How to create an application project using Point Table method for

MR-JE-C CC-Link IE Field Basic Servo on the GX Works3


Version 1.0

R72-19X-SLSASG-003-*
Contents
CONTENTS ......................................................................................................................................................................... I

DISCLAIMER .................................................................................................................................................................... III

FURTHER READING REFERENCE LIST ................................................................................................................................ IV

INTRODUCTION ........................................................................................................................................................ 1

PREPARATION .......................................................................................................................................................... 2

WIRING: ...................................................................................................................................................................... 2
ACTIVATE THE CC-LINK IE FIELD NETWORK BASIC IN MR-J4-GF AMPLIFIER ............................................................................. 3
IP ADDRESS SETTING ...................................................................................................................................................... 3
SERVO PARAMETER SETTING............................................................................................................................................ 5
REGISTER THE CC-LINK IE FIELD PROFILE .......................................................................................................................... 10
CREATING A NEW PROJECT............................................................................................................................................. 11
EXTEND THE DEVICE SETTING ......................................................................................................................................... 11
IMPORT THE USER STRUCTURE DATA ............................................................................................................................... 12
ENABLE THE CC-LINK IE FIELD BASIC AND ADDING THE MR-JE-C SERVO AMPLIFIER IN THE CC-LINK IE FIELD BASIC NETWORK .......... 15
CONFIGURE REFRESH SETTING ....................................................................................................................................... 17
CREATE A GLOBAL LABEL FOR MR-JE-C AXIS AND ASSIGN THE LINKS ADDRESS OF CC-LINK IEF ................................................... 18
Description of MRJEC Structure Data Type ..................................................................................................... 20

CREATE A SAMPLE PROGRAM..................................................................................................................................21

START THE CYCLIC COMMUNICATION BETWEEN THE SERVO AMPLIFIER AND CONTROLLER............................................................ 21
SERVO ENABLE ............................................................................................................................................................ 21
JOGGING THE AXIS ....................................................................................................................................................... 22
HOMING THE AXIS ....................................................................................................................................................... 23
START THE POINT TABLE MOVE ....................................................................................................................................... 24
SERVO PARAMETERS READ AND WRITE: ........................................................................................................................... 26
Read the Parameter PA09 Auto Tune response .............................................................................................. 26
Write the servo parameters ............................................................................................................................ 28
Sample example to retain parameters and point table data in the servo amplifier. ...................................... 29
POINT TABLE READ AND WRITE: ..................................................................................................................................... 30
Point Table Read ............................................................................................................................................. 30

i
Point Table Write ............................................................................................................................................ 31
GOT PROJECT ASSOCIATE WITH SAMPLE PROJECT............................................................................................................... 32
Demonstration of Simple motion .................................................................................................................... 32
Read and write the parameters using the GOT Project though the PLC program .......................................... 34
Read and write the Point Table using the GOT Project ................................................................................... 35
Read and write the Parameters directly using MR-JE-C driver ....................................................................... 36
Monitoring Alarm and Status directly using MR-JE-C driver........................................................................... 36

REVISIONS .......................................................................................................................................................................37

ii
Disclaimer

This book applies to the Mitsubishi Electric Corporation product components and to all
subsequent releases and modifications until otherwise indicated in new editions. Make sure
you are using the correct edition for the level of the product.

MITSUBISHI ELECTRIC CORPORATION PROVIDES THIS BOOK "AS IS," WITHOUT WARRANTY OF
ANY KIND, EITHER EXPRESS OR IMPLIED, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED
WARRANTIES OF MERCHANTABILITYOR FITNESS FOR A PARTICULAR PURPOSE.

