician ID RLACEY
Date Analysed 27-05-2022
Torque Test - (P/F) Not Applicable
Comments Electrofusion fittings

FI20220531082634 J-00427215 Page 5 of 29


<< Results >> (Continued)

TCS 2114.2 (Issue 4) Opacity (Proc. 18632) (WP1349) (Continued)


Technician ID RLACEY
Date Analysed 27-05-2022
Opacity test result - P/F Not Applicable
comment For underground use only (R008)

TCS 1112.1 (N) (Issue 3) Porosity – All Other Valves-Fittings (Proc. 28705) (WP1368)
Technician ID CBROAD
Date Analysed 30-05-2022
Temperature (20 ± 10 deg C) 16 deg C
Above or Below Ground Use Below Ground
Pressure Rating (PN) 25 bar
Pressure multiplier x 2.0
Required Test Pressure 50 bar
Test pressure limits ± 1.0 bar
Actual test pressure 50.4 bar
Hydraulic Pressure Duration (60 ± 5 sec) 60 sec
Leakage (None) None
Porosity Test - (P/F) Pass

TCS 1312.9 (A) (Issue 2) Deformation – Non BS Fittings (Proc. 18556) (WP1382)
Technician ID RLACEY
Date Analysed 27-05-2022
Deformation Test Result (P/F) Not Applicable
Comments Electrofusion fittings

TCS 1113.2 (A) (Issue 2) Joint Effectiveness (Proc. 28708) (WP1375)


Technician ID CBROAD
Date Analysed 30-05-2022
Temperature (20 ± 10 Deg C) 16 Deg C
Test pressure required 50 bar
Test pressure Limits ± 1.0 bar
Actual test pressure 50.4 bar
Pressure Duration (60 ± 5 min) 60 min
Leakage (None) None
Joint Effectiveness - (P/F) Pass

TCS 2211.2 (Issue 2) Contamination (vacuum when submerged) (Proc. 18634) (WP1390)
Technician ID RLACEY
Date Analysed 26-05-2022
Temperature (20 ± 10 °C) 16 deg C
Pipe Nominal Diameter 20 mm
Minimum Submerged Depth 10 Times Diameter

FI20220531082634 J-00427215 Page 6 of 29


<< Results >> (Continued)

TCS 2211.2 (Issue 2) Contamination (vacuum when submerged) (Proc. 18634) (WP1390) (Continued)
Actual Submerged Depth 200 mm
Vacuum Applied (-0.9 Bar to -1.0 Bar) -0.95 Bar
Time (60 ± 5 min) 60 min
Water Ingress (None Reqd) None
Vacuum Test Result Pass

Tension Test (See below for test code used) (WP1625)


Technician ID RLACEY
Date Analysed 27-05-2022
Tension test - (Pass/Fail) Not Applicable
Comments Electrofusion fittings

† TCS 4001.11 (Issue 1) Visual inspection (Proc. 18685) (WP1397)


Technician ID BBOWEN
Date Analysed 18-05-2022
Visual Confirmation of Sample Does / do the samples submitted for
testing visually conform (without
dismantling) to the product(s) that were
identified as representative of the range for
which approval is sought?
Visual Confirmation of Sample Result Yes
Confirmation of Sub Components Does / do the individually declared sub-
component(s) used in the sample
submitted for testing appear to be those
that were declared in the application?
Confirmation of Sub Components Result Yes

FI20220531082634 J-00427215 Page 7 of 29


Sample ID: S-0001909338
Sample Name: DN160 25bar
Sample Description: PE100 SDR7.4 pipe – 21.00.250160 Socket connected to 21.36.250160 Cap electrofusion fittings.
Sample Received: 18-MAY-2022

Product Type: Polyethylene electrofusion fittings for use with polyetheylene pipe ( EN 12201-3)
Model Number/Trade Designation: PE100 SDR7.4 pipe: 21.00.250160 (Socket) connected to 21.36.250160 (End
Cap)
Maximum Working Pressure: 25 Bar
Maximum Operating Temperature: 20 deg C
Comments: Cold Water Use Only. Tested and for use with PE100 Pipe (EN 12201-2)

<< Results >>

TCS 6001.1 (A) (Issue 7) Marking for Identification (All fittings) (Proc. 18703) (WP1355)
Technician ID BBOWEN
Date Analysed 18-05-2022
Product Marking and location EURO, PE100, size, SDR, PN and date of
manufacture (MM/YY) on the fitting
TCS Clause (A, A+B, A+C, A+D, A+E, A+F) A
Permanence of Marking Yes
Marking for Identification (P/F) Pass

TCS 1412.1 (Issue 3) Corrosion protection. (Proc. 18593) (WP1343)


Technician ID RLACEY
Date Analysed 27-05-2022
List Metals in Contact No metals in contact
Coating Irregularities (None Reqd) None
Electrochem Test Result Pass

TCS 2111.1 (Issue 3) Effect upon water quality (non-metallic materials) (Proc. 18629) (WP1385)
Technician ID RLACEY
Date Analysed 27-05-2022
Non Metallic Materials Please see attached declaration

TCS 5011.1 (Issue 3) Measurement of linear dimensions (Proc. 18688) (WP1354)


Technician ID RLACEY
Date Analysed 27-05-2022
Linear Dimensions 21.00.250160 Socket (DN160 x DN160)
with 21.36.250160 Cap (DN160)
Linear Dimension Result (P/F) Pass

TCS 1315.2 (Issue 3) Torque (Connection and Disconnection) (Proc. 18586) (WP1374)
Technician ID RLACEY
Date Analysed 27-05-2022
Torque Test - (P/F) Not Applicable
Comments Electrofusion fittings

FI20220531082634 J-00427215 Page 8 of 29


<< Results >> (Continued)

TCS 2114.2 (Issue 4) Opacity (Proc. 18632) (WP1349) (Continued)


