PoolPak Natatorium Design Guide
PoolPak Natatorium Design Guide
Introduction................................................................................................................................ 4
Condensation Control............................................................................................................... 16
Energy Considerations.............................................................................................................. 20
Replacement Systems.............................................................................................................. 35
“
Maintenance
A first-class indoor pool experience should The building itself also needs to be designed
be everyone’s expectation. Fortunately, it is suitable for a higher temperature and dew point
absolutely possible to provide a safe, healthy, application. An indoor pool environment is
comfortable indoor pool environment, all different from traditional conditioned spaces and
while keeping operating costs at a minimum. needs to be designed appropriately. The building,
HVAC system, and all equipment must perform
There is no “one thing” that will ensure reliably, day in and day out, ideally with minimum
a successful pool. Many things need to energy consumption, no matter the ambient
come together during the design and then temperatures or level of pool activity.
during operations.
“
many critical considerations that, if overlooked,
can develop into serious problems affecting
A natatorium is one of the building structure or result in an unpleasant
experience or ill-health effects for the occupants.
the most notoriously There are vital design aspects that must be
difficult facilities to considered in order to deliver a successful
facility. These include relative humidity levels,
design because there condensation, air temperature, pool water
are so many critical temperature, pool activity levels, air distribution,
outdoor air, exhaust air, pool water treatment, and
considerations. chloramine control.
Bacteria
Viruses
Fungi
Mites
Respiratory Infections1
Chemical Interaction
Ozone Production
20 40 60 80
1
Insufficient data above 50% R.H.
% Relative Humidity
Study by Theodore Sterling Ltd., A. Arundel Research Associates and Simon Fraser University.
P o o l P a k N a t a t o r i u m D e s i g n G u i d e / H e a l t h , S a f e t y, a n d C o m f o r t 6
The type of facility being designed will typically dictate the space temperature. Table 1 helps target
some typical conditions. It is critical to understand who will be using the facility in order to deliver the
conditions most likely to satisfy them.
Diving 80 to 85 84 to 88
Elderly Swimmers 84 to 85 85 to 90
Hotel 82 to 85 82 to 86
Physical Therapy 80 to 85 90 to 95
Recreational 82 to 85 80 to 84
GENERAL NOTES
• Discuss the planned operation of the facility • Elderly swimmers and kids swim schools
with the operator to establish operating tend to prefer much warmer air and water
temperatures and general expectations. temperatures.
• Facilities with warmer water temperatures tend • Maintain relative humidity between 50% and
to have warmer space temperatures. Warmer 60% RH. Allowing the RH to go to 60% in
spaces have higher dew points summer will help reduce operating costs and
and will have condensation issues equipment size while eliminating condensation
unless the building is designed suitable concerns (condensation occurs only in cool/
for this application. cold weather).
• Physical therapy facilities will often cater to the
comfort of the therapist rather than the patient.
The patient is generally not in the space for
more than an hour, whereas the therapist is
there all day. The designer should consult local
codes. Some states require a full purge of the
clinic room air with 100% outdoor air for every
hour of occupancy.
P o o l P a k N a t a t o r i u m D e s i g n G u i d e / H e a l t h , S a f e t y, a n d C o m f o r t 7
HUMIDITY CONTROL
CALCULATIONS
While warm space temperatures and 50-60% In the summer, the outdoor air tends to be a load,
relative humidity levels are ideal for patron but since it is warm outside, condensation is not
comfort, they also translate to high dew point a concern, so it is recommended to model the
conditions which can lead to condensation space at 60% RH.
problems and serious damage to the building
In the winter, there is significant risk of
structure (in cool/cold weather). If the building
condensation, so it is recommended to model at
structure itself has not been properly designed
50% RH. The outdoor air in winter almost always
for this higher indoor dew point application,
is a dehumidification credit, making this easily
catastrophic results may occur. The architect
achievable.
should design and protect the building envelope
based on an indoor dew point design condition.
POOL EVAPORATION
Controlling humidity to provide this stable dew The internal load in a natatorium is the
point condition year round requires that a total evaporation from the pool water and continuously
moisture load be accurately calculated. This wet surfaces. In a natatorium, this represents
moisture load must be removed from the space the majority of the total dehumidification load.
at the same rate it is generated in order to Consequently, it is essential to accurately predict
maintain stable space conditions. the pool evaporation.
It is imperative that the designer know what There are five variables used to calculate the
the operating temperatures will be in order to evaporation rate:
properly establish loads.