This book could contain technical inaccuracies or typographical errors. Changes are made
periodically to the information herein. Mitsubishi Electric Corporation may make
improvements and changes at any time to the product(s) and/or program(s) described in this
book.

iii
Further Reading Reference List

MELSERVO MR-JE-_C Servo Amplifier Instruction Manual (Positioning Mode) SH(NA)030277ENG

MELSERVO MR-JE-_C Servo Amplifier Instruction Manual SH(NA)030257ENG

MELSERVO-JE Servo Amplifier Instruction Manual (Troubleshooting) SH(NA)030166ENG

MELSERVO MR-JE- C Servo Amplifier Instruction Manual (Network) SH030256ENG

MELSERVO HG-KN/HG-SN Servo Motor Instruction Manual SH(NA)030135ENG

MELSERVO EMC Installation Guidelines IB(NA)67310ENG

GOT2000 Series Connection Manual (Mitsubishi Electric Products) For GT Works3 Version1 (ELE) SH-081217ENG

TB: Registering CC‐LINK and CC‐LINK IE Field Device Profiles in iQ Works Navigator, GXW3 and GXW2 Software

iv
Introduction

This document describes the details setup procedure to run the MR-JE-C CC-Link IE Field Basic Servo Amplifier with point
table method on the GX Works3 platform using the iQ-FCPU PLC as CC-Link IE Field Basic master.
The following items have been demonstration:

1) Preparation
2) IP Address and Servo parameters setting
3) How to utilize the user Data structure in the program
4) Execute the Home, Jog and point table movement
5) Read/write the point table and servo parameter using FBs [SLMP]
6) GOT sample code

The following hardware and software are used to create this quick start guide.

Item Version
GX Works3 1.038Q or later
MR Configurator2 1.70Y
FX-F5U 1050
MR-JE-C A4 or later
HG-KN13 Motor
MR-BAT6V1SET-A battery Optional [ Required for Absolute system)
MR-TB26A Terminal block
MR-TBNATBL05M Junction Terminal Block Cable
Ethernet Switch

R72-19X-SLSASG-003-*
Preparation

Assumed the user has a PC with installed GX Works3 and MR configurator2. These steps will be further detailed in the
subsequent section.
1) Connect the programming PC, PLC and Mitsubishi Servo amplifier to the Ethernet network:

a. Configure all devices to have proper IP addresses and subnet masks;

b. Ensure that GX Works3 (Ver. 1.038W or later) and MR Configurator2 (Ver. 1.70Y or later) software
packages are installed on the programming PC.

2) Register the MR-JE-C CC-Link IE basic profile

3) Create a new project to control the MR-JE-C servo amplifier

a. Import the user structure data type [included with this document]

b. Make a sample project for Jog, home and execute the Point table.

c. Create a sample project to read/write servo parameters and point table data

4) Created a GOT project that is associated with this sample project.

Wiring:
One MR-JE-C drive with a servomotor and FX-F5U PLC are used to create the demo program. The wiring option
shows below:

1) Wired three-phase AC power supply to L1, and L3 for main power main and control power.
2) U, V, W wiring between Motor and Amplifier
3) Connect the motor encoder cable between motor and CN2 of the MR-JE-C Amplifier.
4) Connect Ethernet patch cable between PC, PLC’s Ethernet Port, and MR-JE-C Amplifier [CN1 Port] to Ethernet
switch.
5) Wire the digital switch LSP, LSN and EMG2 from MR-TB26A terminal to switch box

Switch Box Input # Pin Number Assigned function


1 CN3-1 EM2- Forced stop 2
2 CN3-2 DOG-Proximity dog
3 CN3-3 LSP-Forward rotation stroke end
4 CN3-4 LSN-Reverse rotation stroke end
6) Wire the AC Power to iQ-F PLC system

2
R72-19X-SLSASG-003-*
Activate the CC-Link IE Field Network Basic in MR-J4-GF amplifier
By default the communication method is CC-Link IE Field Network Basic, SLMP and Modbus/TCP. Check the
communication function selection" of [Pr. PN08] is set to 0001.

IP address Setting
The IP address can be set by SLMP command or MR Configurator2.The initial value of the IP address is 192.168.3.0. 1st
, 2nd and 3rd octet must be set by SLMP command or MR Configurator2. The 4th octet can be set to 1 to 255 by using
rotary switches (SW1/SW2) or parameter PN14. The 4th octet setting only is valid through the Parameter PN14 when
the (SW1/SW2) rotary switch position are set to zero.

3
R72-19X-SLSASG-003-*
Note: Cycle the power of the servo amplifier after changing the parameter setting of the IP address or switching the
rotary switches (SW1/SW2).

