Table of reinforcement anchorage length & lap length - Eurocode 2 https://eurocodeapplied.com/design/en1992/anchorage-and-lap-length...

Eurocode Project: NWPSP-ICB2


Applied.com
Subject: Anchorage and Laps
Free online calculation tools for structural
design according to Eurocodes Designer:

Date:

Eurocode 2
Table of reinforcement anchorage length and lap
length
Description:
Design aid - Table of reinforcement anchorage length lbd & lap length l0 and associated detailing rules
According to:
EN 1992-1-1:2004+AC2:2010 Sections 8.4 and 8.7
Supported National
Annexes:
Nationally Defined Parameters (NDPs) automatically filled for supported countries (left blank otherwise)

Input
Steel characteristic yield strength fyk = 500 MPa

Nationally Defined Parameters


Coefficient taking account of long term αct = 1
effects and loading effects on the tensile
strength of concrete

Concrete partial material safety factor γc = 1.5

Reinforcement steel partial material γs = 1.15


safety factor

Tables

Design anchorage length lbd for ribbed bars Φ ≤ 32 mm according to EN1992-1-1


§8.4.4 (γc = 1.50, fyk = 500 MPa)
Good bond conditions Poor bond conditions

1 of 7 9/24/2022, 11:20 AM
Table of reinforcement anchorage length & lap length - Eurocode 2 https://eurocodeapplied.com/design/en1992/anchorage-and-lap-length...

• Straight bars in • Straight bars in


tension / • Other-than- tension / • Other-than-
compression straight bars in compression straight bars in
Concrete
tension and tension and
class
• Other-than- adequate cover • Other-than- adequate cover
straight bars in cd > 3Φ straight bars in cd > 3Φ
compression compression

C12/15 66Φ 47Φ 95Φ 66Φ

C16/20 55Φ 39Φ 78Φ 55Φ

C20/25 47Φ 33Φ 67Φ 47Φ

C25/30 41Φ 29Φ 58Φ 41Φ

C30/37 36Φ 26Φ 52Φ 36Φ

C35/45 33Φ 23Φ 47Φ 33Φ

C40/50 30Φ 21Φ 43Φ 30Φ

C45/55 28Φ 20Φ 39Φ 28Φ

C50/60 26Φ 18Φ 37Φ 26Φ

C55/67 25Φ 18Φ 36Φ 25Φ

≥ C60/75 24Φ 17Φ 34Φ 24Φ

Design lap length l0 for ribbed bars Φ ≤ 32 mm, when >50% of the bars are lapped
in one section, according to EN1992-1-1 §8.7.3 (γc = 1.50, fyk = 500 MPa)
Good bond conditions Poor bond conditions

• Straight bars in • Straight bars in


tension / • Other-than- tension / • Other-than-
compression straight bars in compression straight bars in
Concrete
tension and tension and
class
• Other-than- adequate cover • Other-than- adequate cover
straight bars in cd > 3Φ straight bars in cd > 3Φ
compression compression

C12/15 99Φ 70Φ 142Φ 99Φ

C16/20 82Φ 58Φ 117Φ 82Φ

C20/25 71Φ 50Φ 101Φ 71Φ

C25/30 61Φ 43Φ 87Φ 61Φ

C30/37 54Φ 38Φ 77Φ 54Φ

C35/45 49Φ 34Φ 70Φ 49Φ

C40/50 45Φ 31Φ 64Φ 45Φ

2 of 7 9/24/2022, 11:20 AM
Table of reinforcement anchorage length & lap length - Eurocode 2 https://eurocodeapplied.com/design/en1992/anchorage-and-lap-length...

Good bond conditions Poor bond conditions

• Straight bars in • Straight bars in


tension / • Other-than- tension / • Other-than-
compression straight bars in compression straight bars in
Concrete
tension and tension and
class
• Other-than- adequate cover • Other-than- adequate cover
straight bars in cd > 3Φ straight bars in cd > 3Φ
compression compression

C45/55 41Φ 29Φ 59Φ 41Φ

Definition of good and poor bond conditions (reproduced from EN1992-1-1 Figure 8.2)