Technician ID RLACEY
Date Analysed 27-05-2022
Opacity test result - P/F Not Applicable
comment For underground use only (R008)

TCS 1112.1 (N) (Issue 3) Porosity – All Other Valves-Fittings (Proc. 28705) (WP1368)
Technician ID CBROAD
Date Analysed 30-05-2022
Temperature (20 ± 10 deg C) 16 deg C
Above or Below Ground Use Below Ground
Pressure Rating (PN) 25 bar
Pressure multiplier x 2.0
Required Test Pressure 50 bar
Test pressure limits ± 1.0 bar
Actual test pressure 50.4 bar
Hydraulic Pressure Duration (60 ± 5 sec) 60 sec
Leakage (None) None
Porosity Test - (P/F) Pass

TCS 1312.9 (A) (Issue 2) Deformation – Non BS Fittings (Proc. 18556) (WP1382)
Technician ID RLACEY
Date Analysed 27-05-2022
Deformation Test Result (P/F) Not Applicable
Comments Electrofusion fittings

TCS 1113.2 (A) (Issue 2) Joint Effectiveness (Proc. 28708) (WP1375)


Technician ID CBROAD
Date Analysed 30-05-2022
Temperature (20 ± 10 Deg C) 16 Deg C
Test pressure required 50 bar
Test pressure Limits ± 1.0 bar
Actual test pressure 50.4 bar
Pressure Duration (60 ± 5 min) 60 min
Leakage (None) None
Joint Effectiveness - (P/F) Pass

TCS 2211.2 (Issue 2) Contamination (vacuum when submerged) (Proc. 18634) (WP1390)
Technician ID RLACEY
Date Analysed 26-05-2022
Temperature (20 ± 10 °C) 17 deg C
Pipe Nominal Diameter 160 mm
Minimum Submerged Depth Fully Submerged

FI20220531082634 J-00427215 Page 9 of 29


<< Results >> (Continued)

TCS 2211.2 (Issue 2) Contamination (vacuum when submerged) (Proc. 18634) (WP1390) (Continued)
Actual Submerged Depth 650 mm
Vacuum Applied (-0.9 Bar to -1.0 Bar) -0.95 Bar
Time (60 ± 5 min) 60 min
Water Ingress (None Reqd) None
Vacuum Test Result Pass

Tension Test (See below for test code used) (WP1625)


Technician ID RLACEY
Date Analysed 27-05-2022
Tension test - (Pass/Fail) Not Applicable
Comments Electrofusion fittings

† TCS 4001.11 (Issue 1) Visual inspection (Proc. 18685) (WP1397)


Technician ID BBOWEN
Date Analysed 18-05-2022
Visual Confirmation of Sample Does / do the samples submitted for
testing visually conform (without
dismantling) to the product(s) that were
identified as representative of the range for
which approval is sought?
Visual Confirmation of Sample Result Yes
Confirmation of Sub Components Does / do the individually declared sub-
component(s) used in the sample
submitted for testing appear to be those
that were declared in the application?
Confirmation of Sub Components Result Yes

FI20220531082634 J-00427215 Page 10 of 29


Sample ID: S-0001909339
Sample Name: DN315 25bar
Sample Description: PE100 SDR7.4 pipe – 21.00.250315 Socket connected to 300mm PE100 SDR 7.4 pipe with end
cap electrofusion fittings.
Sample Received: 18-MAY-2022

Product Type: Polyethylene electrofusion fittings for use with polyetheylene pipe ( EN 12201-3)
Model Number/Trade Designation: PE100 SDR7.4 pipe: 21.00.250315 (Socket) connected to end cap (for testing
purposes).
Maximum Working Pressure: 25 Bar
Maximum Operating Temperature: 20 deg C
Comments: Cold Water Use Only. Tested and for use with PE100 Pipe (EN 12201-2)

<< Results >>

TCS 6001.1 (A) (Issue 7) Marking for Identification (All fittings) (Proc. 18703) (WP1355)
Technician ID BBOWEN
Date Analysed 18-05-2022
Product Marking and location EURO, PE100, size, SDR, PN and date of
manufacture (MM/YY) on the fitting
TCS Clause (A, A+B, A+C, A+D, A+E, A+F) A
Permanence of Marking Yes
Marking for Identification (P/F) Pass

TCS 1412.1 (Issue 3) Corrosion protection. (Proc. 18593) (WP1343)


Technician ID RLACEY
Date Analysed 27-05-2022
List Metals in Contact No metals in contact
Coating Irregularities (None Reqd) None
Electrochem Test Result Pass

TCS 2111.1 (Issue 3) Effect upon water quality (non-metallic materials) (Proc. 18629) (WP1385)
Technician ID RLACEY
Date Analysed 27-05-2022
Non Metallic Materials Please see attached declaration

TCS 5011.1 (Issue 3) Measurement of linear dimensions (Proc. 18688) (WP1354)


Technician ID RLACEY
Date Analysed 27-05-2022
Linear Dimensions 21.00.250315 Socket (DN315 x DN315)
Linear Dimension Result (P/F) Pass

TCS 1315.2 (Issue 3) Torque (Connection and Disconnection) (Proc. 18586) (WP1374)
Technician ID RLACEY
Date Analysed 27-05-2022
Torque Test - (P/F) Not Applicable
Comments Electrofusion fittings

FI20220531082634 J-00427215 Page 11 of 29


<< Results >> (Continued)

TCS 2114.2 (Issue 4) Opacity (Proc. 18632) (WP1349) (Continued)


Technician ID RLACEY
Date Analysed 27-05-2022
Opacity test result - P/F Not Applicable
comment For underground use only (R008)