4
R72-19X-SLSASG-003-*
Servo Parameter Setting
1) It is good idea to set the all parameters in factory default you use it any others mode.
i) Open the MR configurator2 with Model selection [MR-JE-C] and click on [Parameter] in the Project
Window and then click [Set To Default] Tab.

ii) Choose radio button [00AA] and Clsick [OK]

iii) Write to Amplifier by Click [Axis Writing] Tab and then recycle the power.

5
R72-19X-SLSASG-003-*
2) Set the IP address: Click on Network 1 Tab and set ip address.

3) Select a Control Mode selection to Positioning mode (point table method).

4) Set the absolute Position detection [optional] if you want to retain position value after power off the system.

6
R72-19X-SLSASG-003-*
5) Set the electronic gear ratio. In this example is set one rev of servo motor move equal to 8192 PLS of command.

6) Set the necessary parameters for homing routine, in this example, home type setting is the [Dog less Z phase
reference] and home speed is 100 r/min.

7
R72-19X-SLSASG-003-*
7) Setting the actual position value after home return completion in parameter PT08[Home position return
position data]

Note: switch power off once after setting, and then switch it on again, and it will be valid
8) Assign the Digital I/O to CN3 connector pins. In this example LSP, LSN and EM2 signal is connect to the
amplifier CN3 connector.

9) Set PD35 =0202 for keep retain the home position if LSP/LSN signal is experienced.

8
R72-19X-SLSASG-003-*
You may ignore or bypass the digital signal LSN, LSP and EM2 by the setting below:

10) Set the Command interface selection to communication interface (Object command enabled) at parameter
PN08 to 0001

11) Write to all parameters to Amplifier by Click [Axis Writing] Tab and then recycle the power.

9
R72-19X-SLSASG-003-*
Register the CC-Link IE Field profile
Install the CC-Link IE Field profile before creating a project.
1) Download the CC-Link IE Field profile for MR-JE-C basic and save at the local hard drive. The profile name:

0x0002_MR-JE-C_1_en.CSPP.zip

2) Open the GX Works3 and open the profile register window from ToolProfile Management  Register

3) Choose the file [unzip format] and double click on [Register] button. Profile will install and completion pop-up
window will appear

Note: Details in the links Registering CC‐LINK and CC‐LINK IE Field Device Profiles in iQ Works Navigator, GXW3
and GXW2 Software

10
R72-19X-SLSASG-003-*
Creating a new project
Create a new project with the proper PLC type and choose programming language FBD/LD. In this example PLC Series
FX5CPU and type FX5U.

Extend the Device setting


Periodically performs the data communication between the master station and slave stations using link devices
(RX/RY/RWr/RWw). Every station needs 64 bits input link device and 64 bits output link devices. In this project, B device
is going to be used for bits links devices. iQ-F series PLC allocates 256 bit B device by default. We would like to extend
the B device so that it can handle 6-slave station. In this example reduced the Latch Relay L and increased Link Relay B
from the Parameter  FX5UCPU  CPU Parameter  Memory/Device Setting  Device/Label Memory Area setting
 Detailed Setting

11
R72-19X-SLSASG-003-*
Ether the Value 4032 in Latch Relay L row and 3094 in Link Relay row and click the [Apply] button.

Import the User Structure data


The user library FBs_iQF_MRJEC_Basic_PT_A2 include the data structure that we will use to create a sample project.

FBs_iQF_MRJEC_Bas
ic_PT_A2 .usl

1) In the Element Selection Window, Click [Library] Tab. If Element Selection Window does not appear
at the right side of your GX Works3, then bring from View  Docking Windows  Element Selection

12
R72-19X-SLSASG-003-*
2) In the Element selection window, right click on the open area and choose [Register to Library List]  User
Library..

3) Choose library from your local hard drive and click [Open] Tab.

13
R72-19X-SLSASG-003-*
4) Now the User library in your GX works3 platform.

14
R72-19X-SLSASG-003-*
Enable the CC-Link IE Field basic and adding the MR-JE-C servo amplifier in the CC-Link IE
Field basic network
1) Double click on Parameter  FX5UCPU  Module Parameter  Ethernet Port

2) Then click Basic setting and set the own node IP Address, Subnet Mask, and Default Gateway and enable the
CC-Link IE Field basic setting. In this example, IP Address and Gateway address set respect to 192.168.3.250
and 192.168.3.254. and choose the [Enable] on the CC-Link IEF Basic function.

