Professional Documents
Culture Documents
Three Phase Six Phase
Three Phase Six Phase
Three Phase Six Phase
net/publication/3274632
CITATIONS READS
5 3,824
1 author:
Xusheng Chen
Seattle University
20 PUBLICATIONS 355 CITATIONS
SEE PROFILE
Some of the authors of this publication are also working on these related projects:
Duality Derived Transformer Models for Low-Frequency Electromagnetic Transients View project
All content following this page was uploaded by Xusheng Chen on 28 May 2015.
Abstract—The first commercial demonstration of six-phase conversion autotransformers were conceptually designed. It is
transmission, the Goudey-Oakdale three-phase/six-phase project, well known that the weight and cost of transformers of similar
used two delta wye-grounded three-phase transformers to realize voltage ratings are proportional to the total megavolt ampere
the required phase/voltage conversion. This paper proposes the
usage of autotransformers for phase/voltage conversion for the (MVA) of parts. The cost ratios of the proposed step-up and
actual three-phase/six-phase systems to be built in the future. step-down autotransformers with respect to three-winding
The design considerations of the three-phase/six-phase conversion conversion transformers are 64.3% and 64.1%, respectively.
autotransformers are described. Topology-based, nonlinear, Clearly, the autotransformers are superior economically to
core-type conversion autotransformer EMTP models are de- other transformer designs. Considering that for the same
veloped. The behavior of the conversion autotransformers in a
practical three-phase/six-phase system is simulated. These include line-to-neutral voltage the six-phase transmission line could
transformer energization, short circuits, voltage regulation, open double the power flow capability—this is why the six-phase
conductor, and ferroresonance. The simulation results show transmission system is being actively researched, and that the
that the autotransformer is a viable choice for the conversion installation costs of the two delta-wye three-phase transformers
transformer. Since the cost ratio of the proposed conversion used in the Goudey-Oakdale project account for 60% of the
autotransformers with respect to the three-winding conversion
transformers is approximately 64%, the new design is superior total terminal costs [4], the proposed autotransformers will
economically to other transformer designs, and will help push the definitely help push the HPO technology.
HPO technology.
Index Terms—Autotransformer, six-phase, transmission. II. CONCEPTUAL DESIGN OF THE STEP-UP CONVERSION
AUTOTRANSFORMER AND DETERMINATION OF
ITS EMTP MODEL PARAMETERS
I. INTRODUCTION
Fig. 1 shows the three-phase/six-phase transmission system
C ONSIDERATION of the fundamental limits on power
transfer in a restricted right-of-way led to the concept of
increasing the number of phases in a circuit from three to six
similar to the Goudey-Oakdale system described in [3]. The
line-to-neutral voltages for the three-phase and the six-phase
lines are kV and 93 kV, respectively. This
or twelve. This is called high phase order power transmission
conversion autotransformer is termed as the step-up autotrans-
(HPO). At first as an idea, it gained credibility with a feasibility
former (the six-phase side has a higher line-to-neutral voltage
analysis published in the late 1970s [1]. As a laboratory proto-
than that of the three-phase side). Note that the polarities of
type demonstration, an 80-kV phase-to-ground six-phase line
the “dfb” three-phase windings (called tertiary windings in
and a 138-kV phase-to-ground twelve-phase line were built at
this paper) are reversed. The neutrals of the transformer are
the Malta test facility of Power Technologies Inc., Schenectady,
grounded.
NY, with support from the Department of Energy [2]. As the
The autotransformer is assumed to be 250/125/125-MVA,
initial application on an operating utility transmission system,
66.4/93/93-kV line-to-neutral, 60 Hz, five-legged, and wye-
the Goudey-Oakdale line near Binghamton, NY, operated as a
grounded. Its characteristics are summarized in Table I, and its
six-phase, 93-kV phase-to-ground line for two years [3]. Two
one-phase schematic diagram is shown in Fig. 2.
delta/wye-grounded three-phase transformers were used to
The design of the conversion autotransformer and the prepa-
realize the required phase/voltage conversion. Possible reuse of
ration of ATP data file proceed as follows:
the existing three-phase transformers and the isolation of the
To have the autotransformer provide a balanced set of volt-
zero-sequence networks of the three-phase/six-phase systems
ages and currents, it is required that the short-circuit impedances
resulted in the above choice.
from the three-phase side to the two sets (ace and dfb) of the six
However, in a panel discussion of the 1994 IEEE Trans-
phase side be equal .