Notes
1. Other-than-straight bar shapes include a) standard bend, b) standard hook, and c) standard
loop. The detailing rules and the equivalent anchorage length for each of these standard shapes
are defined in EN1992-1-1 Figure 8.1.
2. The condition of adequate cover cd > 3Φ for other-than-straight bars in tension is defined in
EN1992-1-1 Figure 8.3. When adequate cover is not present the anchorage and lap lengths for
other-than-straight bars in compression should be used instead.
3. 'Good' bond conditions are applicable when any of the following conditions is fulfilled: a) Vertical
bars or almost vertical bars inclined at an angle 45° ≤ α ≤ 90° from the horizontal, b) bars that
are located up to 250 mm from the bottom of the formwork for elements with height h ≤ 600 mm,
or c) bars that are located at least 300 mm from the free surface during concreting for elements
with height h > 600 mm. 'Poor' bond conditions are applicable for all other cases and also for
bars in structural elements built with slip-forms, unless it can be shown that 'good' bond
conditions exist. The different bond regions are shown in the figure above that is reproduced
from EN1992-1-1 Figure 8.2.
4. The anchorage and lap lengths presented in the tables are conservative values for ribbed bars
with diameter Φ ≤ 32 mm. The required anchorage and lap length may be further reduced when
one or more of the following conditions are present: a) adequate concrete cover, b) adequate
confinement by transverse reinforcement, c) welded transverse bars along the anchorage length,
and d) compressive pressure transverse to the plane of splitting. The favorable effect of these
factors is described in EN1992-1-1 §8.4.4.
5. The anchorage and lap lengths presented in the tables assume full utilization of the
reinforcement bar yield stress, i.e. the stress of the bar is assumed equal to the design yield
stress fyd = fyk / γs. For ULS verifications when the provided tensile reinforcement As,prov is more

3 of 7 9/24/2022, 11:20 AM
Table of reinforcement anchorage length & lap length - Eurocode 2 https://eurocodeapplied.com/design/en1992/anchorage-and-lap-length...

than than the required reinforcement As,req then the required anchorage and lap lengths may be
reduced by the ratio As,req / As,prov, however the minimum required anchorage length lb,min the
minimum required lap length l0,min should be provided in accordance with EN1992-1-1 §8.4.4(1)
and §8.7.3(1).
6. The lap lengths presented in the tables assume that >50% of the bars are lapped in one section
(i.e. α6 = 1.5). If a smaller percentage of bars is lapped in one section then required lap length
may be multiplied by the factor α6 / 1.5, where α6 = (ρl / 25)0.5 and ρl is the percentage of the
bars lapped in one section. However the minimum required lap length l0,min should be provided
in accordance with EN1992-1-1 §8.7.3(1).
7. According to EN1992-1-1 §8.7.2 laps between bars should normally be staggered and not
located in areas of high moments. The required staggering layout is presented in EN1992-1-1
Figure 8.7. Staggering is not required for compression reinforcement and secondary
(distribution) reinforcement.
8. It is possible that laps between bars are not staggered because this is not feasible or it is very
difficult (e.g. column starter bars). This case is not covered explicitly in the current version of
EN1992-1-1. The authors of this website recommend to increase the provided lap lengths by a
factor of (1.20)3/2 = 1.315 when staggering is not possible. This recommendation is based on the
relevant provision of the next issue of EN1992-1-1 that is currently in draft version.
9. When the reinforcement bars are arranged in more than one horizontal layers then only 50% of
the bars may be lapped in tension in one section according to EN1992-1-1 §8.7.2(4). This is not
required for compression reinforcement and secondary (distribution) reinforcement.
10. When individual bars with diameter Φ larger than 32 mm or bundles of bars with equivalent
diameter Φn larger than 32 mm are used then the required anchorage and lap lengths are
divided by the factor η2 = (132 - Φ) / 100 ≤ 1.0
11. Transverse reinforcement is generally required in the lap zone to resist transverse tensile forces.
See details below for more information.

Details
Calculation of design anchorage length of longitudinal reinforcement according
to EN1992-1-1 §8.4

Ultimate bond stress fbd

The design value of ultimate bond stress for ribbed bars is defined in EN1992-1-1 §8.4.2(2):

fbd = 2.25 ⋅ η1 ⋅ η2 ⋅ fctd

where fctd = αct ⋅ fctk,0.05 / γc is the design tensile strength of concrete determined according to
EN1992-1-1 §3.1.6(2)P.

The coefficient η2 takes into account the effect of large bar diameters Φ > 32 mm as follows:

η2 = min[1.0, (132 - Φ) / 100 ], where Φ in mm

The coefficient η1 is related to the quality of the bond condition and the position of the bar during
concreting. The coefficient η1 takes a value of 1.0 when 'good' bond conditions are obtained and a
value of 0.7 otherwise i.e. when 'poor' bond conditions exist. The distinction between 'good' and 'poor'
bond conditions is provided in EN1992-1-1 Figure 8.2.