15
R72-19X-SLSASG-003-*
3) Double click on [<Detailed Setting>] on Network configuration settings

4) Drag and drop the MR-JE-C in the network from the Module List.

5) In this example, Three MR-JE-C amplifiers bring to the network and keep the all default setting. By default, IP
address of servo amplifier setting are 192.168.3.1 and then click the Tab[Close with Reflecting Setting ]

16
R72-19X-SLSASG-003-*
Configure Refresh Setting
Double click on [<Detailed setting>] from Parameter  FX5UCPU  Module ParameterEthernet Port, select CC-Link
IEF basic settings, and click on Refresh settings. In this example, the head address of RX assign to B000, the head address
of RY assign to B180, the head address of RWr assign to W000 and the head address of RWw assign to WC0

17
R72-19X-SLSASG-003-*
Create a global label for MR-JE-C axis and assign the links address of CC-Link IEF
1) Drag and drop the Structure Data [AxisJEC] under FBs_iQF_MRJEC_Basic_PT_A2 from Element selection
window to under Structure Data Types in the Navigation window. This process will bring all the necessary user
data structure in the project

2) Create a label variable Axis1 with Data Type AxisJEC

18
R72-19X-SLSASG-003-*
3) Click on display setting and choose

To assign the links Device, expand the AxisJEC edit window and click IN and assign to W0. In this example, the
1st station word read links is W0 [RWr]

Then click on Outs and assign W0C0: In this example, the 1st station write links device is W0C0 [[RWw]

If your system has 2nd station, the links read and write resister will be W20 and W0E0 respectively.

19
R72-19X-SLSASG-003-*
Description of MRJEC Structure Data Type

A Structured Data Type is a structured, derived data type containing a collection of labels, which can have assigned
different data types. Structured Data Types can be declared as global or as local labels. Values can be given to the
individual elements (labels) of the data type in the body of a Program Organizational Unit (POU).

MRJEC Structured Data type is contained of RWwn/RWrn mapping of MR-JE-C CC-Link IE Field basic servo amps.

Structure Label Name


Data
Label under IN [FromJEC] Label under STA[Statusword]

IN

AxisJEC Out Label under Outs [ToJEC] Label under CTR [Controlword]

20
R72-19X-SLSASG-003-*
Create a Sample Program

This section shows an example to create sample program by using MRJEC structure data.

Start the cyclic communication between the servo amplifier and controller
Turn on the cyclic communication ready command [RY (n + 3) F] to establish the communication between CC-Link IF master
and salve. Check the status on Cyclic communication ready [RX (n + 3) F]. The screenshot below shows an example of station
one.

Servo enable
The enabling the servo, turn on 1st four LSB bits of the control word and disabling to servo turn of the bit # 3 of the control
word. In this example, the Label variable [ServoONAx1] off to ON make servo enable and OFF to ON make servo disable.

21
R72-19X-SLSASG-003-*
Jogging the Axis
The following table shows the necessary setting for executing the Jog function.

Label Name Setting Value Comment


Axis1.Outs.ModeOfOperation -100 Modes of operation selection [-100: Jog mode]
Axis1.Outs.ProfileVelocity 10000 Set the servo motor speed in rpm x0.01
Axis1.Outs.Acceleration 1000 Set the acceleration time constant in ms to reach the rated speed
Axis1.Outs.Deceleration 1000 Set the deceleration time constant in ms from the rated speed to
zero speed.
Axis1.Outs.CTR.Immediate_Dir True or False Set Direction of rotation in Controlword bit 5. The setting value:
ON: CW and OFF: CCW
Axis1.Outs.CTR.StartNewPos OFF to ON Set start/stop in "Controlword bit 4 [Rotation start) The setting
is shown as follows: On: start
Off: deceleration to a stop

In this example, axis one switch to jog mode when the Label [JogModeAx1] turn OFF to ON and starts to move forward
direction with 100 rpm when the label [RunJogAx1] goes turn OFF to ON and axis stop when variable [RunJogAx1] is turn
ON to OFF.

