Cal Cert No: MMA/21-22/12492 Cal Date: 07.01.2022


CALIBRATION CERTIFICATE
Customer Name& Address: M/s.Sachu Technologies
15-29-887Ic2,Road No2 ,KPHB Colony
Medchal Malkajgiri,Telangana,500072
W.O/ Receipt Form No:- MMA12492 Date of Receipt -07.01.2021

Details of Device Under Calibration


DUC: Power Analyzer Make:-Krykard Model:ALM33 Serial. No:00002073

Condition of item on Receipt- Satisfactory Calibrated at In-house/Onsite


Dateof Calibration -07.01.2022 Recommended Calibration Due:-06.01.2023

Cert No:MMA/21 -22/12492 Issue Date:10.01.2022

Applicable Spec:StandardAManufacturelUser Calibration Procedures followed-As perCP2,CP4,CP


Environmental Conditions: Temp:-25 +2.5°C Relative Humidity:- 35-65%
Details of Standards used
SIL.No Name of the Standard Make/Model/Serial No
Equipment Traceability Cal Date
1 Multi-Function Calibrator Fluke/5080A/4367102 Tektronix(BNG) 13.10.21

2 Current Coil (50 Turns) Fluke/5500A/20080770D Godrej& Boyce 28.06.21


(Chennai)
The Standards used are traceable to National Standards/S.I Units
Results Reported are valid at the Time of &Underthestated conditions of Measurements.
This certificate refers only to the item(s) calibrated.

Any error in the certificate should be brought to our knowledge within 45 days from the date of this certificate
Certificate shall not be reproduced (except in full) without written approval from MMACALABS TECH LTD,
Hyderabad.
ULR No: Cc251522000000024F

Calab
M.Maommh
Calibrated by: Tech Approved & Issued by:

E(MIMA Pavan kumar


(Technical Manager)
under

Rev. 4Dt: 01.07.2019 Page 1 of 3


MMA CALABS: Cert: 01,

328, Chandralok Complex, Near Paradise Circle, 111, S. D.Road,Secunderabad, Telangana, India 500 003.
Tel:+91 40 27846863, Fax: +91 40 27814172, Mob: +91 9346004047
Email: sales@mmacalabs.com Website: www.mmacalabs.com
MMA CALABS TECH LTD
IsO 9001:2015 Certified Company
CC-2515

Cal Cert No: MMA21-22/12492 Cal Date:07.01.2022

Electrotechnical Calibration
CALIBRATION RESULTS

DUC Standard Measured Accuracy Deviation Measurement


parameter Value Readings () () Uncertainty
DUC
and range
AC Voltage @50Hz
R-Phase V 0.6 V -0.1 0.0642 V
1000 100 V 99.9
500 V 499.8 V 2.6 V 02 v 0.3343 V
900 V 899.7 V 4.6 V -0.3 0.4541

Y-Phase 0.0818
1000 100 V 99.9 0.6 V -0.1 V
500 VV 499.7 2.6 V -0.3 v 0.3201 V
900 899.4 4.6 V -0.6 V 0.5245 V

B-Phase 0.6 V 0.0 V 0.0642


1000 V 100 V 100.0 V
500 V 499.9 V 2.6 -0.1 V 0.3245
900 V 899.7 V 4.6 V -0.3 V 0.5124

PowerP.F=1
1 1.2 k W 1.2 k W 1.208 kW 0.028 k W 0.008 kW 0.0079 k W

4.8 kW 4.8 k W 4.817 k W 0.082 k W 0.017 kW 0.1245 k W

L2 1.197 k W 0.028 k W -0.003 kW 0.0081 k W


1.2 k W 1.2 k W
4.8 k W 4.781 k W 0.082 k W -0.019 kW 0.1245 k W
4.8 k WN

L3 1.211 k W 0.028 k W 0.011 kW 0.0086 k W


1.2 k W 1.2 k W
4.8 k W 4.8 k W 4.817 k W 0.082 k W 0.017 kW 0.1245 k W

Note: Overall uncertainty is calculated at 95.45% confidence level at k=2


MMA CALABS: Res.01 Rev.04 Dt: 01.07.2019

Page 2 of 3

A
328, Chandralok Complex, Near Paradise Circle, 11, S. D. Road. Secunderabad, Telangana, India 500 003.
Tel: +91 40 27846863, Fax: +91 40 27814172, Mob: +91 9346004047
Email: sales@mmacalabs.com Website: www.mmacalabs.com
MMA CALABS TECH LTD
ISO 9001:2015 Certified Company

CC-2515

Cal Cert No: MMA/21-22/12492 Cal Date:07.01.2022

CALIBRATION RESULTS
DUC Standard Measured Accuracy Deviation Measurement
parameter Value Readings () (t) Uncertainty
andrange DUC

AC Current@50Hz
R-Phase
With MN93 Clamp
100 A 10 10.09 A 0.15 0.09 A 0.0776 A

50 50.35 A 0.35 A 0.35 A 0.3421 A


90 A 90.55 A 0.55 0.55 A 0.8109 A

With Ampflex Clamp


1000 A 100 A 99.2 A 0.8 A -0.8 A 0.9027 A
500 A 498.6 A 2.8 A -1.4 A 3.3158 A
900 A 898.2 A 4.8 A -1.8 A 5.8645 A

Y-Phase
With MN93 Clamp
100 A 10 A 9.85 A 0.15 A -0.15 A 0.0876 A
50 A 49.65 A 0.35 A -0.35 A 0.4508 A
90 89.45 A 0.55 A -0.55 A 0.8105 A

With Ampflex Clamp


1000 A 100 A 99.3 AA 0.8 A -0.7 A 0.9028 A
500 A 498.3 A 2.8 A -1.7 A .3250 A
900 A 898.1 A 4.8 A -1.9 A 5.9158 A

B-Phase
With MN93 Clamp
100 A 10 A 9.87 A 0.15 A -0.13 A 0.0876 A
50
90
A
A
49.66
89.4
A
A
0.35
0.55
A -0.34
-0.55
A
A
0.4528
0.8148
A
A

With Ampflex Clamp


1000 A 100 A 99.8 A 0.8 A -0.2 A 0.9028 A
500 A 500.1 A 2.8 A 0.1 A 3457 A
900 A 901.1 A 4.8 A 1.1 A 5 9845 A

END OF CERTIFICATE

Calibrated by: Approved &lssued by:

Tech
C a l a b s

Note: Overall uncertainty is calculated at 95.45MMA t k=2


Pavan Kumar
(Technical Manager)

MMA CALABS: Res.01 Rev.04 Dt: 01.07.2019 rabad