71u63-Eq63p533b 01

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

GENERAL INFORMATION ANCHOR BOLT'S SET (dimensions shown are in mm)

Missing skid (Y/N) Any obstacle Missing equipment (Y/N) Anchor bolts' status
Bolts position from WP Bolts dimension Missing bolts Missing nuts Corroded bolts
(CLV1, CVL2 or CLV3)
N (ref. mark up on plan view) N
Projection Before equip. After equip. Before equip. After equip. Before equip. After equip. Before equip. After equip.
# Xb Yb Dia. (See Note 1)
dismantling dismantling (*) dismantling dismantling (*) dismantling dismantling (*) dismantling dismantling (*)
FUNDATION GEOMETRY (dimensions shown are in mm) 1 805 610 17 40 - N/A - N/A x N/A CLV2 N/A
L found W found H found L grout W grout t grout L1 L2 W1 W2 SIDE
(see note 2) ORIENTATION 2 1620 610 17 40 - N/A - N/A x N/A CLV2 N/A

3375 1220 300 1160 3295 40 420 455 230 130 N N 3 805 1660 17 40 - N/A - N/A x N/A CLV2 N/A

4 1620 1660 17 40 - N/A - N/A x N/A CLV2 N/A


Lfound
5 805 2710 17 40 - N/A - N/A x N/A CLV2 N/A
L1 SIDE L2 6 1620 2710 17 40 - N/A - N/A x N/A CLV2 N/A
"S4" A
W2

SIDE ORIENTATION

Hfound

tgrout
Wfound

Wgrout
SIDE SIDE
Pump skid (*) Mark N/A if equipment not dismantled
"S3" "S1"
Anchor bolts' status:
CLV1: reduction of a.bolt original diameter less than 2.00mm, no damage of anchor bolts and nuts' thread
W1

CLV2: reduction of a.bolt original diameter more than 2.00mm, no damage of anchor bolts and nuts' thread
SECTION "A-A" CLV3: damage of anchor bolts and nuts' thread or bending of existing anchor bolt
SIDE A (Pump skid omitted for clarity)
"S2" Yb
Lgrout WP (#1,2,3,4,5,6,7,8,9,10)

Projection
A
ANCHOR
PUMP BOLTS

SIDE ORIENTATION
PLAN VIEW #1 #3 #5 #7 #9

(#1,2,3,4,5,6,7,8,9,10)
Remarks before dismantling:
1. SURFACE DETERIORATION AND DISCOLORATION OF CONCRETE SURFACE DUE TO EXPOSURE TO ENVIRONMENTAL FACTORS AND OIL SPILLS OBSERVED.

Xb
2. SLIGHT DAMAGE ON THE CONCRETE FOUNDATION OBSERVED.
3. ANCHOR BOLTS APPEAR CORRODED. HOWEVER, AFTER PROPER CLEANING AND WIRE BRUSHING TO ASCERTAIN BOLT CONDITION IN THE FUTURE.
THIS DOCUMENT IS TECNIMONT'S PROPERTY AND CANNOT BE USED BY OTHERS FOR ANY PURPOSE, WITHOUT PRIOR WRITTEN CONSENT

4. EXISTING FOUNDATION CAN BE RETAINED AND REFURBISHED OF DAMAGED CONCRETE FOUNDATION AND WITH RESTORATION OF CONCRETE SURFACE
APPEARANCE.
#2 #4 #6 #8 #10

Remarks after dismantling:


A
ANCHOR BOLTS
PLAN VIEW
SECTION "A-A"
(Pump skid omitted for clarity)

SIDE
"S4"

SIDE SIDE
Pump skid
"S3" "S1"

SIDE "S1" SIDE "S2" SIDE "S3" SIDE "S4"


SIDE (Pump skid omitted for clarity) (Pump skid omitted for clarity) (Pump skid omitted for clarity) (Pump skid omitted for clarity)
"S2"
PLAN VIEW

TEMPLATE STANDARD UPDATED VERSION 26/11/2021

FOUNDATION'S CRACKS (SEE NOTES BELOW) GROUT'S CRACKS (SEE NOTES BELOW)
01 28.JAN.2022 IFC - ISSUE FOR CONSTRUCTION E. Chima O. Rodoye C. Waccher
Sequential no. Width (mm) Length (mm) Depth (mm) Position Sequential no. Width (mm) Length (mm) Depth (mm) Position
00 24.JAN.2022 IFC - ISSUE FOR CONSTRUCTION E. Chima O. Rodoye C. Waccher
Issue Date Reason for Issue - Revision Description Prepared Checked Approved