22
R72-19X-SLSASG-003-*
Homing the Axis
There are many ways to establish the home method. In this example, we are performing the homing type -11[home
to encoder Z pulse]. The Home type (PT45), speed (PT05) creep speed (PT06) have to set by MRC2 or writing these
parameters by programming [SLMP]. See details in section 2.5
Also the actual position value can be set after home return completion in parameter PT08[Home position return position

data]

Note: switch power off once after setting change of PT08, and then switch it on again, and it will be valid

The following table shows the necessary setting for executing the home routine:

Label Name Setting Value Comment


Axis1.Outs.ModeOfOperation 6 Modes of operation selection [6: Homing mode]
Axis1.Outs.CTR.StartNewPos OFF to ON Homing Operation Start (Home position return operation start)
0: Do not start the homing procedure
1: Start or continue homing procedure
In this sample code, axis one switch to Homing mode when the Label [HomeModeAx1] turn OFF to ON and starts the home
routine when the label [StartMoveHomeAx1] goes turn OFF to ON. The label bit HomeDoneAx1 is turn on completion of
the home routine.

23
R72-19X-SLSASG-003-*
Start the point table move
The following table shows the necessary setting for executing the Point table function.

Label Name Setting Value Comment


Axis1.Outs.ModeOfOperation -101 Modes of operation selection [-Point table mode (pt) selection]
Axis1.Outs.TargetPointTable 1 to 255 Set the target point table No.
Axis1.Outs.CTR.Immediate_Dir True or False Set Direction of rotation in Controlword bit 5. The setting value:
ON: CW and OFF: CCW
Axis1.Outs.CTR.StartNewPos OFF to ON Set in "Controlword bit 4 [start new point table)

In this sample code, axis one switch to Point table mode when the Label [PointTableModeAx1] turn OFF to ON and starts
the selected point table move when the label [StartPointTableAx1] goes turn OFF to ON. The label bit [MovecompletedAx1]
turns ON the completion of the point table move. Switching on "Controlword bit 5 (Direction)" starts a reverse rotation of
the motor in accordance with the values set to the selected point table

24
R72-19X-SLSASG-003-*
25
R72-19X-SLSASG-003-*
Servo Parameters Read and write:
SLMP (SeamLess Message Protocol) is a common protocol, which allows applications to communicate seamlessly regardless
of different types of networks and network layers. SLMP communications can be performed for the connection with
external devices, such as a programmable controller, a personal computer, and HMI, that can send and receive messages
by using SLMP control procedures. The MR-JE-C servo amplifier is compatible only with the binary code. In the plc program,
two Fbs have been is created to read and write the object of MR-JE-C amplifier by using the SLMP protocol.

1) SVFB_ReadObject Reads an object of a servo amplifier


2) SVFB_WriteObject Writes an object of a servo amplifier.

Read the Parameter PA09 Auto Tune response

The example shows how to read the object from the amplifier.

1) Set the IP address and Object properties


Label Name Setting Value Comment
ExtDevice.wIPaddress[0] HCOA8 Set 1st and 2nd Octet value of IP Address
ExtDevice.wIPaddress[1] H0301 Set 3rd and 4th Octet value of IP Address
ExtDevice.wPortNo 5010 Setting Fixed UDP port# 5010
ExtDevice.wResendNum 3 Set the retry times
ExtDevice.wMonitoringTime 5 Set the response time in ms
ObjectInfo.wIndex H2009 Set index number of PA09
ObjectInfo.wSubIndex 0 Set sub index number of PA09
ObjectInfo.dData x For reading keep this field empty
ObjectInfo.wSize 0 Set data size: 0 for reading

26
R72-19X-SLSASG-003-*
1) Set the IP Address of MR-JE-C in the structure data[ExtDevice] that is the input of SVFB_ReadObject Fbs

In this example shows the


setting of IP Address is
192.168.3.01 [C0.A8.3.01]

Setting Fixed UDP port#


5010

2) In this example Object number is H2009 to read the parameters PA09 of the servo amplifier, Object sub index is 0
and size and data is set to zero.