TCS 1112.1 (N) (Issue 3) Porosity – All Other Valves-Fittings (Proc. 28705) (WP1368)
Technician ID CBROAD
Date Analysed 30-05-2022
Temperature (20 ± 10 deg C) 16 deg C
Above or Below Ground Use Below Ground
Pressure Rating (PN) 25 bar
Pressure multiplier x 2.0
Required Test Pressure 50 bar
Test pressure limits ± 1.0 bar
Actual test pressure 50.4 bar
Hydraulic Pressure Duration (60 ± 5 sec) 60 sec
Leakage (None) None
Porosity Test - (P/F) Pass

TCS 1312.9 (A) (Issue 2) Deformation – Non BS Fittings (Proc. 18556) (WP1382)
Technician ID RLACEY
Date Analysed 27-05-2022
Deformation Test Result (P/F) Not Applicable
Comments Electrofusion fittings

TCS 1113.2 (A) (Issue 2) Joint Effectiveness (Proc. 28708) (WP1375)


Technician ID CBROAD
Date Analysed 30-05-2022
Temperature (20 ± 10 Deg C) 16 Deg C
Test pressure required 50 bar
Test pressure Limits ± 1.0 bar
Actual test pressure 50.4 bar
Pressure Duration (60 ± 5 min) 60 min
Leakage (None) None
Joint Effectiveness - (P/F) Pass

TCS 2211.2 (Issue 2) Contamination (vacuum when submerged) (Proc. 18634) (WP1390)
Technician ID RLACEY
Date Analysed 26-05-2022
Temperature (20 ± 10 °C) 17 deg C
Pipe Nominal Diameter 315 mm
Minimum Submerged Depth Fully Submerged

FI20220531082634 J-00427215 Page 12 of 29


<< Results >> (Continued)

TCS 2211.2 (Issue 2) Contamination (vacuum when submerged) (Proc. 18634) (WP1390) (Continued)
Actual Submerged Depth 650 mm
Vacuum Applied (-0.9 Bar to -1.0 Bar) -0.95 Bar
Time (60 ± 5 min) 60 min
Water Ingress (None Reqd) None
Vacuum Test Result Pass

Tension Test (See below for test code used) (WP1625)


Technician ID RLACEY
Date Analysed 27-05-2022
Tension test - (Pass/Fail) Not Applicable
Comments Electrofusion fittings

† TCS 4001.11 (Issue 1) Visual inspection (Proc. 18685) (WP1397)


Technician ID BBOWEN
Date Analysed 18-05-2022
Visual Confirmation of Sample Does / do the samples submitted for
testing visually conform (without
dismantling) to the product(s) that were
identified as representative of the range for
which approval is sought?
Visual Confirmation of Sample Result Yes
Confirmation of Sub Components Does / do the individually declared sub-
component(s) used in the sample
submitted for testing appear to be those
that were declared in the application?
Confirmation of Sub Components Result Yes

FI20220531082634 J-00427215 Page 13 of 29


Sample ID: S-0001909340
Sample Name: DN20/DN40 16bar
Sample Description: PE100 SDR11 pipe – 21.51.164020 Reducer connected to 400mm PE100 SDR11 pipe including
21.20.160040 spigot saddle and end cap electrofusion fittings.
Sample Received: 18-MAY-2022

Product Type: Polyethylene electrofusion fittings for use with polyetheylene pipe ( EN 12201-3)
Model Number/Trade Designation: PE100 SDR7.4 pipe: 21.51.164020 (Socket) 21.20.160040 (Spigot saddle)
connected to end cap (for testing purposes).
Maximum Working Pressure: 16 Bar
Maximum Operating Temperature: 20 deg C
Comments: Cold Water Use Only. Tested and for use with PE100 Pipe (EN 12201-2)

<< Results >>

TCS 6001.1 (A) (Issue 7) Marking for Identification (All fittings) (Proc. 18703) (WP1355)
Technician ID BBOWEN
Date Analysed 18-05-2022
Product Marking and location EURO, PE100, size, SDR, PN and date of
manufacture (MM/YY) on the fitting
TCS Clause (A, A+B, A+C, A+D, A+E, A+F) A
Permanence of Marking Yes
Marking for Identification (P/F) Pass

TCS 1412.1 (Issue 3) Corrosion protection. (Proc. 18593) (WP1343)


Technician ID RLACEY
Date Analysed 27-05-2022
List Metals in Contact No metals in contact
Coating Irregularities (None Reqd) None
Electrochem Test Result Pass

TCS 2111.1 (Issue 3) Effect upon water quality (non-metallic materials) (Proc. 18629) (WP1385)
Technician ID RLACEY
Date Analysed 27-05-2022
Non Metallic Materials Please see attached declaration

TCS 5011.1 (Issue 3) Measurement of linear dimensions (Proc. 18688) (WP1354)


Technician ID RLACEY
Date Analysed 27-05-2022
Linear Dimensions 21.51.164020 Socket (DN20 x DN40) with
21.20.160040 spigot saddle (DN40 x
DN40)
Linear Dimension Result (P/F) Pass

TCS 1315.2 (Issue 3) Torque (Connection and Disconnection) (Proc. 18586) (WP1374)
Technician ID RLACEY
Date Analysed 27-05-2022
Torque Test - (P/F) Not Applicable

FI20220531082634 J-00427215 Page 14 of 29


<< Results >> (Continued)

TCS 1315.2 (Issue 3) Torque (Connection and Disconnection) (Proc. 18586) (WP1374) (Continued)
Comments Electrofusion fittings

TCS 2114.2 (Issue 4) Opacity (Proc. 18632) (WP1349)


Technician ID RLACEY
Date Analysed 27-05-2022
Opacity test result - P/F Not Applicable
comment For underground use only (R008)

