Professional Documents
Culture Documents
Week 4 - Case Study 2
Week 4 - Case Study 2
Here,
𝑇𝑖 = 26℃
𝑇𝑜,𝑎𝑣 = 35.5℃
1) West Wall
• 𝐴𝑟𝑒𝑎 = 66.89 𝑚2
• 𝑈 = 0.3565 𝑊�
𝐾. 𝑚2
• 𝑊𝑎𝑙𝑙 𝑇𝑦𝑝𝑒 =
• 𝐿𝑀 = 0
• 𝐾=1
• 𝐶𝐿𝑇𝐷 𝑎𝑡 3 𝑃𝑀 = 10℃
• 𝐶𝐿𝑇𝐷 𝑎𝑡 4 𝑃𝑀 = 10℃
• 𝐶𝐿𝑇𝐷 𝑎𝑡 5 𝑃𝑀 = 10℃
• 𝐶𝐿𝑇𝐷𝑐𝑜𝑟𝑟𝑒𝑐𝑡𝑒𝑑 𝑎𝑡 3 𝑃𝑀 = 10.6℃
• 𝐶𝐿𝑇𝐷𝑐𝑜𝑟𝑟𝑒𝑐𝑡𝑒𝑑 𝑎𝑡 4 𝑃𝑀 = 10.6℃
• 𝐶𝐿𝑇𝐷𝑐𝑜𝑟𝑟𝑒𝑐𝑡𝑒𝑑 𝑎𝑡 5 𝑃𝑀 = 10.6℃
U A CLTDc Qt = U x A x CLTDc
[W/K.m2] [m2] [K] [W]
2) East Wall
• 𝐴𝑟𝑒𝑎 = 30.21 𝑚2
• 𝑈 = 0.3565 𝑊�
𝐾. 𝑚2
• 𝑊𝑎𝑙𝑙 𝑇𝑦𝑝𝑒 =
• 𝐿𝑀 = 0
• 𝐾=1
• 𝐶𝐿𝑇𝐷 𝑎𝑡 3 𝑃𝑀 = 12.2℃
• 𝐶𝐿𝑇𝐷 𝑎𝑡 4 𝑃𝑀 = 12.8℃
• 𝐶𝐿𝑇𝐷 𝑎𝑡 5 𝑃𝑀 = 13.3℃
• 𝐶𝐿𝑇𝐷𝑐𝑜𝑟𝑟𝑒𝑐𝑡𝑒𝑑 𝑎𝑡 3 𝑃𝑀 = 11.71℃
• 𝐶𝐿𝑇𝐷𝑐𝑜𝑟𝑟𝑒𝑐𝑡𝑒𝑑 𝑎𝑡 4 𝑃𝑀 = 11.985℃
• 𝐶𝐿𝑇𝐷𝑐𝑜𝑟𝑟𝑒𝑐𝑡𝑒𝑑 𝑎𝑡 5 𝑃𝑀 = 12.265℃
U A CLTDc Qt = U x A x CLTDc
[W/K.m2] [m2] [K] [W]
• 𝐶𝐿𝑇𝐷 𝑎𝑡 3 𝑃𝑀 = 5.55℃
• 𝐶𝐿𝑇𝐷 𝑎𝑡 4 𝑃𝑀 = 5.55℃
• 𝐶𝐿𝑇𝐷 𝑎𝑡 5 𝑃𝑀 = 6.11℃
• 𝐶𝐿𝑇𝐷𝑐𝑜𝑟𝑟𝑒𝑐𝑡𝑒𝑑 𝑎𝑡 3 𝑃𝑀 = 8.65℃
• 𝐶𝐿𝑇𝐷𝑐𝑜𝑟𝑟𝑒𝑐𝑡𝑒𝑑 𝑎𝑡 4 𝑃𝑀 = 8.65℃
• 𝐶𝐿𝑇𝐷𝑐𝑜𝑟𝑟𝑒𝑐𝑡𝑒𝑑 𝑎𝑡 5 𝑃𝑀 = 8.93℃
U A CLTDc Qt = U x A x CLTDc
[W/K.m2] [m2] [K] [W]
• 𝐶𝐿𝑇𝐷 𝑎𝑡 3 𝑃𝑀 = 5.55℃
