Download as pdf or txt
Download as pdf or txt
You are on page 1of 16

Design Recommendations

For Pump Stations With Large CenTrifugal Flygt Wastewater Pumps


2
Contents

Flygt large centrifugal pumps introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

General considerations for sump design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Xylem standard sump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Sump dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Required sump volume . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Minimum stop levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Installation tips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Installation tips for submerged pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Installation tips for dry installed submersible pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Importance of duty point . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Systems Engineering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

This brochure is intended to help application engineers, Operating costs can be reduced with the help of effective
designers, planners, and users of sewage and stormwater planning and suitable operation schedules.
systems who are incorporating submerged submersible
and dry installed Flygt pumps into their design. Xylem personnel and publications are available to offer
guidance in these areas. Transient analysis such as air
A proper design of the pump sump in such installations is chamber dimensioning, valve selection, etc. should also
crucial. Two important design requirements to be met are: be considered in wastewater pump station design. These
the prevention of significant quantities of air from reaching matters are not addressed in this brochure, but we can offer
the impeller, and disposal of settled and floating solids. advice on these topics.
The Flygt standard pump sump can be used as it is, or with
appropriate variations to meet the requirements of Please consult with our engineers to achieve optimum
most installations. pump performance, maximum pump life, and a
guarantee that product warranties are met. The design
The pump and sump are parts of an overall system that also recommendations are only valid for Flygt products. Xylem
includes a variety of structures and other elements such as assumes no lia­bility for non-Xylem equipment.
ventilation systems and handling equipment.

3
Flygt large centrifugal Flygt dry installed pumps are easy to maintain. The motor
and impeller assembly can easily be lifted out of the pump
pumps introduction volute for overhaul and repair. The submersible pump/
motor unit also provides the possibility of a flood proof
Flygt large centrifugal submersible pumps have been used pumping station for safe operation at all times.
in a variety of applications all over the world. Pumps can
be either submerged or dry installed. Applications include
wastewater pumping stations in a variety of sizes as well as
intake stations to treatment plants, storm water pumping,
irrigation, mine applications, shipyards, and more.

Flygt submersible centrifugal pumps offer important


advantages such as:
• A compact motor and pump unit
• No separate lubrication system
• Low operating sound level
• N impellers which provide sustained efficiency and
enhanced reliability due to a unique hydraulic design
• Flood proof pumping stations even for dry installed
pumps
• Automatic connection and disconnection for
submerged installations. This allows for fast and easy
installation, inspection, and service.
• Minimal station superstructure

Our submerged pumps are installed on a discharge


connection bolted to the pit floor. The pump is guided to
its position with double permanently installed 3” pipes.
The connection is automatic and needs no visibility. The
pump is just lowered onto the discharge connection and is
held in position by its own weight. Retrieval of the pump is
just as simple. General considerations for
sump design
Ideally, the flow of fluid into any pump should be uniform,
steady, and free from swirl and entrained air. Lack of
uniformity can cause a pump to operate at a lower
efficiency. Unsteady flow causes the load on the impeller
to fluctuate, which can lead to noise, vibration, and bearing
problems.

Swirl in the pump intake can cause a significant change


in the operating conditions for a pump, and can produce
changes in the flow capacity, power requirements, and
efficiency. It can also result in local vortex-type pressure
reductions that induce air cores extending into the pump.
This, and any other air ingestion, can cause reductions in
pump flow and fluctuations of impeller load which result
in noise and vibration with consequent physical damage.
Additionally, these fluctuations can impact process loads in
other parts of the system.

