Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

LUMINAIRE KIM LIGHTING

TYPE 4C or 2C/VLA29W5/
1000HPS/480 VOLT/DB-P.
LUMINAIRE TOPS TO BE
EACH LUMINAIRE TO HAVE MOUNTED LEVEL.
ITS OWN ELECTRIC SERVICE
BROUGHT DOWN TO HANDHOLE CABLE GRIPS
1 EACH PER CABLE

OWNER FURNISHED LUMINAIRES, POLE,


#12-2 W/GRD AWG BASE COVER, ANCHOR BOLTS, AND 1000W HPS
TYPE ’UF’, SOLID CU LAMPS, CONTRACTOR SHALL PROVIDE CONCRETE
1 EACH PER LUMINAIRE BASE, CONDUIT, CABLES, GROUND ROD,
ASSEMBLE, SET AND WIRE POLE,

50’
AND GROUT BASE
50 ’ STEEL POLE 2-PIECE
TAPERED ROUND POLE
KIM PTRS50-11188 C/DB-P
NOTE: POLE SHALL BE VISUALLY TRUE
& VERTICAL. FOUNDATION SHALL BE
HANDHOLE FOR WIRING ACCESS. PLUMB & TRUE ON ALL SIDES.
CONDUCTOR TAILS TO EXTEND
18" FROM HANDHOLE. IN-LINE
ISU ID# PLACED UNDER EACH
FUSES TO BE INSTALLED ON
LUMINAIRE. ISU SUPPLIED,
EACH CONDUCTOR.
CONTRACTOR INSTALLED.

GROUT. PROVIDE CHANNEL THROUGH THE


GROUND TO CONNECT TO GROUT FOR LIQUID DRAINAGE FROM POLE
GROUND BOSS IN POLE INTERIOR

1" CHAMFER
3
4"
PVC SCH 40 CONDUIT
BOND GROUND FOR GROUND CABLE

36"
CONDUCTOR
TO REBAR #6 AWG B.C.

6 - #6 BARS EQUAL
SPACING. 2" CLEARANCE #3 TIES AT 12"
FROM ANY SURFACE
GRADE

CONNECT WITH CADWELD

2’
OR BURNDY TYPE YGHPC 95% STANDARD COMPACT
HYTAP CONNECTION FILL AS REQUIRED

8’-0"
GROUND ROD 2" SCH 40 PVC CONDUITS
5
" x 10’-0" AS REQUIRED.
8
INSTALL 1 EA. EXTRA FOR
4000 PSI CONCRETE FUTURE USE. CAP CONDUIT
FOOTING 24" DIAMETER UNDERGROUND.

TYPICAL 50 FT LIGHT POLE FOUNDATION & POLE


SCALE: NONE DATE: 1/07