• 𝐶𝐿𝑇𝐷 𝑎𝑡 4 𝑃𝑀 = 5.55℃
• 𝐶𝐿𝑇𝐷 𝑎𝑡 5 𝑃𝑀 = 6.11℃
• 𝐶𝐿𝑇𝐷𝑐𝑜𝑟𝑟𝑒𝑐𝑡𝑒𝑑 𝑎𝑡 3 𝑃𝑀 = 8.65℃
• 𝐶𝐿𝑇𝐷𝑐𝑜𝑟𝑟𝑒𝑐𝑡𝑒𝑑 𝑎𝑡 4 𝑃𝑀 = 8.65℃
• 𝐶𝐿𝑇𝐷𝑐𝑜𝑟𝑟𝑒𝑐𝑡𝑒𝑑 𝑎𝑡 5 𝑃𝑀 = 8.93℃
U A CLTDc Qt = U x A x CLTDc
[W/K.m2] [m2] [K] [W]
5) Roof
• Flat Type Roof
• 𝐴𝑟𝑒𝑎 = 371.61 𝑚2
• 𝑈 = 0.606 𝑊�
𝐾. 𝑚2
• 𝑊𝑎𝑙𝑙 𝑇𝑦𝑝𝑒 =
• 𝐿𝑀 = 1
• 𝐾=1
• 𝐶𝐿𝑇𝐷 𝑎𝑡 3 𝑃𝑀 = 20℃
• 𝐶𝐿𝑇𝐷 𝑎𝑡 4 𝑃𝑀 = 22.2℃
• 𝐶𝐿𝑇𝐷 𝑎𝑡 5 𝑃𝑀 = 23.9℃
• 𝐶𝐿𝑇𝐷𝑐𝑜𝑟𝑟𝑒𝑐𝑡𝑒𝑑 𝑎𝑡 3 𝑃𝑀 = 15.875℃
• 𝐶𝐿𝑇𝐷𝑐𝑜𝑟𝑟𝑒𝑐𝑡𝑒𝑑 𝑎𝑡 4 𝑃𝑀 = 16.985℃
• 𝐶𝐿𝑇𝐷𝑐𝑜𝑟𝑟𝑒𝑐𝑡𝑒𝑑 𝑎𝑡 5 𝑃𝑀 = 17.82℃
U A CLTDc Qt = U x A x CLTDc
[W/K.m2] [m2] [K] [W]
B. Glaze Conduction:
Here,
𝑇𝑖 = 26℃
𝑇𝑜,𝑎𝑣 = 35.5℃
• 𝐴𝑟𝑒𝑎 = 26.73 𝑚2
• 𝑈 = 1.887 𝑊�
𝐾. 𝑚2
• 𝐶𝐿𝑇𝐷 𝑎𝑡 3 𝑃𝑀 = 17.01℃
• 𝐶𝐿𝑇𝐷 𝑎𝑡 4 𝑃𝑀 = 17.01℃
• 𝐶𝐿𝑇𝐷 𝑎𝑡 5 𝑃𝑀 = 15.89℃
• 𝐶𝐿𝑇𝐷𝑐𝑜𝑟𝑟𝑒𝑐𝑡𝑒𝑑 𝑎𝑡 3 𝑃𝑀 = 14.38℃
• 𝐶𝐿𝑇𝐷𝑐𝑜𝑟𝑟𝑒𝑐𝑡𝑒𝑑 𝑎𝑡 4 𝑃𝑀 = 14.38℃
• 𝐶𝐿𝑇𝐷𝑐𝑜𝑟𝑟𝑒𝑐𝑡𝑒𝑑 𝑎𝑡 5 𝑃𝑀 = 13.82℃
U A CLTDc Qt = U x A x CLTDc
[W/K.m2] [m2] [K] [W]
C. Solar Glaze:
𝑄̇𝑡 = 𝐴 × 𝑆𝐻𝐺𝐹𝑚𝑎𝑥 × 𝑆𝐶 × 𝐶𝐿𝐹𝑡
• 𝑆𝐻𝐺𝐹𝑚𝑎𝑥 = 526.885 𝑚2
• 𝑆𝐶 = 1
• 𝐴𝑟𝑒𝑎 = 26.73 𝑚2
• 𝐶𝐿𝑇𝐷𝑡 𝑎𝑡 3 𝑃𝑀 = 0.22℃
• 𝐶𝐿𝑇𝐷𝑡 𝑎𝑡 4 𝑃𝑀 = 0.2℃