mission and Distribution Conference, Chicago, IL, Guyker
Redefine the autotransformer as a three-winding transformer
from Allegheny Power Service Corporation pointed out that
with series, common, and tertiary windings as I, II, and III wind-
“What is needed today to help push HPO technology is not
ings, respectively (Fig. 2). Assume that cylindrical windings are
a cobbling of wye and delta banks, but an autotransformer
used and that the layout of one phase of the windings and iron
that provides a balanced set of voltages and currents at a cost
is as shown in Fig. 3.
comparable to the wye-delta combination currently used”. This
The short-circuit impedances between the three windings I,
statement motivated the author to conduct the research reported
II, and III are calculated as follows [5]:
in this paper. Step-up and step-down three-phase/six-phase
TABLE I
CHARACTERISTICS OF THE 250-MVA AUTOTRANSFORMER (10)
mH (11)
It should be noted that the base current for the six-phase side
is twice that of its rated current.
The leakage and zero-sequence inductances referred to
winding III are calculated as
mH (12)
mH (13)
mH (14)
mH (15)
where is the zero sequence leakage inductance
through the air and the tank.
Usually, transformer winding resistances are calculated from
short-circuit test data. Since no conversion autotransformers
have yet been built, their values are assumed to be
kV
(2) kV
kV
The core loss resistances are connected to the six-phase side for
the left side transformer and the three-phase side for the right
side transformer (Fig. 1). Their values are
k (16)
k (17)
(3)
A transformer data file was prepared for ATP supporting rou-
The reason for can be found in [6]. tine SPR.FOR [6]. SPR.FOR scales the – curve of the trans-
Assuming that the short-circuit reactances are equal to the former to match the specified excitation current, and generates
short-circuit impedances, and noting that inductance is equal to curves for each nonlinear segment of the core.
reactance in per unit, the values of the leakage inductances of Nine ideal transformers are used to connect the autotrans-
the model can be determined [6] former model to the system. The turns ratios of the ideal trans-
formers are 0.29:1, 0.71:1, and 1:1, for windings I, II, and III,
respectively.
(4) ATP input data for the conversion autotransformer are sum-
marized in Table II.
The 1.51-mile six-phase transmission line is modeled by ATP
(5) branch cards for PI-Equivalents (coupled R-L-C circuits) with
the following constants:
mH F
(6)
mH F
Choosing 250 MVA, kV and kV for and
as the power and voltage bases, respectively, the base currents,
impedances, and inductances for the transformer are calculated The power system external to the three-phase/six-phase
as system is represented by two three-phase voltage sources ,
, and , and , , and . The rated voltage of the
A (7) two sources is 66.4 kV line-to-neutral.
TABLE II
ATP INPUT DATA FOR THE 250-MVA AUTOTRANSFORMER
(a)
(a)
(b)
Fig. 5. Six-phase short-circuit (a–c–e–d–f –b) of the autotransformer.
(a) Simulated six-phase side short-circuit current waveforms. (b) Short-circuit
equivalent circuit.
(b)
Fig. 4. Simulated excitation current and voltage waveforms. (a) Three-phase
side excitation currents. (b) Six-phase side line-to-neutral voltages.
B. Short-Circuit Performance
Breaker is closed, and the rest breakers are open for all
the short-circuit simulations (see Fig. 1)
1) Six-phase short-circuit – – – – – .
Fig. 5(a) shows the six-phase side short-circuit current wave-
forms. The rms currents for phases , , , , , and are
11.84, 11.91, 11.87, 11.69, 11.74, and 11.73 kA, respectively.
The average short-circuit current for phases ace is 11.87 kA or
13.25 p.u., for phases dfb is 11.72 kA or 13.08 p.u., and for
phases ABC (the three-phase side) is Fig. 6. Current waveforms for a–d short-circuit.
kA, or 26.29 p.u.
The transformer’s short-circuit equivalent circuit is shown in Fig. 6 shows the current waveforms for both sides of the trans-
Fig. 5(b). The rms short-circuit current can be calculated as former. The rms currents are kA or 26.45 p.u.,
A, A, and kA
p.u. or 13.29 p.u. It is observed that the short-circuit currents of
the – -ground short-circuit are the same as that of the –
which is seen to be almost the same as the computed value of short-circuit.
26.29 p.u. 3) Phases a and ground short-circuit – .
The astute readers must have noticed that the conventional Fig. 7 shows the current waveforms for both sides of the trans-
star-circuit of a three-winding transformer was used to calcu- former. The rms currents are kA or 12.76 p.u.,
late the six-phase short-circuit currents. A simple reasoning is A, A, and kA or 12.89 p.u.
offered here. If complete balance of the system can be assumed, It is gratifying to note that the results of the short-circuit anal-
then and , which sug- ysis of the transformer are in excellent agreement with that of
gest that a six-phase short-circuit can be treated as two simul- the theoretical analysis presented in [7].
taneous three-phase (ace and dfb) short-circuits. The currents C. Voltage Regulation
on the three-phase side can be determined by the balance of the
magnetomotive forces (mmfs) per phase. The inversion of po- For convenience of simulation, the voltage regulation (VR) is
larity of one set of the voltages on the six-phase side will not defined as
change the short-circuit currents on the three-phase side.
