The Battery 6612 is a lithium battery module built To secure safe operation are all Ericsson Lithium
on high quality NMC cells. batteries integrated with the enclosure controller
system. Battery status is continuously monitored
Battery 6612 is designed to fit into 19” equipment and power system parameters for correct battery
space. operation is set automatically.
ELECTRICAL
Nominal voltage: -48 VDC
Capacity: 100 Ah
Energy: 4800 Wh
Recommended max discharge current 95 A
Discharge current cutoff 100 A
Recharge current limitation 50 A (If charge current is higher than 50 A will the current automatically be reduced to 6-
12 A until 100% SOC
Recommended max recharge current 45 A
Charge voltage to 100% SOC 54.6 V
Charge voltage to 80% SOC 52.0 V
End of Discharge Voltage 39.0 V
DESIGN LIFE
Calendar Life >15 Years
Cycle life @ 80% DOD >6000 cycles
ENVIRONMENTAL
Normal Operating Temp. Range +5 to +50 °C
Extended Operating Temp. Range -20 to +70 °C
Storage Temperature -20 to +50 °C
Humidity 5 – 95%