• Pool water surface area
SEASONAL LOAD CALCULATION • Pool water temperature
Every building’s moisture (latent) load is calculated • Room air temperature
the same way. There are generally three sources
• Room air relative humidity
of moisture that are considered:
• Pool water agitation and activity factor
• Internal load (pool evaporation)
The first four variables are straightforward and
• Occupants
should be dictated by the owner. They are
• Outdoor air load used to calculate the baseline (unoccupied)
evaporation rate in the natatorium.
Wave Pool 1.5 – 2.0 Once equipment has been selected and installed,
any change of the variables that increases the
Whirlpool 1.0
evaporation rate can result in equipment no longer
being suitable for the new larger load.
Manufacturers of water features and toys do not publish the evaporation loads from their products,
forcing engineers to estimate. As a result, any indoor space heavily laden with water toys will make it
difficult to accurately model dehumidification loads, so it is important for designers to set expectations
with the owner. For example, there should not be an expectation that exact relative humidity levels will
be maintained.
A properly designed facility will adequately control Facilities that introduce outdoor air per ASHRAE
and remove chloramines while providing the Standard 62 and have proper/effective air
treated and conditioned air to where it is most distribution will have outstanding IAQ.
needed – into the breathing zone and deck area. • More outdoor air than required by ASHRAE
Standard 62 is not required for good IAQ if the
AIR CHANGE RATE air distribution is done well (except for indoor
ASHRAE recommendations for proper volumetric water and splash parks).
supply air changes per hour are important
• Outdoor air requires a significant amount of
to ensuring that the entire room will see air
heating energy in the winter and must be
movement. Stagnant areas must be avoided, as
included in heat load calculations.
they will be prone to condensation and air quality
problems. • Heat recovery should be considered between
the exhaust air and outdoor air streams.
Short circuiting between supply and return air
• Introduce the outdoor air at the factory-
must also be avoided as it significantly reduces
provided intakes on the air handlers.
the actual air changes within the space and the
overall effectiveness of the HVAC system. • Locate outdoor air intakes away from sources
of airborne contamination, such as exhaust
ASHRAE recommends: fans or plumbing vents.
• 4-6 volumetric air changes per hour in a • The outdoor air may need to be preheated to
regular natatorium 65°F if more than 35% of the total airflow is
outdoor air or if the winter design temperature
• 6-8 volumetric air changes per hour in
is below 10°F.
spectator areas
• A certified air-balancing contractor must
A quick calculation will determine the supply air
balance the system airflow.
requirement:
All air handlers for indoor pools must be equipped
• Supply air required (CFM) = room volume (ft3) x
with an outdoor air connection, filter, two-position
desired air changes / 60
motorized damper, and balancing damper.
“
Chemical
Laden Air
CHLORINE SMELL
VAPOR RETARDER
A vapor retarder is a material that restricts the FIGURE 6: POOLS ARE DIFFERENT –
rate of water vapor diffusion through the ceilings INSTALL THE VAPOR RETARDER ON THE
and walls of a building when below dew point WARM SIDE OF THE DEW POINT
temperature occurs. Figure 5 illustrates how
Temperature Gradient
failure to install the vapor retarder in the proper Through Wall
lead to structural failure. A vapor retarder should 64.5°F Dew Point Location
4°F
be sealed at all seams. 0°F
Inside Outside
Dry Insulation
Vapor Retarder
Skylight
Linear Diffuser
Linear Diffuser
Duct
Main Supply
Duct
Return
Air Grill
Dehumidifier
Air Movement
at Deck Level
GENERAL RECOMMENDATIONS:
• Galvanized sheet metal ducts are acceptable in most installations.
• A below-grade duct system should use PVC or plastic-coated galvanized spiral pipe to avoid
deterioration.
• Stainless steel duct and hardware should be avoided as they are readily attacked by chlorine.
• Fabric duct is an excellent choice of duct material for a natatorium.
• The duct material should not allow air to leak.
• The location of supply grilles and overall duct layout should be exactly the same as with a
metal duct.
• Ductwork that passes through an unconditioned area should be insulated on the exterior.
• When applicable, locate exhaust fan air intakes as close to the whirlpool as possible.
• To prevent excessive vibration noise, install neoprene flex connectors when attaching ductwork to the
dehumidifier. Acoustic insulation on the duct close to the unit may also be a consideration.
• Skylights require significant airflow to avoid condensation on their surfaces.