'Good' bond conditions are obtained when any of the following conditions is fulfilled:

Vertical bars or almost vertical bars inclined at an angle 45° ≤ α ≤ 90° from the horizontal
Bars that are located up to 250 mm from the bottom of the formwork for elements with height h ≤
600 mm
Bars that are located at least 300 mm from the free surface during concreting for elements with
height h > 600 mm

4 of 7 9/24/2022, 11:20 AM
Table of reinforcement anchorage length & lap length - Eurocode 2 https://eurocodeapplied.com/design/en1992/anchorage-and-lap-length...

'Poor' bond conditions are applicable for all other cases and also for bars in structural elements built
with slip-forms, unless it can be shown that 'good' bond conditions exist.

Basic anchorage length lb,rqd

The basic required anchorage length lb,rqd for anchoring a straight steel bar with diameter Φ under
design stress σsd is defined in EN1992-1-1 Eq. (8.3):

lb,rqd = (Φ / 4) ⋅ (σsd / fbd)

The maximum value of the design steel stress σsd under ULS loads is equal to the design yield
strength of the bar fyd = fyk / γs. When the actual design strength of the bar is smaller than fyd then the
basic required anchorage length is reduced proportionally.

Minimum anchorage length lb,min

When no other limitation is applicable, the provided anchorage length should be at least equal to the
minimum value lb,min as described in EN1992-1-1 §8.4.4(1):

- For anchorages in tension: lb,min ≥ max[0.3⋅lb,rqd, 10⋅Φ, 100 mm]

- For anchorages in compression: lb,min ≥ max[0.6⋅lb,rqd, 10⋅Φ, 100 mm]

Design anchorage length lbd

The design anchorage length lbd is defined in EN1992-1-1 §8.4.4(1) as:

lbd = α1 ⋅ α2 ⋅ α3 ⋅ α4 ⋅ α5 ⋅ lb,rqd ≥ lb,min

where the coefficients α1 to α5 are defined in EN1992-1-1 Table 8.2 and account for various factors
reducing the design anchorage length as follows:

Coefficient α1 accounts for the effect of the shape of the bar (α1 = 1.0 for straight bars, α1 = 0.7
for other-than straight bar shapes such as bend, hook, and loop assuming adequate cover cd >
3⋅Φ, α1 = 1.0 for other-than straight bars without adequate cover), where cd is defined in
EN1992-1-1 Figure 8.3.
Coefficient α2 accounts for the effect of minimum concrete cover: a) For straight bars in tension
α2 = 1 - 0.15⋅(cd - Φ) / Φ) and 0.7 ≤ α2 ≤ 1.0, b) for other-than-straight bars in tension α2 = 1 -
0.15⋅(cd - 3⋅Φ) / Φ) and 0.7 ≤ α2 ≤ 1.0, c) for any bar shape in compression α2 = 1.0
Coefficient α3 accounts for the effect of confinement by transverse reinforcement not welded to
main reinforcement. For bars in tension it takes values 0.7 ≤ α3 ≤ 1.0 depending on the quantity
of transverse reinforcement. For bars in compression α3 = 1.0.
Coefficient α4 accounts for the effect of confinement by welded transverse reinforcement. If the
requirements of EN1992-1-1 Table 8.2 are fulfilled then it can take the value α4 = 0.7.
Coefficient α5 accounts for the effect of confinement by transverse pressure. For bars in tension
it takes values 0.7 ≤ α5 ≤ 1.0 depending on the value of transverse pressure. For bars in
compression α5 is not applicable.
In any case the lower limit of the product (α2⋅α3⋅α5) ≥ 0.7 must be observed.

As a simplified and conservative alternative the equivalent anchorage length lb,eq may be provided that
is lb,eq = α1 ⋅ lb,rqd for straight, bend, hook, and loop bar shapes, or lb,eq = α4 ⋅ lb,rqd for bars with welded
transverse bars. In the provided tables in this calculation the equivalent anchorage length lb,eq is
shown.

Detailing rules for reinforcement anchorage

Standard detailing rules for the anchorage of straight bars and other-than-straight bar shapes (bend,
hook, loop) are provided in EN1992-1-1 Figures 8.1 and 8.3. In general for other-than-straight bars with
standard details according to EN1992-1-1 Figure 8.1 the equivalent anchorage length lb,eq is measured
straight up to the end of the bar shape. For standard details for the anchorage of links and shear
reinforcement see EN1992-1-1 Figure 8.5.