2) Phases and short-circuit – . (18)
1558 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 18, NO. 4, OCTOBER 2003
(a)
Fig. 7. Current waveforms for a–g short-circuit.
(b)
where
no load voltage rated voltage;
full load voltage.
Fig. 8 shows the six-phase side voltage waveforms when the
left side transformer carries a rated six-phase pure inductive
load. The six-phase side voltages are balanced. The voltage reg-
ulation is .
Knowing p.u. and p.u., the (c)
voltage regulation can be easily calculated [see Fig. 5(b)]
(19)
Fig. 13. Layout of phase A windings and iron of the step-down conversion full load condition (20)
autotransformer.
where is the voltage ratio of the primary and second
wye-grounded. The short circuit impedances are assumed as sides; , , and , are rated currents of the common
follows: winding, series and tertiary windings, and the three-phase side,
respectively.
and
MVA of parts step-up autotransformer
Following the same procedure as for the step-up auto-
transformer discussed in Section II, the following results are
obtained: (21)
and MVA of parts step-up three-winding transformer
Note that the constraint of for the (22)
layout of windings and iron of Fig. 3 is lifted for that of Fig. 13.
The base inductance for winding III, and the leakage and Cost ratio (23)
zero-sequence inductances referred to it are
2) Cost ratio for the step-down autotransformer (Fig. 12).
The current rating for the common winding is determined by
mH lines ace open if , and lines dfb open if
mH
if (24a)
mH
if (24b)
mH
mH Cost ratio if (25a)
VI. CONCLUSION [2] J. R. Stewart and I. S. Grant, “High phase order—Ready for applica-
tion,” in Proc. 1981 IEEE Power Eng. Soc. Transmission and Distribu-
Conceptual designs for step-up and step-down three- tion Conf., Minneapolis, Minnesota, Sept. 20–25, 1981, Paper 81 TD
phase/six-phase conversion autotransformers are presented. 675-8.
[3] J. R. Stewart et al., “Transformer winding selection associated with
The proposed autotransformers are placed in a practical re-configuration of existing double-circuit line to six-phase operation,”
three-phase/six-phase system and simulated comprehensively. IEEE Trans. Power Delivery, vol. 7, pp. 979–985, Apr. 1992.
The conceptual design shows signs of desirable performace [4] T. L. Landis et al., “High phase order economics: Constructing a new
transmission line,” IEEE Trans. Power Delivery, vol. 13, pp. 1521–1526,
and is superior economically to other transformer designs Oct. 1998.
for conversion purposes. Further work is definitely needed [5] H. W. Dommel, Electromagnetic Transients Programs—Reference
to verify other performance measures such as lightning and Manual. Porland, OR: BPA, 1986.
[6] X. Chen and S. S. Venkata, “A three-phase, three-winding core-type
switching performance, corona behavior, and other important transformer model for low-frequency transient studies,” IEEE Trans.
ones. It is suggested that conversion autotransformers be used Power Delivery, vol. 12, pp. 775–782, Apr. 1997.
in the commercial three-phase/six-phase transmission systems [7] S. S. Venkata et al., “138-kV, six-phase transmission system: Fault anal-
ysis,” IEEE Trans. Power Apparat. Syst., vol. PAS-101, pp. 1203–1218,
to be built in the future. May 1982.
ACKNOWLEDGMENT
The author wishes to express his sincere appreciation to
Dr. S. S. Venkata of Iowa State University, who initiated this
research project and whose advice and experience on HPO Xusheng Chen (M’88) was born in Shanghai, China. He received the M.S.E.E.
technology have been invaluable. degree in power systems from Jiao Tong University, Shanghai, China, in 1981.
He received the Ph.D. degree in electrical and computer engineering from Wash-
REFERENCES ington State University, Pullman, in 1987.
Currently, he is a Professor at Seattle University, WA. His areas of interest
[1] S. S. Venkata, W. C. Guyker, and W. H. Booth, “138-kV, six-phase elec- include power system transients and protection, electrical machine modeling,
trical power transmission system,” in Proc. Amer. Power Conf., vol. 40, six-phase nonlinear circuit analysis, power transmission, and wind generation.
Chicago, IL, Apr. 1978, pp. 1293–1303. Dr. Chen is a member of Tau Beta Pi.