TCS 1112.1 (N) (Issue 3) Porosity – All Other Valves-Fittings (Proc. 28705) (WP1368)
Technician ID RLACEY
Date Analysed 26-05-2022
Temperature (20 ± 10 deg C) 17 deg C
Above or Below Ground Use Below Ground
Pressure Rating (PN) 16 bar
Pressure multiplier x 2.0
Required Test Pressure 32 bar
Test pressure limits ± 1.0 bar
Actual test pressure 32.5 bar
Hydraulic Pressure Duration (60 ± 5 sec) 60 sec
Leakage (None) None
Porosity Test - (P/F) Pass

TCS 1312.9 (A) (Issue 2) Deformation – Non BS Fittings (Proc. 18556) (WP1382)
Technician ID RLACEY
Date Analysed 27-05-2022
Deformation Test Result (P/F) Not Applicable
Comments Electrofusion fittings

TCS 1113.2 (A) (Issue 2) Joint Effectiveness (Proc. 28708) (WP1375)


Technician ID RLACEY
Date Analysed 26-05-2022
Temperature (20 ± 10 Deg C) 17 Deg C
Test pressure required 32 bar
Test pressure Limits ± 1.0 bar
Actual test pressure 32.6 bar
Pressure Duration (60 ± 5 min) 60 min
Leakage (None) None
Joint Effectiveness - (P/F) Pass

TCS 2211.2 (Issue 2) Contamination (vacuum when submerged) (Proc. 18634) (WP1390)
Technician ID RLACEY
Date Analysed 26-05-2022
Temperature (20 ± 10 °C) 17 deg C

FI20220531082634 J-00427215 Page 15 of 29


<< Results >> (Continued)

TCS 2211.2 (Issue 2) Contamination (vacuum when submerged) (Proc. 18634) (WP1390) (Continued)
Pipe Nominal Diameter 40 mm
Minimum Submerged Depth 10 Times Diameter
Actual Submerged Depth 400 mm
Vacuum Applied (-0.9 Bar to -1.0 Bar) -0.95 Bar
Time (60 ± 5 min) 60 min
Water Ingress (None Reqd) None
Vacuum Test Result Pass

Tension Test (See below for test code used) (WP1625)


Technician ID RLACEY
Date Analysed 27-05-2022
Tension test - (Pass/Fail) Not Applicable
Comments Electrofusion fittings

† TCS 4001.11 (Issue 1) Visual inspection (Proc. 18685) (WP1397)


Technician ID BBOWEN
Date Analysed 18-05-2022
Visual Confirmation of Sample Does / do the samples submitted for
testing visually conform (without
dismantling) to the product(s) that were
identified as representative of the range for
which approval is sought?
Visual Confirmation of Sample Result Yes
Confirmation of Sub Components Does / do the individually declared sub-
component(s) used in the sample
submitted for testing appear to be those
that were declared in the application?
Confirmation of Sub Components Result Yes

FI20220531082634 J-00427215 Page 16 of 29


Sample ID: S-0001909341
Sample Name: DN75 16bar
Sample Description: PE100 SDR11 pipe – 21.00.160075 Socket connected to 300mm PE100 SDR11 pipe including
21.20.160075 spigot saddle and 21.36.160075 End cap electrofusion fittings.
Sample Received: 18-MAY-2022

Product Type: Polyethylene electrofusion fittings for use with polyetheylene pipe ( EN 12201-3)
Model Number/Trade Designation: PE100 SDR11 pipe: 21.00.160075 (Socket) 21.20.160075 (Spigot saddle)
21.36.160075 (End cap).
Maximum Working Pressure: 16 Bar
Maximum Operating Temperature: 20 deg C
Comments: Cold Water Use Only. Tested and for use with PE100 Pipe (EN 12201-2)

<< Results >>

TCS 6001.1 (A) (Issue 7) Marking for Identification (All fittings) (Proc. 18703) (WP1355)
Technician ID BBOWEN
Date Analysed 18-05-2022
Product Marking and location EURO, PE100, size, SDR, PN and date of
manufacture (MM/YY) on the fitting
TCS Clause (A, A+B, A+C, A+D, A+E, A+F) A
Permanence of Marking Yes
Marking for Identification (P/F) Pass

TCS 1412.1 (Issue 3) Corrosion protection. (Proc. 18593) (WP1343)


Technician ID RLACEY
Date Analysed 27-05-2022
List Metals in Contact No metals in contact
Coating Irregularities (None Reqd) None
Electrochem Test Result Pass

TCS 2111.1 (Issue 3) Effect upon water quality (non-metallic materials) (Proc. 18629) (WP1385)
Technician ID RLACEY
Date Analysed 27-05-2022
Non Metallic Materials Please see attached declaration

TCS 5011.1 (Issue 3) Measurement of linear dimensions (Proc. 18688) (WP1354)


Technician ID RLACEY
Date Analysed 27-05-2022
Linear Dimensions 21.00.160075 Socket (DN75 x DN75)
21.20.160075 Spigot saddle (DN75 x
DN75) 21.36.160075 End cap (DN75)
Linear Dimension Result (P/F) Pass

TCS 1315.2 (Issue 3) Torque (Connection and Disconnection) (Proc. 18586) (WP1374)
Technician ID RLACEY
Date Analysed 27-05-2022
Torque Test - (P/F) Not Applicable

FI20220531082634 J-00427215 Page 17 of 29


<< Results >> (Continued)

TCS 1315.2 (Issue 3) Torque (Connection and Disconnection) (Proc. 18586) (WP1374) (Continued)
Comments Electrofusion fittings

TCS 2114.2 (Issue 4) Opacity (Proc. 18632) (WP1349)


Technician ID RLACEY
Date Analysed 27-05-2022
Opacity test result - P/F Not Applicable
comment For underground use only (R008)

