ADMINISTRATION AND ENFORCEMENT the provision of this standard and referenced standards, the
provisions of this stand31'd shall apply. Infonnative references
4.1 General
are cited to acknowledge sources and are not part of this stan-
4.1.1 Scope d31·d. They are identified in huonnative Appendix E.
4.1.1.1 New Buildings. New buildings shall comply 4.1.7 Normative Appendices. The nonnative appendi-
with the standard as described in Section 4.2. ces to this standard are considered to be integral parts of
4.1.1.2 Additions to Existing Buildings. An extension the mandatory requirements of this standard, which, for
or increase in the floor area or height of a building outside of reasons of convenience, are placed apart from all other nor-
the existing building envelope shall be considered additions to mative elements.
existing buildings and shall comply with the standard as
4.1.8 Informative Appendices. The infonnative appen-
described in Section 4.2.
dices to this standard and infonnative notes located within this
4.1.1.3 Alterations of Existing Buildings. Alterations standard contain additional information and are not manda-
of existing buildings shall comply with the standard as tory or part of this standard.
described in Section 4.2.
4.2 Compliance
4.1.1.4 Replacement of Portions of Existing Build-
ings. Portions of a building envelope, heating, ventilating, air- 4.2.1 Compliance Paths
conditioning, service water heating, power, lighting, and 4.2.1.1 New Buildings. New buildings shall comply
other systems and equipment that are being replaced shall be with either the provisions of Sections 5, 6, 7, 8, 9, and 10 or
considered as alterations of existing buildings and shall com- Section 11.
ply with the standard as described in Section 4.2. 4.2.1.2 Additions to Existing Buildings. Additions to
4.1.1.5 Changes in Space Conditioning. Whenever existing buildings shall comply with either the provisions of
unconditioned or semiheated spaces in a building are con- Sections 5,6, 7, 8, 9, and 10 or Section 11.
verted to conditioned spaces, such conditioned spaces shall
Exception: When an addition to an e.x;isting building cannot
be brought into compliance with all the applicable require-
comply by itself, trade-offs will be allowed by modifica-
ments of this standard that would apply to the building enve- tion to one or more of the existing components of the
lope, heating, ventilating, air-conditioning, service water existing building. Modeling of the modified components
heating, power, lighting, and other systems and equipment of of the existing building and addition shall employ the
the space as if the building were new. procedures of Section 11; the addition shall not increase
4.1.2 Administrative Requirements. Administrative the energy consumption of the existing building plus the
requirements relating to pennit requirements, enforcement by addition beyond the energy that would be consumed by
the authority havingjurisdiction, locally adopted energy stan- the existing building plus the addition if the addition
dards, interpretations, claims of exemption, and rights of alone did comply.
appeal are specified by the authority having jurisdiction. 4.2.1.3 Alterations of Existing Buildings. Alterations
4.1.3 Alternative Materials, Methods of Construction, of existing buildings shall comply with the provisions of Sec-
or Design. The provisions of this standard are not intended to tions 5,6, 7, 8,9, and 10, provided, however, that nothing in
prevent the use of any material, method of construction, this standard shall require compliance with any provision of
design, equipment, or building system not specifically pre- this standard if such compliance will result in the increase of
scribed herein. energy consumption of the building.
4.1.4 Validity. If any tenn, P31t, provision, section, para- Exceptions:
graph, subdivision, table, chart, or referenced standard of this
standard shall be held unconstitutional, invalid, or ineffective, a. A building that has been specifically designated as
in whole or in part, such detelmination shall not be deemed to historically significant by the adopting authority or is
invalidate any remaining tenn, part, provision, section, para- listed in The National Register of Historic Places or
graph, subdivision, table, chart, or referenced standard ofthis has been detemlined to be eligible for listing by the
standard. US Secretary of the Interior need not comply with
these requirements.