4
The design of a sump should not only provide proper • The sump should be as small and as simple as feasible
approach flow to the pumps, it should also prevent the to minimize construction costs, however, a minimum
accumulation of sediments and surface scum in the sump. sump volume may be specified for other reasons, such
The following points must be considered: as to provide for a minimum retention time, or to ensure
• Flow of water from the sump entrance should that only a certain number of pump starts per hour
be directed toward the pump inlets in such a way that occur.
the flow reaches the inlets with a minimum of swirl and
Principles to be adopted in the design of any sump
energy loss.
are given in a number of design guides or “codes of
• In order to prevent the formation of air-entraining practice” – for example, both the American Hydraulic
surface vortices in the sump, the walls must be designed Institute and the British Hydromechanics Research
and built to avoid stagnation regions in the flow. A Association have published such guides. Nevertheless,
properly placed wall close to the inlet can reduce the whenever a new design departs significantly from
tendency toward localized swirl and vorticity. The water established configurations, model tests of the sump and its
depth must also be great enough to suppress surface approaches should be considered.
vortices.
• Although excessive turbulence or large eddies should
be avoided, some turbulence does help to prevent the Xylem standard sump
formation and growth of vortices.
A sump designed in accordance with this brochure is
• Sediment, which could be foul, must not accumulate smaller than a conventional sump. Consequently, there
within the sump. Stagnant regions, or regions of such may be less buffer volume to accommodate transient
low velocity where sedimentation might occur, must be variations of the flow rate. Nor is there extra retention
avoided. A sloping floor and fillets or benching often volume to store the inflow in excess of the total pump
help to prevent sedimentation. For large variations in capacity (the pipe volumes are usually much larger than
flow, part of the sump can be dedicated to low inflows any pump station volume). A proper design of a complete
with a lower floor level and a small pump. Consult Xylem pump station should therefore consider all critical aspects
for an optimum sump design. of operation. Of course, the pump capacity must match the
• Surface scum, floating sludge, and small debris can extreme inflows to minimize the risk of flooding. Often flow
accumulate in any relatively calm region of the water characteristics of the feeding sewer system should also
surface, and this material must be pumped away. The be analyzed.
water level should be lowered as much as possible
at intervals to increase both velocity and turbulence, The control system for the pumps must also provide
however, air should not be drawn into the pump. Please protection in the event of a power failure. Precise level
consult with an Xylem engineer in order to achieve sensors are crucial if the sump volume is minimized in
optimum pumping performance. The occasional accordance with the recommendations in the
increases in flow velocity will also assist in preventing preceding section.
the accumulation of sediment on the floor.
• Station inflow often approaches the wet well at a The discharge pipe work should be designed to
relatively high elevation. In such cases, the liquid may prevent flooding by the return flow when the pumps are
fall a significant distance as it enters the sump. Such a stopped, and also in emergency situations. The effects
drop can also occur whenever the pumps have lowered of possible pressure surges should be minimized by
the liquid level in the sump to the point at which all appropriate design of the control devices.
pumps are about to be switched off. Therefore, the path
between the sump entrance and the pump inlets must
be sufficiently long for the air to rise to the surface
and escape before reaching the pumps. The energy
of the falling water should be dissipated sufficiently
so that excessively high and irregular velocities do not
occur within the sump. This can be accomplished with
properly designed and correctly positioned baffle walls.

5
To avoid pre-swirl into the pump chamber, the
A1 inlet pipe must have a straight length of five
pipe diameters upstream from the sump. The
exact sump design varies with the number of
pumps and pump size.

The central front high-level entry sump design


is referred to as type A1. In this configuration,
the flow does not have to make a horizontal
turn, which might induce mass rotation in
the sump.

A specially designed baffle wall minimizes


air entrainment due to falling water. The
flow from the inlet pipe strikes the partition
wall then flows down into the inlet chamber
through the slot in the floor of the baffle. The
slot distributes the flow evenly toward all the
pump inlets. The partition wall is high enough
to ensure that the flow does not surge over
it. Although the flow in the inlet chamber is
highly turbulent, various materials can collect
there. In such cases, side overflow weirs or
side gaps may be used to carry away debris
and thus prevent its accumulation. (The top
of the partition wall, or parts of it should be
below the highest start-level of any of the
pumps to allow transport of the floating
material into the pump chamber).