In winter, there is significant risk of condensation, The use of the pool water heating option satisfies
so it is recommended to model the space at ASHRAE Energy Standard 90.1; otherwise, a pool
50% RH. The outdoor air in winter almost always cover is required to meet the standard.
is a dehumidification credit, making this easily
A refrigeration-based dehumidifier can use up
achievable.
to 100% of the compressor hot gas waste heat
POOL WATER HEATING ENERGY RECOVERY to heat the pool water and/or reheat the air.
Returning this free energy back to the pool
When using a refrigeration-based approach to water or room air greatly reduces the annual
control humidity, the dehumidification process heating costs. During winter, the dehumidifier is
captures energy in the refrigerant at the evaporator capable of providing 100% of the pool’s water-
coil. The latent heat component is essentially heating requirement.
the pool’s evaporation. Evaporation represents
a significant portion of the pool’s annual water The mechanical refrigeration system approach
heating requirements. This captured energy can be to controlling the environment in a pool is a unique
returned to the pool water to provide free heating use of the refrigeration system. The evaporator
(Figure 9). controls the humidity, while the compressor
hot gas can be used to heat the pool water
and/or room air simultaneously. Traditional air
FIGURE 9: THE ENERGY CYCLE conditioning systems merely send the compressor
The Energy Cycle Dry Air
hot gas outdoors to a condenser or cooling tower
and do not tap into this heat source.
“
Humid Air
Recycled
4000 Gas $640 $960 $1280 $1600 $3200 $4800 $6400 $9600
hours
Electricity $1880 $2820 $3760 $4700 $9400 $14100 $18800 $28200
2000 Gas $320 $480 $640 $800 $1600 $2400 $3200 $4800
hours
Electricity $940 $1410 $1880 $2350 $4700 $7050 $9400 $14100
Space cooling is a free byproduct from packaged • Introducing more outdoor air than codes
dehumidifiers and chilled water systems. These require is not recommended:
systems can provide year-round temperature and – In winter, it will increase space heating and
humidity control. They dehumidify by cooling the pool water heating costs significantly.
air below its dew point and condensing moisture
– Too much outdoor air in winter can
at the cooling coil. If the cooling load exceeds the
also lower the relative humidity levels to
standard output of a dehumidification unit, a larger
uncomfortable levels for the patrons.
unit with compressor staging is often specified.
– In summer, it can introduce so much
“
additional moisture that larger equipment
could be needed.
Outdoor ventilation air is
• Warm “energy rich” air is required to be
essential for maintaining exhausted from the space to maintain negative
pressure and good IAQ.
good IAQ.
Energy recovery from the “energy rich” exhaust air
should be considered.
Air-to-air heat exchangers are available for both a large airside pressure drop, which increases
sensible heat recovery and total energy recovery. blower motor sizes and operating costs.
Sensible-only devices are used in natatoriums.
The annualized energy recovery of the glycol
All sensible recovery devices are effective,
runaround loop outperforms any other form of
but some are better suited to provide a cost-
heat recovery.
effective solution. Figure 10 highlights two
examples. There are several questions that must
be answered to determine which heat recovery
approach is best suited for a particular facility:
FIGURE 11: PACKAGED HEAT RECOVERY
Portland, OR 53 17
ANNUAL SAVINGS FROM HEAT RECOVERY DEVICE
Salt Lake City 52 3
$ {Q x $/CCF} / HE $2,062
Seattle 51 20
REDUCTION IN PEAK HEATING
St-Louis 55 2
Q1 {T3-T2} x 1.08 x V x HE Btu/h
Toronto 46 -5
• The exhaust fan can be installed remotely or A vapor retarder restricts the rate of water vapor
within the dehumidifier. diffusion through the ceilings and walls of a
building when below dew point temperature
• Energy recovery from the energy rich exhaust
occurs. Failure to install the vapor retarder in the
air to outdoor air should be considered.
proper location will result in condensation within
STEP 5: LOAD CALCULATIONS the structure and lead to structural failure. Always
ensure the vapor retarder is sealed at all the
The natatorium needs to be heated, cooled,
seams.
and dehumidified. This requires the accurate
calculation of the following loads: • The vapor retarder must be on the warm
side of the dew point temperature in all walls,
• Building envelope sensible heating load that
ceilings, and floors.
includes outdoor air
• All exterior windows, doors, and skylights must
• Building envelope sensible cooling load that
be fully blanketed with warm supply air. 3-5
includes outdoor air
CFM/ft² is recommended.