5 of 7 9/24/2022, 11:20 AM
Table of reinforcement anchorage length & lap length - Eurocode 2 https://eurocodeapplied.com/design/en1992/anchorage-and-lap-length...

Calculation of design lap length of longitudinal reinforcement according to


EN1992-1-1 §8.7

Design lap length l0

The design lap length l0 is defined in EN1992-1-1 §8.7.3(1) as:

l0 = α1 ⋅ α2 ⋅ α3 ⋅ α5 ⋅ α6 ⋅ lb,rqd ≥ l0,min

where the coefficients α1 to α5 are as defined above in the estimation of the design anchorage length
lbd.

The coefficient α6 accounts for the percentage ρl of reinforcement bars lapped within ±0.65l0 from the
center of the lap length considered. The coefficient α6 is defined as:

α6 = (ρl / 25)0.5 and 1.0 ≤ α6 ≤ 1.5, where ρl expressed in %.

The maximum value of the coefficient α6 = 1.5 is obtained when the percentage of lapped bars in a
section exceeds 50%. In the provided tables in this calculation the design lap length l0 is calculated
taking into account the value of coefficient α1 and assuming α6 = 1.5. The provided lap lengths are
adequate even when more than 50% of the bars are lapped in a section.

Minimum anchorage length l0,min

When no other limitation is applicable, the provided lap length should be at least equal to the minimum
value l0,min as described in EN1992-1-1 §8.7.3(1):

l0,min ≥ max[0.3⋅α6⋅lb,rqd, 15⋅Φ, 200 mm]

Staggering of laps

According to EN1992-1-1 §8.7.2 laps between bars should normally be staggered and not located in
areas of high moments (e.g. plastic hinges). The required staggering layout is presented in
EN1992-1-1 Figure 8.7. Two adjacent laps are not considered to belong in the same section when the
clear distance between the lap ends is ≥ 0.3l0. Staggering is not required for compression
reinforcement and secondary (distribution) reinforcement. It is possible that laps between bars are not
staggered because this is not feasible or it is very difficult (e.g. column starter bars). This case is not
covered explicitly in the current version of EN1992-1-1. The authors of this website recommend to
increase the provided lap lengths by a factor of (1.20)3/2 = 1.315 when staggering is not possible. This
recommendation is based on the relevant provision of the next issue of EN1992-1-1 that is currently in
draft version.

Detailing rules for reinforcement laps

Standard detailing rules for the arrangement of lapped bars are provided in EN1992-1-1 §8.7.2 and
Figure 8.7:

The lapped bars may be allowed to touch each other.


The clear distance of lapped bars should be in general not greater than 4Φ or 50 mm. Otherwise
the lap length should be increased by a length equal to the clear space where it exceeds 4Φ or
50 mm.
The longitudinal distance between two adjacent laps should not be less than 0.3l0.
In case of adjacent laps, the clear distance between adjacent lapped bars should not be less
than 2Φ or 20 mm.

Transverse reinforcement in the lap zone

The required transverse reinforcement in the lap zone to resist transverse tension forces is described
in EN1992-1-1 §8.7.4. When the diameter of the bar is Φ ≥ 20 mm the total area of the sum of all legs
of transverse reinforcement ΣAst, placed perpendicular to the direction of lapped bars, should be at
least equal to the area As of one lapped bar:

6 of 7 9/24/2022, 11:20 AM
Table of reinforcement anchorage length & lap length - Eurocode 2 https://eurocodeapplied.com/design/en1992/anchorage-and-lap-length...

ΣAst ≥ 1.0 ⋅ As

Additional detailing rules are presented in EN1992-1-1 Figure 8.9:

The required transverse reinforcement should be placed at the outer thirds of the lap length l0,
i.e. at distance ≤ l0 / 3 from the lap ends.
For the case of lapped bars permanently in compression one bar of the transverse reinforcement
should be placed outside each end of the lap length and within 4Φ of the end.
The spacing between transverse reinforcement bars should not exceed 150 mm.
If more than 50% of the reinforcement is lapped at one point and the distance between adjacent
laps at a section is ≤ 10Φ transverse reinforcement should be formed by links or U bars
anchored into the body of the section.
When the diameter of the lapped bars is Φ < 20 mm or the percentage of lapped bars in any
section is less than 25%) then any transverse reinforcement or links necessary for other reasons
may be assumed sufficient without further justification.

Eurocode EurocodeApplied.com

Applied.com Copyright © 2017-2022. All rights reserved.