A2 If the piping system and the sump location do


not allow for a front entry inlet – a side entry
inlet with a baffle wall modified with ports can
be used. This configuration is referred to as
type A2. In this design, the baffle wall redirects
the incoming flow and distributes the flow
evenly toward the pumps through the ports.
At high inlet, it is recommended to have a
baffle on the inlet chamber floor. This baffle
breaks flow jets when the water level in the
station is low.

Equipping the sump with fillets, baffles, and/


or benching is often beneficial depending
on the number of pumps and their size.
Therefore, please consult with Xylem for an
optimum sump design.

6
Circular sump Double sump

Construction alternatives
Distributing the flow evenly to all pumps over the width of
the sump can present problems if the number of pumps
B2 is more than four. In such cases, a double sump may be
more suitable.

For deep sumps, using a circular outer structure


can be advantageous from a construction viewpoint.
Inside such a structure, individual pump sump modules
similar to those used for the compact sump can
be accommodated.

Please contact Xylem for advice of compact sump designs


with a central front low-level entry.

In type B2, with a straight baffle wall, the sewer is below


the normal water level in the sump, or an open channel
supplies the sump. In the absence of falling flow in the
entrance, no intense entrainment of air takes place.
Consequently, the inlet chamber can be greatly simplified
because its only task is to distribute the flow evenly to
the pumps. In dry pumps application, it is recommended
to have vertical baffles between suction pipes, to protect
mass rotation in the wet well.

Reverse oriented pumps Sometimes there is a need to locate the riser pipe in
the center of the stations or locate the outlet in another
direction where reversed pump orientation can be
a solution.

This picture shows an extract of a reverse orientation


wastewater pumping station design.

When operated in combination with recommended pump


control philosophies, optimal pumping conditions are
achieved while also providing sump floor cleaning for
transportation of solids.

7
Sump dimensions
The sizing diagram is valid for pumping stations up to of the departures does not lead to velocities significantly
four pumps, all of which may be duty pumps. Tolerances higher than those for the standard sump. Flow per pump
of ±10 % on the sump dimensions shown in the table refers to one pump duty point for maximum total flow (in a
below are acceptable provided that the combined effect common pressure pipe).

Pump sump dimensioning diagram


Flow rate per pump at single pump duty [gpm]

A
B
C
16,000 D
E
F

1,600
8 80

Dimension [in]

Please note that in this flow region is also sump design recommendations for the mid–range product line are applicable.

A1 Submerged A1 Dry

8
A2 Submerged A2 Dry

B2 Submerged B2 Dry

9
Required sump volume Sump design type A1, A2, B2
The required live volume of the sump, V, i.e. the volu­me These recommendations are valid for the Flygt pump
between the start level and the stop level of the pump, sump design for two, three, or four pumps, installed
depends upon such factors as the cycle time for the pump, either in a semi-permanent (P) or permanent wet well
T; the pump capacity, Q; and the rate of the inflow, q. (T). It is valid for all four positions of the pumps at all
For one pump and for variable inflow rate, the shortest combinations of pumps in duty, though exceptions in
cycle time occurs if q = Q/2 which gives the minimum the recommendations are made for the straight baffle
required volume of the sump: wall. It is assumed that at least one pump is assigned as
a standby pump, and only in extreme cases will all four
pumps run simultaneously.

The minimum cycle time, (Tminimum) is determined by When the location of the inlet pipe is unsymmetrical, at
the number of pump starts with regard to the mechan­ical low level, or the last part is less than five straight pipe
stress from the temperature rise in the motor. diameters, higher stop levels to suppress vortices should
T = 3600 / starts per hour be applied according to the recommendations for non-
optimal inflow (see graph: Low level front entry).