Digital signature

TECNIMONT IDENTIFICATION CODE


REHABILITATION OF Job-EC-Type-N°

CRACKS:-
PORT HARCOURT
REFINERY PROJECT DOC. CLASS. ISSUE
1.
2.
3 NOS. 1.0 mm CRACK WIDTH ON GROUT AND FUNDATION SIDE "S3" OBSERVED.
2 NOS. 2.0 mm CRACK WIDTH ON GROUT AND FOUNDATION SIDE "S1" OBSERVED.
(Port Harcourt - Nigeria) 3 01
3. 4 NOS. 1.3 mm CRACK WIDTH ON GROUT AND FUNDATION SIDE "S2" OBSERVED. CLIENT IDENTIFICATION CODE
4. 4 NOS. 1.3 mm CRACK WIDTH ON GROUT AND FUNDATION SIDE "S4" OBSERVED
PORT HARCOURT
REFINING COMPANY
LIMITED (PHRC)
NOTES:- TITLE
FOUNDATION REFURBISHMENT SCHEDULE - PUMPS
MOD-CADA2 E rev.1

1. BOLT PROJECTION WITH RESPECT TO TOP OF GROUT.


2. H FOUNDATION WITH RESPECT TO HPP VARIES.
OFFSITE
71U63-EQ63P533B SCALE
N.T.S.
ORIG. SIZE
A1
REMARKS & NOTES:-
1. ALL DIMENSIONS AND ELEVATIONS ARE IN MILLIMETERS UNLESS NOTED OTHERWISE.
2. ALL COORDINATES ARE IN METERS UNLESS NOTED OTHERWISE.
3. TOP OF PAVING SHALL BE TAKEN AS EL. +0.000 CORRESPONDS TO HIGHEST POINT OF PAVING.
4. ALL FOUNDATION ELEVATIONS ARE REFERENCED TO THE HPP VARIES.
5. ONLY ANCHOR BOLTS VISIBLE HAVE BEEN INDICATED.

4 NOS. 18 mm Ø 2560 4 NOS. 18 mm Ø


ANCHOR BOLTS ANCHOR BOLTS
01 01 01
40 40 ABBREVIATIONS:-
585 1220 675
(STUB WIDTH) (PUMP FDN. WIDTH) (STUB WIDTH)
T.O.C. TOP OF CONCRETE
T.O.P TOP OF PAVING
T.O.G. TOP OF GROUT
EL. ELEVATION
TYP. TYPICAL
H.P.P. HIGHEST POINT OF PAVING (VARIES)

280
350

255

825
860

EL +375.000 T.O.C.
255

EL +350.000 T.O.C.
THIS DOCUMENT IS TECNIMONT'S PROPERTY AND CANNOT BE USED BY OTHERS FOR ANY PURPOSE, WITHOUT PRIOR WRITTEN CONSENT

625

2105
1280

3435
EL +300.000 T.O.C.
1050

1090

EL +420.000 T.O.G.
TEMPLATE STANDARD UPDATED VERSION 26/11/2021

1330
01 28.JAN.2022 IFC - ISSUE FOR CONSTRUCTION E. Chima O. Rodoye C. Waccher

1315 00 24.JAN.2022 IFC - ISSUE FOR CONSTRUCTION E. Chima O. Rodoye C. Waccher

Issue Date Reason for Issue - Revision Description Prepared Checked Approved

Digital signature
610

TECNIMONT IDENTIFICATION CODE


REHABILITATION OF Job-EC-Type-N°

180 765 275 1040 PORT HARCOURT 4239-AA-DA-2100A001


REFINERY PROJECT DOC. CLASS. ISSUE
2260 (Port Harcourt - Nigeria) 3 01
CLIENT IDENTIFICATION CODE

PORT HARCOURT
REFINING COMPANY
LIMITED (PHRC)
TITLE
OFFSITE
MOD-CADA2 E rev.1

71U63-EQ63P533B
SCALE ORIG. SIZE
1:10 A1
21U63-EQ63P533B

You might also like