• 𝐶𝐿𝑇𝐷𝑡 𝑎𝑡 5 𝑃𝑀 = 0.16℃
D. Air Exchange:
𝑄� = 1.2 × 𝑉̇ × (𝑇𝑜 − 𝑇𝑖 )
E. Internal gains:
1. Lights
• 𝑇𝑜𝑡𝑎𝑙 𝐿𝑖𝑔ℎ𝑡𝑠 = 16
• 𝐺𝑎𝑖𝑛 𝑝𝑒𝑟 𝐿𝑖𝑔ℎ𝑡 = 40 𝑊
• 𝐶𝐿𝐹
o 𝐶𝐿𝐹𝑡 𝑎𝑡 3 𝑃𝑀 = 0.73
o 𝐶𝐿𝐹𝑡 𝑎𝑡 4 𝑃𝑀 = 0.75
o 𝐶𝐿𝐹𝑡 𝑎𝑡 5 𝑃𝑀 = 0.76
• 𝑇𝑜𝑡𝑎𝑙 𝐺𝑎𝑖𝑛 𝑓𝑟𝑜𝑚 𝐿𝑖𝑔ℎ𝑡𝑠 𝑖𝑠 𝑐𝑎𝑙𝑐𝑢𝑙𝑎𝑡𝑒𝑑 𝑎𝑠 𝑓𝑜𝑙𝑙𝑜𝑤𝑠
Gain/unit Ǭ Ǭt = Ǭ x CLFt
Number CLFt
[W] [W] [W]
16 40 640 0.73 0.75 0.76 467.2 480 486.4
2. Occupants
• 𝑇𝑜𝑡𝑎𝑙 𝑜𝑐𝑐𝑢𝑝𝑎𝑛𝑐𝑦 = 425
• 𝐺𝑎𝑖𝑛 𝑝𝑒𝑟 𝑜𝑐𝑐𝑢𝑝𝑎𝑛𝑡 = 75 𝑊
• 𝑇𝑜𝑡𝑎𝑙 𝐺𝑎𝑖𝑛 𝑓𝑟𝑜𝑚 𝑜𝑐𝑐𝑢𝑝𝑎𝑛𝑡𝑠 = 31875 𝑊
3. Appliances
• 𝐶𝐿𝐹 = 1
o 𝑃𝑟𝑜𝑗𝑒𝑐𝑡𝑜𝑟 𝐼𝑛𝑝𝑢𝑡 = 175 𝑊
o 𝑆𝑜𝑢𝑛𝑑 𝑆𝑦𝑠𝑡𝑒𝑚 𝐼𝑛𝑝𝑢𝑡 = 120 𝑊
o 𝐿𝑎𝑝𝑡𝑜𝑝 𝐼𝑛𝑝𝑢𝑡 = 25 𝑊
• 𝑇𝑜𝑡𝑎𝑙 𝐺𝑎𝑖𝑛 𝑓𝑟𝑜𝑚 𝑎𝑝𝑝𝑙𝑖𝑎𝑛𝑐𝑒𝑠 = 320 𝑊
Sound
Projector Laptop Total Input Total Input * CLF
System CLF
[W] [W] [W] [W]
[W]
175 25 120 320 1 320
V° Q = hfg x Cp x V° x ( ωo - ωi )
Cp x Hfg ωo ωi
[L/s] [W]
3187.5 3010 0.029 0.0105 177495.9375
B. Occupants:
• 𝐿𝑎𝑡𝑒𝑛𝑡 ℎ𝑒𝑎𝑡 𝑔𝑎𝑖𝑛 𝑝𝑒𝑟 𝑜𝑐𝑐𝑢𝑝𝑎𝑛𝑡 = 55 𝑊
• 𝑇𝑜𝑡𝑎𝑙 𝑛𝑜 𝑜𝑓 𝑜𝑐𝑐𝑢𝑝𝑎𝑛𝑡𝑠 = 425
• 𝑇𝑜𝑡𝑎𝑙 𝐺𝑎𝑖𝑛 𝑓𝑟𝑜𝑚 𝑜𝑐𝑐𝑢𝑝𝑎𝑛𝑡𝑠 = 23375 𝑊
Total load
𝑄̇𝑐𝑜𝑜𝑙 = 𝑇𝑜𝑡𝑎𝑙 𝑆𝑒𝑛𝑠𝑖𝑏𝑙𝑒 + 𝑇𝑜𝑡𝑎𝑙 𝐿𝑎𝑡𝑒𝑛𝑡