For a pumping station with identical pumps, the A1 High level central front entry
required volume is smallest if the pumps start in sequence L-shaped baffle
as the water level rises due to increasing inflow, and stop
in sequence as the water level drops due to decreasing
inflow. To minimize the required sump volume, the last
Submergence to pump inlet
10 One pump stop level
pump to start should be the last pump to stop, i.e.
1st pump stop out of 2 pumps running
cyclic alternation. 8
1st pump stop out of 3 pumps running
6
4
Minimum stop levels 2
The pumps can be stopped at the same water level, but
0
a time delay between the stops is important to avoid 0 10000 20000 30000 40000 Flow / pump
high immediate flow changes and pressure transients in
the discharge pipes. The following minimum stop level
recommendations prevent vortices and air pene­tration
through to the pump intakes. For a short period of time the
level could be less, e.g. during the sump cleaning cycle. Low level front entry
Off-set front entry
A1 L-shaped baffle

10 One pump stop level


Submergence to pump inlet

1st pump stop out of 2 pumps running


8
1st pump stop out of 3 pumps running

0
0 10000 20000 30000 40000Flow / pump

10
where:
A2 Side entry
NPSHav – Available suction pressure due to atmospheric
L-shaped baffle
pressure, temperature, water level in the sump, and inlet
10
losses.
NPSHreq – The pressure required to obtain a trouble-free
operation in terms of cavitation, the value is determined
Submergence to pump inlet

8
by the NPSH curve for the pump.
6 One pump stop level The available suction head has to be greater than the
1st pump stop out of 2 pumps running suction head required by the pump.
1st pump stop out of 3 pumps running
4 The available suction head in a wet-installed pump
application is:
2
NPSHav = Hatm + Hsump – Hev
0 0 10000 20000 30000 40000

Flow per pump gpm

B2 Side entry
Straight baffle wall
10

8
Submergence to pump inlet

4 For a dry installed application, the dynamic head


losses in the inlet pipe have to be taken into account.
2
Consequently the relation for the available suction
0 0 10000 20000 30000 40000
head becomes:
Flow per pump gpm
One pump stop level NPSHav = Hatm + Hsump – Hloss – Hev
1st pump stop out of 2 pumps running
1st pump stop out of 3 pumps running
Stop level pump 1 or pump 4

Note that NPSHreq has to be fulfilled


according to the paragraph below.

Net Positive Suction Head – NPSHav


where:
The positive head required on the suction side of the
Hatm – Atmospheric pressure
pump to secure safe operation in terms of cavitation is
determined by the NPSH (net positive suction head) curve. Hsump – Difference in level between centerline of the
The basic condition to be fulfilled in all applications where impeller and liquid surface in the sump
rotodynamic pumps are used is:
Hev – Evaporation pressure of the liquid
NPSHav > NPSHreq
Hloss – Dynamic head loss in inlet pipe system

