Professional Documents
Culture Documents
71u63-Eq63p533b 01
71u63-Eq63p533b 01
71u63-Eq63p533b 01
Missing skid (Y/N) Any obstacle Missing equipment (Y/N) Anchor bolts' status
Bolts position from WP Bolts dimension Missing bolts Missing nuts Corroded bolts
(CLV1, CVL2 or CLV3)
N (ref. mark up on plan view) N
Projection Before equip. After equip. Before equip. After equip. Before equip. After equip. Before equip. After equip.
# Xb Yb Dia. (See Note 1)
dismantling dismantling (*) dismantling dismantling (*) dismantling dismantling (*) dismantling dismantling (*)
FUNDATION GEOMETRY (dimensions shown are in mm) 1 805 610 17 40 - N/A - N/A x N/A CLV2 N/A
L found W found H found L grout W grout t grout L1 L2 W1 W2 SIDE
(see note 2) ORIENTATION 2 1620 610 17 40 - N/A - N/A x N/A CLV2 N/A
3375 1220 300 1160 3295 40 420 455 230 130 N N 3 805 1660 17 40 - N/A - N/A x N/A CLV2 N/A
SIDE ORIENTATION
Hfound
tgrout
Wfound
Wgrout
SIDE SIDE
Pump skid (*) Mark N/A if equipment not dismantled
"S3" "S1"
Anchor bolts' status:
CLV1: reduction of a.bolt original diameter less than 2.00mm, no damage of anchor bolts and nuts' thread
W1
CLV2: reduction of a.bolt original diameter more than 2.00mm, no damage of anchor bolts and nuts' thread
SECTION "A-A" CLV3: damage of anchor bolts and nuts' thread or bending of existing anchor bolt
SIDE A (Pump skid omitted for clarity)
"S2" Yb
Lgrout WP (#1,2,3,4,5,6,7,8,9,10)
Projection
A
ANCHOR
PUMP BOLTS
SIDE ORIENTATION
PLAN VIEW #1 #3 #5 #7 #9
(#1,2,3,4,5,6,7,8,9,10)
Remarks before dismantling:
1. SURFACE DETERIORATION AND DISCOLORATION OF CONCRETE SURFACE DUE TO EXPOSURE TO ENVIRONMENTAL FACTORS AND OIL SPILLS OBSERVED.
Xb
2. SLIGHT DAMAGE ON THE CONCRETE FOUNDATION OBSERVED.
3. ANCHOR BOLTS APPEAR CORRODED. HOWEVER, AFTER PROPER CLEANING AND WIRE BRUSHING TO ASCERTAIN BOLT CONDITION IN THE FUTURE.
THIS DOCUMENT IS TECNIMONT'S PROPERTY AND CANNOT BE USED BY OTHERS FOR ANY PURPOSE, WITHOUT PRIOR WRITTEN CONSENT
4. EXISTING FOUNDATION CAN BE RETAINED AND REFURBISHED OF DAMAGED CONCRETE FOUNDATION AND WITH RESTORATION OF CONCRETE SURFACE
APPEARANCE.
#2 #4 #6 #8 #10
SIDE
"S4"
SIDE SIDE
Pump skid
"S3" "S1"
FOUNDATION'S CRACKS (SEE NOTES BELOW) GROUT'S CRACKS (SEE NOTES BELOW)
01 28.JAN.2022 IFC - ISSUE FOR CONSTRUCTION E. Chima O. Rodoye C. Waccher
Sequential no. Width (mm) Length (mm) Depth (mm) Position Sequential no. Width (mm) Length (mm) Depth (mm) Position
00 24.JAN.2022 IFC - ISSUE FOR CONSTRUCTION E. Chima O. Rodoye C. Waccher
Issue Date Reason for Issue - Revision Description Prepared Checked Approved
Digital signature
CRACKS:-
PORT HARCOURT
REFINERY PROJECT DOC. CLASS. ISSUE
1.
2.
3 NOS. 1.0 mm CRACK WIDTH ON GROUT AND FUNDATION SIDE "S3" OBSERVED.
2 NOS. 2.0 mm CRACK WIDTH ON GROUT AND FOUNDATION SIDE "S1" OBSERVED.
(Port Harcourt - Nigeria) 3 01
3. 4 NOS. 1.3 mm CRACK WIDTH ON GROUT AND FUNDATION SIDE "S2" OBSERVED. CLIENT IDENTIFICATION CODE
4. 4 NOS. 1.3 mm CRACK WIDTH ON GROUT AND FUNDATION SIDE "S4" OBSERVED
PORT HARCOURT
REFINING COMPANY
LIMITED (PHRC)
NOTES:- TITLE
FOUNDATION REFURBISHMENT SCHEDULE - PUMPS
MOD-CADA2 E rev.1
280
350
255
825
860
EL +375.000 T.O.C.
255
EL +350.000 T.O.C.
THIS DOCUMENT IS TECNIMONT'S PROPERTY AND CANNOT BE USED BY OTHERS FOR ANY PURPOSE, WITHOUT PRIOR WRITTEN CONSENT
625
2105
1280
3435
EL +300.000 T.O.C.
1050
1090
EL +420.000 T.O.G.
TEMPLATE STANDARD UPDATED VERSION 26/11/2021
1330
01 28.JAN.2022 IFC - ISSUE FOR CONSTRUCTION E. Chima O. Rodoye C. Waccher
Issue Date Reason for Issue - Revision Description Prepared Checked Approved
Digital signature
610
PORT HARCOURT
REFINING COMPANY
LIMITED (PHRC)
TITLE
OFFSITE
MOD-CADA2 E rev.1
71U63-EQ63P533B
SCALE ORIG. SIZE
1:10 A1
21U63-EQ63P533B