27
R72-19X-SLSASG-003-*
3) Then execute the SVFB_ReadObject FBs. Turn the label [ExcuteRead] Off to ON, the read value of PA09 will show
on the Label [ReadData]

Write the servo parameters

The following example shows the writing the servo parameter of PT08 Home position return position data
2) Set the IP address and Object properties
Label Name Setting Value Comment
ExtDevice.wIPaddress[0] HCOA8 Set 1st and 2nd Octet value of IP Address
ExtDevice.wIPaddress[1] H0301 Set 3rd and 4th Octet value of IP Address
ExtDevice.wPortNo 5010 Setting Fixed UDP port# 5010
ExtDevice.wResendNum 3 Set the retry times
ExtDevice.wMonitoringTime 5 Set the response time in ms
ObjectInfo.wIndex H2488 Set Index number of PT08
ObjectInfo.wSubIndex 0 Set Sub Index number of PA09
ObjectInfo.dData 0 to 65535 Set the value of Position
ObjectInfo.wSize 4 Set data size: 4 for writing

3) Execute the SVFB_WriteObject FBs. Turn the label [ExcuteWrite] Off to ON, the parameter PA09 will be written to
Servo Amplifier.

28
R72-19X-SLSASG-003-*
Sample example to retain parameters and point table data in the servo amplifier.

The parameters and the point table data is written to RAM area when the user modifies by using the SLMP commands. That
means after power recycles, the data will loss. The user has to execute the writing command to EEP-ROM to retain the value
in the amplifier.

The following table shows the necessary setting for the writing command to EEP-ROM
Label Name Setting Value Comment
st nd
ExtDevice.wIPaddress[0] HCOA8 Set 1 and 2 Octet value of IP Address
ExtDevice.wIPaddress[1] H0301 Set 3rd and 4th Octet value of IP Address
ExtDevice.wPortNo 5010 Setting Fixed UDP port# 5010
ExtDevice.wResendNum 3 Set the retry times
ExtDevice.wMonitoringTime 5 Set the response time in ms
ObjectInfo.wIndex H1010 Set index number of Writing command to EEP-ROM
ObjectInfo.wSubIndex 0 Set sub index number of Writing command to EEP-ROM
ObjectInfo.dData H65766173 Set the value for Save command
ObjectInfo.wSize 4 Set data size: 4 for Writing data size

The label [ExecuteWrite] turn OFF to ON starts to store all parameters and point tables.

Note: Executing the writing


command to EEP-ROM (Store
Parameters) takes about a
maximum of 10 s because all
parameters are written at the
same time. Do not shut off the
power during writing.

29
R72-19X-SLSASG-003-*
Point Table Read and write:
In the plc program, two FBs have been is created to read and write the Point table of MR-JE-C amplifier by using the SLMP
protocol.

1) SVFB_ReadPointTable Reads the point table value of a servo amplifier


2) SVFB_WritePointTable Writes the point table value to the servo amplifier.

Point Table Read

The following table shows the necessary setting for reading the Point Table data from the amplifier

Label Name Setting Value Comment


st nd
ExtDevice.wIPaddress[0] HCOA8 Set 1 and 2 Octet value of IP Address
ExtDevice.wIPaddress[1] H0301 Set 3rd and 4th Octet value of IP Address
ExtDevice.wPortNo 5010 Setting Fixed UDP port# 5010
ExtDevice.wResendNum 3 Set the retry times
ExtDevice.wMonitoringTime 5 Set the response time in ms
PointTableNoAx1 1 to 255 Set the point table number need to be read

Then turn OFF to ON the label variable [ExecuteReadPT] and reading will store in the user data type label variable
[ReadValuePT] which is the structure data of [PointTableData].

The sample example is given below:

The elements of Data structure PointTableData is shown below:

30
R72-19X-SLSASG-003-*
Point Table Write

The following shows tables the necessary setting for writing the Point Table data to the amplifier.