11
Installation tips Dry installed submersible pumps

Suction pipe design


Submerged pumps The position of the suction pipe relative to the dry
installed pump follows the same hydraulic guidelines
The following are some general installation guidelines for as for a submerged pump. However, with dry installed
submersible pumps: pumps, additional consideration must be given to the
• The check valve should be located at least 8 meters (27 submergence of the inlet. This is because air can be
feet) above the pump discharge to avoid cavitation. drawn into the inlet pipe in a dry installed pump easier
than the suction of a wet installed pump since the volute
• A trough in the wetwell floor is recommended for
of a submerged pump acts as a vortex suppressor.
station cable runs (refer to electrical codes). This will
protect the cable make the station easier to maintain.
Accumulated air in the inlet pipe can impair pump
• The cable support bracket/strain relief sheathing should operation and can cause the system to become “air
be mounted for easy access, i.e. within reach under bound” – preventing pumping altogether.
the hatch.
• When a pipe or a hose is used to protect the cable, For flows over 500  l/s (8000 gpm), the inlet pipe should
it should not cover the cable all the way into the be equipped with an inlet bell to minimize losses and
control panel, as evaporating explosive gases from the disturbed flow into the pump.
wastewater entering the cabinet could be dangerous
inside the control panel (refer to local codes). To achieve a uniform flow to the inlet of the pump, the
• Wastewater gas can cause relay oxidation. It is therefore suction pipe design should fulfill the following:
beneficial to locate the control panel in a ventilated 1. Provide sufficient NPSHav
environment. 2. Minimize friction losses
• A stillwell located with its opening below the lowest 3. Minimize number of elbows
water level may be used to avoid any problems with
4. Eliminate vapor from suction pipe
floating debris interfering with the operation of level
regulators. 5. Ensure correct pipe alignment
• The pocket in the benching with the discharge 6. Provide automatic air venting downstream of the pump
connections can collect sediment. A steel plate or before the check valve
concrete infill benching covering the pocket may be
used to prevent sedimentation. Valve location at the suction pipe
To minimize the risk of cavitation, noise, and vibration, the
valve and the valve seat should be smooth to avoid flow
disturbance (gate valves are preferred), and if possible,
be located more than five pipe diameters away from the
pump.

Effects of elbows
Elbows in the piping generate dynamic losses and
swirling flow and should be avoided whenever possible.
To minimize the effects of
the elbows, the pre-swirl 90° 360° 180°
(which could increase
the power requirements
for the pump) should be
located in one plane – as
shown in the 360° and 270°
180° pipe configurations.

12
The inlet bellmouth Installation guidelines for the pump
To accelerate the flow smoothly into the inlet pipe and and its piping
reduce inlet losses, the inlet should be provided with
a bellmouth.
Avoiding vibration and noise
A rotary machine will always be a source of energy for
acoustic/vibrational disturbance. The pump and/or motor
unit can propagate disturbances to the environment that
may excite vibration and cause noise in other parts of
the system, pipes, etc. With wet-well installed pumps, the
medium helps reduce vibration and noise. The design for
dry installed pumps must be more carefully analyzed in
order to reduce these types of problems.

The first rule to follow is that the pump is best operated


in the duty area it is designed for – normally between
50 % and 125 % of best efficiency point (BEP). In this area,
disturbances such as impeller and volute forces, cavitation,
etc., are kept to a minimum.

The standard pump accessories are designed for use


with a fixed, stiff installation where the main disturbance
frequency will be below the lowest natural frequency and
result in low vibration levels.

The optimal velocity at the entrance of the bellmouth is In some cases, a totally fixed design is not enough, and
1.7 m/s, (5.6 ft/s) and should be within the following limits. the system or parts of it have to be isolated with rubber
machine feet, a rubber carpet, flexible pipe joints, etc.

When evaluating the system, an analysis of the source of


Flow Velocity
any disturbance can include:
< 1200 l/s, 0.9–2.4 m/s,
<19,000 gpm • Imbalance in the rotating parts. These have a
3–8 ft/s
dominating magnitude at the rotation frequency of the
> 1200 l/s, 1.2–2.1 m/s, pump.
>19,000 gpm
4–7 ft/s
• Hydraulic forces that are caused by the pressure
differences in the volute
• The passage of the impeller blade past the volute cut
water which creates both forces on the impeller and
pressure pulses in the pipe system at a frequency that is
the product of the rotating impeller frequency and the
blade number.

With this information, it is possible to analyze the


system in order to minimize the risk for vibration, i.e. the
critical pipe length and the minimum distance for the pipe
support to prevent harmonics.

Other factors that might create noise are the electric


motor, the internal flow (turbulence and swirl can cause
pipes and valves to radiate noise), and cavitation within
the pump or in the pipes/valves.