• Latent load [pool evaporation, outdoor air
(summer), and spectators] STEP 7: ENERGY & LEED CONSIDERATIONS
All manufacturers offer the ability to include the The energy consumption and performance
heating coil inside the dehumidifier. The coil should implications of the building type and operating
be fully corrosion protected and suitable for a pool conditions must be discussed with the owner.
environment. Manufacturers generally offer unit-
mounted control valves as well.
• Ensure the pool water chemicals are • If allowed by local codes, the condensate
introduced downstream of the unit, reclaim from the dehumidifier can be the
auxiliary heaters, and pumps. equivalent of one pool fill annually.
REFRIGERANT REDUCTION
If a compressorized system is being used,
efforts should be made to minimize the system
refrigerant charge and reduce the refrigerant
piping complexity. Fluid-cooled systems are a
popular option because of their inherently low
refrigerant charge and simple installation.
Spa
Equipment
Room
Typical Hotel Pool
Exterior Door
Door
Duct heater available
unit mounted
Return Air
Outdoor Condenser
Windows
Outdoor Air
Purge–Economizer
Mode ON ON 100%
EVACUATOR INTEGRATION
From an HVAC standpoint, the Evacuator is an exhaust fan that just factors into the total exhaust air
needed for the space. They generally exhaust the same amount of air required to keep the space
negative, so they blend into the design nicely.
Dehumidifier
1
14
2
13
12
3
4
6 11
7
9 10
8
5
LEGEND
Legend
1. Refrigerant Piping to Outdoor Condenser 8. Auxilary Pump
1.
2. 2.
Refrigerant Piping to Outdoor Condenser
Dehumidifier
8. 9. Auxiliary
AutomaticPumpChemical Feeder
Dehumidifier 9. Automatic Chemical Feeder
3. 3. P-Trap
P-Trap 10.10.Pool
Pool Filter
Filter
4. 4. Outdoor
Outdoor Condenser/Drycooler
Condenser/Drycooler 11.11.Main
MainPool
Pool Pump
Pump
5. Ball Valve 12. Water Inlet
5. 6.
BallFlow
ValveMeter 12. Water Inlet
13. Water Outlet
6. 7.
FlowAuxiliary
Meter Pool Heater 14.13.AirWater
Vent Outlet
7. Auxillary Pool Heater 14. Air Vent
P o o l P a k N a t a t o r i u m D e s i g n G u i d e / H u m i d i t y C o n t r o l Te c h n o l o g y 41
FIGURE 18: HOT GAS REHEAT REFRIGERATION-BASED
COIL RESULTS IN UNSTABLE DEHUMIDIFIERS
TEMPERATURES AND RH LEVELS Refrigeration-based dehumidifiers are by far
the most common and popular method of
100
90 removing moisture from the space. These are
80
70
the PPK Series units built by PoolPak. The units
60 are designed and developed specifically for
50
40
dehumidifying indoor pools, offering year-round
30
humidity control at the lowest possible operating
20
10 costs.
0
P o o l P a k N a t a t o r i u m D e s i g n G u i d e / H u m i d i t y C o n t r o l Te c h n o l o g y 42
FIGURE 20: REFRIGERATION-BASED DEHUMIDIFIERS
Filter
Bypass Heating
82°F
Compressor
52°F Vestibule
Evaporator Reheat
Filter
Pool water heating not only contributes The PPK Series substitutes hundreds of pounds of
considerable energy savings, but it also refrigerant with glycol, which is 95% less expensive
helps the unit operate more efficiently and an environmentally-preferred heat transfer fluid
overall. This generally has a tremendous for LEED® and other sustainable building projects.
return on investment that alone should make
it worth considering.
P o o l P a k N a t a t o r i u m D e s i g n G u i d e / H u m i d i t y C o n t r o l Te c h n o l o g y 43
All-DX systems have outdoor condensers Other benefits of the PPK Series include the
and hot gas reheat coils that flood with liquid following:
refrigerant for extended periods. The result
• Fully modulating, total variable reheat provides
is a large system charge, which aside from
the ultimate indoor air comfort by providing
being expensive, creates the tendency for oil
unprecedented stability in pool space
migration and premature compressor failure. The
temperature and relative humidity levels.
PPK Series’ heat exchangers instead transfer
refrigerant heat to the glycol loop, which is then • Factory-charged and sealed refrigeration
used for air reheat or heat rejection to outdoor air system means no on-site field charge
cooled dry coolers. refrigeration work or EPA-certified installation
technicians are required.
