ALPINE FIRE PROTECTION DISTRICT


2/25/14
FIRE PREVENTION POLICY MANUAL
STANDARD
3-31-2014
FIRE CHIEF APPROVAL EFFECTIVE DATE PIV
1. POST INDICATOR CONTROL VALVE WINDOWS SHALL BE VISIBLE FROM 10’ AWAY AT ALL TIMES. IF WINDOWS
BECOME DEFACED OR CRACKED REPLACE ON ANNUAL SPRINKLER INSPECTION OR TITLE 19 FIVE YEAR SERVICE.

2. 36” OF UNOBSTRUCTED CLEARANCE SHALL BE TO ALL SIDES OF THE POST INDICATOR CONTROL VALVE AT ALL
TIMES, UNLESS APPROVED BY THE FAHJ IN ADVANCE.

POST INDICATOR W/
OUTDOOR LISTED SUPERVISORY
BREAKAWAY PADLOCK
TAMPER SWITCH.

2 COATS OF RUSTOLEUM OIL APPROVED SIGNAGE SECURED TO


BASE SAFETY RED PAINT POST INDICATING CONTROL VALVE AS
SHALL BE APPLIED TO POST PER ALPINE FIRE PROTECTION SIGN
INDICATOR AT LEAST EVERY STANDARDS
FIVE YEARS SUPERVISORY DEVICE CONDUIT &
WIRING FROM FACP INSTALLED AS PER
NFPA 72 STANDARDS.

DASHED LINE AROUND PIPE APPROVED UNDERGROUND SIZE AND


INDICATES APPROVED TYPE OF PIPE PER NFPA 24 STANDARD.
UNDERGROUND
POLYETHYLENE WRAP.

NON RISING STEM UNDERGROUND GATE VALVE WITH POST PLATE.

POST INDICATOR CONTROL VALVE