13
For more information regarding vibration and noise
prevention for dry installed pumps, please see Xylem’s
Importance of
engineering paper “Noise and vibrations from pumping
installations”.
duty point
In order to achieve the best possible pump operation
Pump anchoring and piping support and maximize equipment life, it is very important to
guidelines select the correct pump for the duty point in question.
The following guidelines can prevent unwanted vibration: The preferred operating region (POR) for most large
centrifugal pumps is between 70 % and 120 % of the Best
1) All parts of the system should be anchored so the Efficiency Point (BEP), as outlined in the Hydraulic Institute
primary disturbances have frequencies below the Standards. The Allowable Operating Region (AOR)
lowest natural frequency of the system, including pump, from BEP for optimal operation of centrifugal pumps in
valves, supports, and pipes. wastewater applications is between 50 % and 125 % of
BEP (unless the curve does not have an operational limit
2) If the pump and foundation are to be insulated from
and sufficient NPSH is available). By running the pump
the pumping station, the following procedure is
outside the AOR the following problems can occur:
recommended:
• Unstable operation.
a) The weight of the foundations should be at least two • Incipient cavitation resulting in impeller erosion, noise
times the weight of the rotating parts. or vibration.
b) Use flexible supports, e.g. machine feet or a rubber
carpet, between the base and the floor or ground. High radial and axial forces
50% – 125% of Qopt
c) Use flexible joints for the pipes.

d) Anchor the pipes to the floor or to another solid


structure. BEP

3) Horizontal and vertical supports should be provided,


with extra supports at heavy components such as valves. NPSHr

4) For pipe systems with bellows to minimize vibration,


the pipe should be supported at the bellows to avoid High radial forces
transference of pressure fluctuations.

5) Vertical pipe velocities must be kept at a level that Consult Xylem Engineering if operation outside of the
prevents the settling of solids. The recommended range AOR is required.
is 1.5–2.5 m/sec.

14
Systems Engineering
Xylem offers in-depth expertise in the design and Additional services:
execution of comprehensive solutions for water and • Optimization of pump sump design for our
wastewater transport and treatment. products and specific sites
• Assistance with mixing and aeration specifications and
Our know-how and experience are combined with
design of appropriate systems
a broad range of suitable products for delivering
customized solutions that ensure trouble-free operations • System simulation utilizing computational fluid dynamics
for customers. To do this our engineers utilize our (CFD)
own specially developed computer programs, as well • Guidance for model testing
as commercially available programs, for design and • Guidance for achieving the lowest costs in
development projects. operations, service, and installation
• Specially developed engineering software for system
Scope of assistance includes a thorough
design
analysis of the situation and proposed solutions,
together with selection of products and accessories.
The range of services is comprehensive, but our
philosophy is very simple: There is no substitute for
We also provide hydraulic guidance and assistance
excellence.
for flow-related or rheological issues. Customers turn to
us, as well, for analysis of complex systems for network
pumping, including calculations for hydraulic transients,
pump starts, and flow variations.

15
Xylem |'zīl m| e
1) The tissue in plants that brings water upward from the roots;
2) a leading global water technology company.

FB157-665 • Flygt Design Recommendations For Pump Stations with Large Centrifugal Flygt Wastewater Pumps Brochure • 4/2015 • NACT
We’re 12,000 people unified in a common purpose: creating innovative solutions to
meet our world’s water needs. Developing new technologies that will improve the way
water is used, conserved, and re-used in the future is central to our work. We move, treat,
analyze, and return water to the environment, and we help people use water efficiently, in
their homes, buildings, factories and farms. In more than 150 countries, we have strong,
long-standing relationships with customers who know us for our powerful combination
of leading product brands and applications expertise, backed by a legacy of innovation.

For more information on how Xylem can help you, go to www.xyleminc.com

Xylem, Inc.
14125 South Bridge Circle
Charlotte, NC 28273
Tel 704.409.9700
Fax 704.295.9080
855-XYL-H2O1 (855-995-4261)
www.xyleminc.com
Flygt is a trademark of Xylem Inc. or one of its subsidiaries.
© 2015 Xylem, Inc. APR 2015

You might also like