Label Name Setting Value Comment


ExtDevice.wIPaddress[0] HCOA8 Set 1st and 2nd Octet value of IP Address
ExtDevice.wIPaddress[1] H0301 Set 3rd and 4th Octet value of IP Address
ExtDevice.wPortNo 5010 Setting Fixed UDP port# 5010
ExtDevice.wResendNum 3 Set the retry times
ExtDevice.wMonitoringTime 5 Set the response time in ms
WriteValuePT.Position -999999 to 999999 Set target position
WriteValuePT.Speed 0 to 16777215 Set motor speed x 0.01 r/min
WriteValuePT.Acceleration 0 to 20000 Set the acceleration time in ms to reach the rated speed
WriteValuePT.Deceleration 0 to 20000 Set the deceleration time in ms to stop from the rated speed
WriteValuePT.Dwell 0 to 20000 Set dwell time and complete the position command
WriteValuePT.Subfunction 0-3, 8-11 Set auxiliary function ( see the in manual0
PointTableNoAx1 1 to 255 Set the point table number need to be written

Set the above value and turn OFF to ON the label variable [ExecuteWritePT].
The sample example is given below:

31
R72-19X-SLSASG-003-*
GOT project associate with sample project.
A sample GOT Project is included with this QSG to the demonstrated simple functionality of MR-JE-C CCLIF basic servo.

Demonstration of Simple motion

The main screen is associate to control the axis number one.

Assume GOT and PLC project is downloaded and amplifier is connected properly to the controller.
1) Click the button [Servo ON ] to make the servo Enable.
2) Click on the [Switch to Speed Mode] button, Enter speed in r/min and then click [Jog] button to execute the Jog.
The user can change the direction by clicking the [FWD/REV].
3) Click on the [Switch to Homing Mode] button to execute the home routine and click [Home] button to execute
the home routine. Homing parameters need to set before by using SLMP command or MRC2.
4) Click on the [Switch to Positioning Mode] button to execute the point table and then enter the point table number
PT# and click [Run] button to execute the specified point table. The user can change the direction by clicking the
FWD/REV button. The direction bit valid if the servo amplifier set the position command of the point table as
incremental value command system.
5) In addition, the user can read and modify the command position and speed command value from this screen by
click the [Read PT] and [Write PT] value

32
R72-19X-SLSASG-003-*
6) Switch to Setting and monitoring window.

PLC program is required

Servo access directly using


MR-JE-C Driver

33
R72-19X-SLSASG-003-*
Read and write the parameters using the GOT Project though the PLC program
Read and write the parameters of all the axes.
1) Click the button [Setting /Monitoring ] from main screen and then Click the button [Parameters and Point Table
Read/Write via PLC] to access the screen below.

2) Set the axis number number (4th octet of IP address) in Axis # numerical input box.
3) Set the Parameter Group 1 to 9. [Setting value 1: PA , 2: PB …..]
4) Enter the parameter number and click [Read] button
5) Read value will show numerical display box.
6) For writing the enter the value input box and click [Write] button

34
R72-19X-SLSASG-003-*
Read and write the Point Table using the GOT Project

Read and write the point table data of all the axes.
1) Click the button [Setting /Monitoring ] from main screen and then Click the button [Parameters and Point Table
Read/Write via PLC] to access the screen below:

2) Set the axis number number (4th octet of IP address) in Axis # numerical input box.
3) Enter the Point Table number in PT# numerical input box ,
4) Then click [Read PT] button
5) Read value will show numerical display box.
6) For writing, Enter the point table number, position command, speed command , acceleration , deceleration, Dwell
time and auxiliary function in the input boxes and click [Write PT] button
7) Click Write to EEP-ROM button to save the all parameters and point table data to EEPROM.

35
R72-19X-SLSASG-003-*
Read and write the Parameters directly using MR-JE-C driver

Click the button [Setting /Monitoring ] from main screen and then Click the button [Parameters Read/Write using]
to access the screen below:

User can access all parameters and modify. All parameters retain in non-volatile memory in the servo amplifier

Monitoring Alarm and Status directly using MR-JE-C driver

Click the button [Setting /Monitoring ] from main screen and then Click the button [Monitoring] to access the screen below:

Details list of status device in manual GOT2000 Series Connection Manual (Mitsubishi Electric Products) For GT Works3
Version1 (ELE) SH-081217ENG  Section 16.4.2 : 11. MELSERVO-JE-*C.

36
R72-19X-SLSASG-003-*
Revisions

1) Version 1.0 Issued Date: 10/10/2019

37