TCS 1112.1 (N) (Issue 3) Porosity – All Other Valves-Fittings (Proc. 28705) (WP1368)
Technician ID RLACEY
Date Analysed 26-05-2022
Temperature (20 ± 10 deg C) 17 deg C
Above or Below Ground Use Below Ground
Pressure Rating (PN) 16 bar
Pressure multiplier x 2.0
Required Test Pressure 32 bar
Test pressure limits ± 1.0 bar
Actual test pressure 32.7 bar
Hydraulic Pressure Duration (60 ± 5 sec) 60 sec
Leakage (None) None
Porosity Test - (P/F) Pass

TCS 1312.9 (A) (Issue 2) Deformation – Non BS Fittings (Proc. 18556) (WP1382)
Technician ID RLACEY
Date Analysed 27-05-2022
Deformation Test Result (P/F) Not Applicable
Comments Electrofusion fittings

TCS 1113.2 (A) (Issue 2) Joint Effectiveness (Proc. 28708) (WP1375)


Technician ID RLACEY
Date Analysed 26-05-2022
Temperature (20 ± 10 Deg C) 17 Deg C
Test pressure required 32 bar
Test pressure Limits ± 1.0 bar
Actual test pressure 32.2 bar
Pressure Duration (60 ± 5 min) 60 min
Leakage (None) None
Joint Effectiveness - (P/F) Pass

TCS 2211.2 (Issue 2) Contamination (vacuum when submerged) (Proc. 18634) (WP1390)
Technician ID RLACEY
Date Analysed 26-05-2022
Temperature (20 ± 10 °C) 17 deg C

FI20220531082634 J-00427215 Page 18 of 29


<< Results >> (Continued)

TCS 2211.2 (Issue 2) Contamination (vacuum when submerged) (Proc. 18634) (WP1390) (Continued)
Pipe Nominal Diameter 75 mm
Minimum Submerged Depth Fully Submerged
Actual Submerged Depth 650 mm
Vacuum Applied (-0.9 Bar to -1.0 Bar) -0.95 Bar
Time (60 ± 5 min) 60 min
Water Ingress (None Reqd) None
Vacuum Test Result Pass

Tension Test (See below for test code used) (WP1625)


Technician ID RLACEY
Date Analysed 27-05-2022
Tension test - (Pass/Fail) Not Applicable
Comments Electrofusion fittings

† TCS 4001.11 (Issue 1) Visual inspection (Proc. 18685) (WP1397)


Technician ID BBOWEN
Date Analysed 18-05-2022
Visual Confirmation of Sample Does / do the samples submitted for
testing visually conform (without
dismantling) to the product(s) that were
identified as representative of the range for
which approval is sought?
Visual Confirmation of Sample Result Yes
Confirmation of Sub Components Does / do the individually declared sub-
component(s) used in the sample
submitted for testing appear to be those
that were declared in the application?
Confirmation of Sub Components Result Yes

FI20220531082634 J-00427215 Page 19 of 29


Sample ID: S-0001909342
Sample Name: DN160 16bar
Sample Description: PE100 SDR11 pipe – 21.00.160160 Socket connected to 300mm PE100 SDR11 pipe including
21.20.160160 spigot saddle and 21.36.160160 End cap electrofusion fittings.
Sample Received: 18-MAY-2022

Product Type: Polyethylene electrofusion fittings for use with polyetheylene pipe ( EN 12201-3)
Model Number/Trade Designation: PE100 SDR11 pipe: 21.00.160160 (Socket) 21.20.160160 (spigot saddle)
21.36.160160 (End cap)
Maximum Working Pressure: 16 Bar
Maximum Operating Temperature: 20 deg C
Comments: Cold Water Use Only. Tested and for use with PE100 Pipe (EN 12201-2)

<< Results >>

TCS 6001.1 (A) (Issue 7) Marking for Identification (All fittings) (Proc. 18703) (WP1355)
Technician ID BBOWEN
Date Analysed 18-05-2022
Product Marking and location EURO, PE100, size, SDR, PN and date of
manufacture (MM/YY) on the fitting
TCS Clause (A, A+B, A+C, A+D, A+E, A+F) A
Permanence of Marking Yes
Marking for Identification (P/F) Pass

TCS 1412.1 (Issue 3) Corrosion protection. (Proc. 18593) (WP1343)


Technician ID RLACEY
Date Analysed 27-05-2022
List Metals in Contact No metals in contact
Coating Irregularities (None Reqd) None
Electrochem Test Result Pass

TCS 2111.1 (Issue 3) Effect upon water quality (non-metallic materials) (Proc. 18629) (WP1385)
Technician ID RLACEY
Date Analysed 27-05-2022
Non Metallic Materials Please see attached declaration

TCS 5011.1 (Issue 3) Measurement of linear dimensions (Proc. 18688) (WP1354)


Technician ID RLACEY
Date Analysed 27-05-2022
Linear Dimensions 21.00.160160 Socket (DN160 x DN160)
21.20.160160 spigot saddle (DN160 x
DN160) and 21.36.160160 End cap
(DN160)
Linear Dimension Result (P/F) Pass

TCS 1315.2 (Issue 3) Torque (Connection and Disconnection) (Proc. 18586) (WP1374)
Technician ID RLACEY
Date Analysed 27-05-2022

FI20220531082634 J-00427215 Page 20 of 29


<< Results >> (Continued)

TCS 1315.2 (Issue 3) Torque (Connection and Disconnection) (Proc. 18586) (WP1374) (Continued)
Torque Test - (P/F) Not Applicable
Comments Electrofusion fittings

TCS 2114.2 (Issue 4) Opacity (Proc. 18632) (WP1349)


Technician ID RLACEY
Date Analysed 27-05-2022
Opacity test result - P/F Not Applicable
comment For underground use only (R008)