The result is greater system reliability and
• Small factory-sealed refrigerant charges
reduced project costs. Not only is there a huge
totally eliminate all issues of refrigerant and
savings in refrigerant charge, but there are also
oil migration associated with all traditional
additional installation cost savings because
DX systems.
external PVC glycol piping to dry coolers is
less expensive to install in labor/materials • Significant reduction of system refrigerant
than copper refrigerant piping. The dry cooler charges prevent costly service costly service
system also has reduced likelihood of refrigerant bills in the event of a refrigerant leak.
leaks and longer compressor life, which further • Package or split system and indoor or
reduces lifetime cost of ownership. outdoor configurations are available with no
distance limits between the unit and the AC
It should be noted this technology is not new.
heat exchanger.
Dry coolers have been employed in precision
computer-room air-conditioning systems and • Glycol is 95% less expensive than refrigerants,
environmentally-sensitive areas for decades. thus any recharging service costs are
significantly reduced in materials and labor.
At the moment, PPK Series units are offered
• No copper piping between the unit and
starting at 20 HP, but all PoolPak units can
remote condenser eliminates temptation
be provided with the dry cooler heat rejection
of material theft.
option.
• All critical components are located outside
PoolPak’s innovative heat rejection design makes of the corrosive air stream in a protective
the PPK Series equally efficient as DX systems service vestibule.
on summer design days and 5-7% more efficient
throughout the rest of the year. The innovative
fluid design uses an active refrigeration head
PADDOCK EVACUATOR INTEGRATION
pressure monitor/control that ensures the lowest
PoolPak’s PPK Series is fully compatible
possible condensing pressures to boost system
with the Paddock Evacuator source
performance year round.
capture system (www.paddockevacuator.
com), an essential technology for reducing
chloramines and delivering good indoor air
quality.
P o o l P a k N a t a t o r i u m D e s i g n G u i d e / H u m i d i t y C o n t r o l Te c h n o l o g y 44
OUTDOOR AIR VENTILATION SYSTEMS The Hybrid Series offers the following
Ventilation-based dehumidification is an advantages:
established approach that uses fresh air to dry
• Its simple design makes it easier to
the space. This approach to dehumidification is
service and maintain; smaller refrigeration
possible in areas with suitable climates that are
components cost less to operate and
dry and/or cool outdoors year round and has
maintain.
been used successfully for decades. A cooling
coil is sometimes added when the conditions • Mechanical cooling keeps the space
might be warm in summer. temperature comfortable by meeting the
sensible load.
These outdoor ventilation style units have
• Advanced control algorithm precisely
several attractive features if the facility is located
modulates outdoor air, using only
in a suitable geographic area. They have a lower
the minimum necessary to maintain
first cost than a refrigerant-based approach and
space humidity.
are also considerably simpler units operationally.
With heat recovery between the exhaust air and • Direct-drive fan array with ECM motors
outdoor air streams and controls that properly means lower energy costs and no belts!
sequence the outdoor air, this can be a very • Heat recovery standard with PoolPak’s
attractive means to ventilate a natatorium. energy efficient glycol runaround loop that
THE HYBRID SERIES dramatically reduces the cost of pre-heating
outdoor air.
The PoolPak Hybrid design provides the
simplicity, reliability, and efficiency of ventilation- The Hybrid Series is available with the following
based dehumidification for indoor pools, along options:
with heat recovery and an optional cooling coil
• Unit-mounted, EC motorized exhaust fans
to provide air conditioning if required.
• Purge mode
While the Hybrid Series is a suitable
• Packaged space heating – hot water,
dehumidification solution for indoor pools
electric, or gas furnace
in most North American climates, it is most
cost-effective in areas where outdoor air is
dry for most of the year. However, unlike
other ventilation-based dehumidifiers, the
Hybrid Series also provides sensible cooling
capability, so high outdoor air temperatures
are no longer a concern.
P o o l P a k N a t a t o r i u m D e s i g n G u i d e / H u m i d i t y C o n t r o l Te c h n o l o g y 45
TABLE 7 – SYSTEM COMPARISON
REFRIGERATION OUTDOOR AIR VENTILATION
Operating Cost Lowest Medium
P o o l P a k N a t a t o r i u m D e s i g n G u i d e / H u m i d i t y C o n t r o l Te c h n o l o g y 46
Design Checklist for Traditional Pools*
Having a checklist comes in handy when designing complex jobs. PoolPak® is pleased to provide this dehumidification
design checklist for your convenience.
* Please contact factory for Waterparks and pools heavy with water features. Design standards have been established for
‘traditional’ bodies of water and do not adequately address the special needs of these facilities.