TCS 1112.1 (N) (Issue 3) Porosity – All Other Valves-Fittings (Proc. 28705) (WP1368)
Technician ID RLACEY
Date Analysed 26-05-2022
Temperature (20 ± 10 deg C) 17 deg C
Above or Below Ground Use Below Ground
Pressure Rating (PN) 16 bar
Pressure multiplier x 2.0
Required Test Pressure 32 bar
Test pressure limits ± 1.0 bar
Actual test pressure 32.5 bar
Hydraulic Pressure Duration (60 ± 5 sec) 60 sec
Leakage (None) None
Porosity Test - (P/F) Pass

TCS 1312.9 (A) (Issue 2) Deformation – Non BS Fittings (Proc. 18556) (WP1382)
Technician ID RLACEY
Date Analysed 27-05-2022
Deformation Test Result (P/F) Not Applicable
Comments Electrofusion fittings

TCS 1113.2 (A) (Issue 2) Joint Effectiveness (Proc. 28708) (WP1375)


Technician ID RLACEY
Date Analysed 26-05-2022
Temperature (20 ± 10 Deg C) 17 Deg C
Test pressure required 32 bar
Test pressure Limits ± 1.0 bar
Actual test pressure 32.5 bar
Pressure Duration (60 ± 5 min) 60 min
Leakage (None) None
Joint Effectiveness - (P/F) Pass

TCS 2211.2 (Issue 2) Contamination (vacuum when submerged) (Proc. 18634) (WP1390)
Technician ID RLACEY
Date Analysed 26-05-2022

FI20220531082634 J-00427215 Page 21 of 29


<< Results >> (Continued)

TCS 2211.2 (Issue 2) Contamination (vacuum when submerged) (Proc. 18634) (WP1390) (Continued)
Temperature (20 ± 10 °C) 17 deg C
Pipe Nominal Diameter 160 mm
Minimum Submerged Depth Fully Submerged
Actual Submerged Depth 650 mm
Vacuum Applied (-0.9 Bar to -1.0 Bar) -0.95 Bar
Time (60 ± 5 min) 60 min
Water Ingress (None Reqd) None
Vacuum Test Result Pass

Tension Test (See below for test code used) (WP1625)


Technician ID RLACEY
Date Analysed 27-05-2022
Tension test - (Pass/Fail) Not Applicable
Comments Electrofusion fittings

† TCS 4001.11 (Issue 1) Visual inspection (Proc. 18685) (WP1397)


Technician ID BBOWEN
Date Analysed 18-05-2022
Visual Confirmation of Sample Does / do the samples submitted for
testing visually conform (without
dismantling) to the product(s) that were
identified as representative of the range for
which approval is sought?
Visual Confirmation of Sample Result Yes
Confirmation of Sub Components Does / do the individually declared sub-
component(s) used in the sample
submitted for testing appear to be those
that were declared in the application?
Confirmation of Sub Components Result Yes

FI20220531082634 J-00427215 Page 22 of 29


Sample ID: S-0001909343
Sample Name: DN250 16bar
Sample Description: PE100 SDR11 pipe including 21.20.160250 spigot saddle with end cap electrofusion fittings.
Sample Received: 18-MAY-2022

Product Type: Polyethylene electrofusion fittings for use with polyetheylene pipe ( EN 12201-3)
Model Number/Trade Designation: PE100 SDR11 pipe: 21.20.160250 (spigot saddle) connected to end cap (for
testing purposes).
Maximum Working Pressure: 16 Bar
Maximum Operating Temperature: 20 deg C
Comments: Cold Water Use Only. Tested and for use with PE100 Pipe (EN 12201-2)

<< Results >>

TCS 6001.1 (A) (Issue 7) Marking for Identification (All fittings) (Proc. 18703) (WP1355)
Technician ID BBOWEN
Date Analysed 18-05-2022
Product Marking and location EURO, PE100, size, SDR, PN and date of
manufacture (MM/YY) on the fitting
TCS Clause (A, A+B, A+C, A+D, A+E, A+F) A
Permanence of Marking Yes
Marking for Identification (P/F) Pass

TCS 1412.1 (Issue 3) Corrosion protection. (Proc. 18593) (WP1343)


Technician ID RLACEY
Date Analysed 27-05-2022
List Metals in Contact No metals in contact
Coating Irregularities (None Reqd) None
Electrochem Test Result Pass

TCS 2111.1 (Issue 3) Effect upon water quality (non-metallic materials) (Proc. 18629) (WP1385)
Technician ID RLACEY
Date Analysed 27-05-2022
Non Metallic Materials Please see attached declaration

TCS 5011.1 (Issue 3) Measurement of linear dimensions (Proc. 18688) (WP1354)


Technician ID RLACEY
Date Analysed 27-05-2022
Linear Dimensions 21.20.160250 spigot saddle (DN250 x
DN250)
Linear Dimension Result (P/F) Pass

TCS 1315.2 (Issue 3) Torque (Connection and Disconnection) (Proc. 18586) (WP1374)
Technician ID RLACEY
Date Analysed 27-05-2022
Torque Test - (P/F) Not Applicable
Comments Electrofusion fittings

FI20220531082634 J-00427215 Page 23 of 29


<< Results >> (Continued)

TCS 2114.2 (Issue 4) Opacity (Proc. 18632) (WP1349) (Continued)


Technician ID RLACEY
Date Analysed 27-05-2022
Opacity test result - P/F Not Applicable
comment For underground use only (R008)

TCS 1112.1 (N) (Issue 3) Porosity – All Other Valves-Fittings (Proc. 28705) (WP1368)
Technician ID RLACEY
Date Analysed 26-05-2022
Temperature (20 ± 10 deg C) 17 deg C
Above or Below Ground Use Below Ground
Pressure Rating (PN) 16 bar
Pressure multiplier x 2.0
Required Test Pressure 32 bar
Test pressure limits ± 1.0 bar
Actual test pressure 32.5 bar
Hydraulic Pressure Duration (60 ± 5 sec) 60 sec
Leakage (None) None
Porosity Test - (P/F) Pass

TCS 1312.9 (A) (Issue 2) Deformation – Non BS Fittings (Proc. 18556) (WP1382)
Technician ID RLACEY
Date Analysed 27-05-2022
Deformation Test Result (P/F) Not Applicable
Comments Electrofusion fittings

TCS 1113.2 (A) (Issue 2) Joint Effectiveness (Proc. 28708) (WP1375)


Technician ID RLACEY
Date Analysed 26-05-2022
Temperature (20 ± 10 Deg C) 17 Deg C
Test pressure required 32 bar
Test pressure Limits ± 1.0 bar
Actual test pressure 32.4 bar
Pressure Duration (60 ± 5 min) 60 min
Leakage (None) None
Joint Effectiveness - (P/F) Pass

TCS 2211.2 (Issue 2) Contamination (vacuum when submerged) (Proc. 18634) (WP1390)
Technician ID CBROAD
Date Analysed 25-05-2022
Temperature (20 ± 10 °C) 17 deg C
Pipe Nominal Diameter 250 mm
Minimum Submerged Depth Fully Submerged

FI20220531082634 J-00427215 Page 24 of 29


<< Results >> (Continued)

TCS 2211.2 (Issue 2) Contamination (vacuum when submerged) (Proc. 18634) (WP1390) (Continued)
Actual Submerged Depth 650 mm
Vacuum Applied (-0.9 Bar to -1.0 Bar) -0.95 Bar
Time (60 ± 5 min) 60 min
Water Ingress (None Reqd) None
Vacuum Test Result Pass

Tension Test (See below for test code used) (WP1625)


Technician ID RLACEY
Date Analysed 27-05-2022
Tension test - (Pass/Fail) Not Applicable
Comments Electrofusion fittings

† TCS 4001.11 (Issue 1) Visual inspection (Proc. 18685) (WP1397)


Technician ID BBOWEN
Date Analysed 18-05-2022
Visual Confirmation of Sample Does / do the samples submitted for
testing visually conform (without
dismantling) to the product(s) that were
identified as representative of the range for
which approval is sought?
Visual Confirmation of Sample Result Yes
Confirmation of Sub Components Does / do the individually declared sub-
component(s) used in the sample
submitted for testing appear to be those
that were declared in the application?
Confirmation of Sub Components Result Yes

FI20220531082634 J-00427215 Page 25 of 29


Sample ID: S-0001909344
Sample Name: 21.00.100400 Socket
Sample Description: PE100 SDR17 pipe – 21.00.100400 Socket DN400 10bar
Sample Received: 18-MAY-2022

Product Type: Polyethylene electrofusion fittings for use with polyetheylene pipe ( EN 12201-3)
Model Number/Trade Designation: PE100 SDR17 pipe: 21.00.100400 (Socket) connected to an end cap (for testing
purposes).
Maximum Working Pressure: 10 Bar
Maximum Operating Temperature: 20 deg C
Comments: Cold Water Use Only. Tested and for use with PE100 Pipe (EN 12201-2)

<< Results >>

TCS 6001.1 (A) (Issue 7) Marking for Identification (All fittings) (Proc. 18703) (WP1355)
Technician ID BBOWEN
Date Analysed 18-05-2022
Product Marking and location EURO, PE100, size, SDR, PN and date of
manufacture (MM/YY) on the fitting
TCS Clause (A, A+B, A+C, A+D, A+E, A+F) A
Permanence of Marking Yes
Marking for Identification (P/F) Pass

TCS 1412.1 (Issue 3) Corrosion protection. (Proc. 18593) (WP1343)


Technician ID RLACEY
Date Analysed 27-05-2022
List Metals in Contact No metals in contact
Coating Irregularities (None Reqd) None
Electrochem Test Result Pass

TCS 2111.1 (Issue 3) Effect upon water quality (non-metallic materials) (Proc. 18629) (WP1385)
Technician ID RLACEY
Date Analysed 27-05-2022
Non Metallic Materials Please see attached declaration

TCS 5011.1 (Issue 3) Measurement of linear dimensions (Proc. 18688) (WP1354)


Technician ID RLACEY
Date Analysed 27-05-2022
Linear Dimensions 21.00.100400 Socket (DN400 x DN400)
Linear Dimension Result (P/F) Pass

TCS 1315.2 (Issue 3) Torque (Connection and Disconnection) (Proc. 18586) (WP1374)
Technician ID RLACEY
Date Analysed 27-05-2022
Torque Test - (P/F) Not Applicable
Comments Electrofusion fittings

TCS 2114.2 (Issue 4) Opacity (Proc. 18632) (WP1349)

FI20220531082634 J-00427215 Page 26 of 29


<< Results >> (Continued)

TCS 2114.2 (Issue 4) Opacity (Proc. 18632) (WP1349) (Continued)


Technician ID RLACEY
Date Analysed 27-05-2022
Opacity test result - P/F Not Applicable
comment For underground use only (R008)

TCS 1112.1 (N) (Issue 3) Porosity – All Other Valves-Fittings (Proc. 28705) (WP1368)
Technician ID RLACEY
Date Analysed 27-05-2022
Temperature (20 ± 10 deg C) 15 deg C
Above or Below Ground Use Below Ground
Pressure Rating (PN) 10 bar
Pressure multiplier x 2.0
Required Test Pressure 20 bar
Test pressure limits ± 0.5 Bar
Actual test pressure 20.4 bar
Hydraulic Pressure Duration (60 ± 5 sec) 60 sec
Leakage (None) None
Porosity Test - (P/F) Pass

TCS 1312.9 (A) (Issue 2) Deformation – Non BS Fittings (Proc. 18556) (WP1382)
Technician ID RLACEY
Date Analysed 27-05-2022
Deformation Test Result (P/F) Not Applicable
Comments Electrofusion fittings

TCS 1113.2 (A) (Issue 2) Joint Effectiveness (Proc. 28708) (WP1375)


Technician ID RLACEY
Date Analysed 27-05-2022
Temperature (20 ± 10 Deg C) 15 Deg C
Test pressure required 20 bar
Test pressure Limits ± 0.5 Bar
Actual test pressure 20.4 bar
Pressure Duration (60 ± 5 min) 60 min
Leakage (None) None
Joint Effectiveness - (P/F) Pass

TCS 2211.2 (Issue 2) Contamination (vacuum when submerged) (Proc. 18634) (WP1390)
Technician ID CBROAD
Date Analysed 25-05-2022
Temperature (20 ± 10 °C) 17 deg C
Pipe Nominal Diameter 400 mm
Minimum Submerged Depth Fully Submerged

FI20220531082634 J-00427215 Page 27 of 29


<< Results >> (Continued)

TCS 2211.2 (Issue 2) Contamination (vacuum when submerged) (Proc. 18634) (WP1390) (Continued)
Actual Submerged Depth 650 mm
Vacuum Applied (-0.9 Bar to -1.0 Bar) -0.95 Bar
Time (60 ± 5 min) 60 min
Water Ingress (None Reqd) None
Vacuum Test Result Pass

Tension Test (See below for test code used) (WP1625)


Technician ID RLACEY
Date Analysed 27-05-2022
Tension test - (Pass/Fail) Not Applicable
Comments Electrofusion fittings

† TCS 4001.11 (Issue 1) Visual inspection (Proc. 18685) (WP1397)


Technician ID BBOWEN
Date Analysed 18-05-2022
Visual Confirmation of Sample Does / do the samples submitted for
testing visually conform (without
dismantling) to the product(s) that were
identified as representative of the range for
which approval is sought?
Visual Confirmation of Sample Result Yes
Confirmation of Sub Components Does / do the individually declared sub-
component(s) used in the sample
submitted for testing appear to be those
that were declared in the application?
Confirmation of Sub Components Result Yes

FI20220531082634 J-00427215 Page 28 of 29


<< Testing Laboratories >>
Flag Id Address
------------------- ------------------------ ----------------------------------------------------------------------------------
All work performed at: NSF_WALES NSF Wales Ltd.
(Unless otherwise specified) NSF Wales Ltd
Unit 30 Fern Close
Pen-Y-Fan Industrial Estate
Oakdale, Newport
NP11 3EH, UK

NOTES

1. This report is issued in accordance with the laboratory accreditation requirements of the United Kingdom Accreditation
Service (UKAS). NSF Wales Ltd is UKAS accredited against ISO/IEC 17025:2017 for calibration and testing, laboratory
numbers 0248 and 0626 respectively. For details of the laboratory Schedule of Accreditation please see the UKAS
website (www.ukas.com).
2. It provides traceability of measurement to the SI system of units and/or to units of measurement realised at the National
Physical Laboratory or other recognised national metrology institutes.
3. The contents of this report are the copyright of NSF Wales Ltd and all rights are reserved. No part of this publication may
be reproduced, stored in a retrieval system in any form or by any means electronic, mechanical, photocopying, recording or
otherwise, without prior written consent of NSF Wales Ltd.
4. This test report does not constitute approval or endorsement of the product by either NSF Wales Ltd or its parent companies.
5. Any queries regarding this report should be addressed to the authorised signatory at NSF Wales Ltd. Copies of reports are
retained by NSF Wales Ltd for ten years after issue.
6. The results specified in this report relate only to the sample(s) of the product submitted for testing. Any change in the
source or nature of the product or materials used in the product, method of manufacture or application could affect the
performance of the product.
7. Where tests are static and rely on a single measurand, any statements of conformity will be non-binary and will be based
on guard banded acceptance (ref: ILAC-G8:09-2019 4.2.3) which takes into account the estimated uncertainty of
measurement. Measured results within the guard band but below the tolerance limit will be reported as a conditional pass
whilst results within the guard band but outside the tolerance limit will be reported as a conditional fail. Measured results
outside the guard band will be reported as pass or fail as appropriate. The risk of results reported as pass to be outside
the tolerance limit or for results reported as fail to be inside the tolerance limit is < 2.5%.
8. Where tests are dynamic and rely on a number of disparate input variables each with tolerances defined in the specification
for the test, statements of conformity will be binary and based on a simple acceptance rule (ref: ILACG8:09-2019 4.2.3).
Statements of conformity will be reported as pass or fail based on the measured value without taking measurement
uncertainty into account. Uncertainty of measurement for the instrumentation used for each measured value will be
reported alongside the individual measurements. The risk of measured results reported as pass or fail being outside the
tolerance limit is 50%.
9. Where an expanded uncertainty is reported for a test, this will be based on a standard uncertainty multiplied by a coverage
factor k = 2, providing a level of confidence of approximately 95%. The expanded uncertainty will have been carried out in
accordance with UKAS requirements.
10. Test reports utilise the simplified test report format option allowed by ISO/IEC 17025:2017 (reference clause 7.8.1.3).
This simplified report does not include all of the information on the report specified by ISO/IEC 17025:2017
(clauses 7.8.2 to 7.8.7) but as stated in the standard this data is held by the laboratory and is available to
the client on request.
11. Opinions and interpretations in this report are outside the scope of UKAS Accreditation.
12. Non UKAS accredited tests or tests which have been subcontracted will be identified in the following manner:aboratory.
- Tests marked † are not included in the laboratory's ISO 17025 accreditation schedule.
- Tests marked ‡ have not been performed by NSF Wales and have been performed at an approved subcontract laboratory.
13. All work is performed at NSF Wales Ltd laboratory, 30 Fern Close, Pen-Y-Fan Ind Est, Oakdale NP11 3EH, unless otherwise
specified in accordance with point 12 above.

FI20220531082634 J-00427215 Page 29 of 29

You might also like