4.1.5 Other Laws. The provisions of this standard shall
b. Where one or more components of an existing build-
not be deemed to nullify any provisions of local, state, or fed-
ing or portions thereof are being replaced, the annual
erallaw. Where there is a conflict between a requirement of
energy consumption of the comprehensive design
this stand31'd and such other law affecting construction of the
shall not be greater than the annual energy consump-
building, precedence shall be detennined by the authority
tion of a substantially identical design, using the same
havingjurisdiction. energy types, in which the applicable requirements of
4.1.6 Referenced Standards. The standards referenced Sections 5, 6, 7, 8, 9, and 10, as provided in Section
in this standard and listed in Section 12 shall be considered 4.2.1.3, and such compliance is verified by a design
part of the requirements of this standard to the prescribed professional, by the use of any calculation methods
extent of such reference. Where differences occur between acceptable to the authority havingjurisdiction.
a. Joints around fenestration and door frames (both manu- a. 1.0 cfrn/ft2 for glazed swinging entrance doors and
factured and site-built). revolving doors, tested at a pressure of at least 1.57
b. Junctions between walls and jloors, between walls at pounds per square foot (psf) in accordance with AAMAI
building comers, between walls and roofs or ceilings. WDMAlCSA 1011I.S.2/A440, NFRC 400, or ASTM
c. Penetrations through the air barrier in building envelope E283.
roofs, walls, andjloors. b. 0.06 cfrn/ft2 for curtainwall and storefront glazing, tested
d. Building assemblies used as ducts or plenums. at a pressure of at least 1.57 pounds per square foot (ps£)
e. Joints, seams, connections between planes, and other or higher in accordance with NFRC 400 or ASTM E283.
changes in air barrier materials. c. 0.3 cfrn/ft2 for unit skylights having condensation
weep age openings, when tested at a pressure of at
5.4.3.1.3 Acceptable Materials and Assemblies. least 1.57 pounds per square foot (pst) in accordance
Continuous air barrier materials and assemblies for the with AAMA/WDMA/CSA 101lI.S.2/A440 or NFRC
zone 3 that are less than four stories above grade and
Ventilated
less than 10,000 :ft2 in area. Unconditioned Crawlspace
Space
f. Building entrances in buildings located in climate
zone 4, 5, 6, 7, or 8 that are less than 1000 ft2 in
. . . . Exterior Envelope
area. E'·'::'·.·~;:')] Semi-Exterior Envelope
Insulation Entirely above Deck U-0.063 R-15.0 c.i. U-O.048 R-20.0 d. U-O.218 R-3.8 ci
Metal Buildinga U-O.065 R-19.0 U-O.065 R-19.0 U-O.l67 R-6.0
Attic and Other U-O.034 R-30.0 U-O.027 R-38.0 U-O.081 R-13.0
Walls, Above-Grade
Mass U-O.580 NR U-O.15l b R-5.7 c.i. b U-O.580 NR
Metal Building U-O.093 R-16.0 U-O.093 R-16.0 U-O.ll3 R-13.0
Steel-Framed U-O.124 R-13.0 U-0.124 R-13.0 U-0.352 NR
Wood-Framed and Other U-0.089 R-13.0 U-0.089 R-13.0 U-0.292 NR
Walls, Below-Grade
Below-Grade Wall C-l.140 NR C-1.140 NR C-1.140 NR
}l7oors
Mass U-0.322 NR U-0.322 NR U-0.322 NR
Steel-Joist U-0.350 NR U-0.350 NR U-0.350 NR
Wood-Framed and Other U-0.282 NR U-O.282 NR U-0.282 NR
Slab-an-Grade Floors
Unheated F-0.730 NR F-0.730 NR F-O.730 NR
Heated F-1.020 R-7.5 for 12 in. F-l.020 R-7.5 for 12 in. F-l.020 R-7.5 for 12 in.
Opaque Doors
Swinging U-0.700 U-0.700 U-0.700
Nonswinging U-1.450 U-1.450 U-1.450
Assembly Assembly Max. Assembly Assembly Max. Assembly Assembly Max.
Fenestration Max. U SHGC Max. U SHGC Max. U SHGC
Vertical Glazing,
Nonmetal framing (all)C U-1.20 U-I.20 U-1.20
Metal framing
U-1.20 U-1.20 U-1.20
(curtainwa11Jstorefront)d SHGC-0.25 all SHGC-0.25 all SHGC-NRall
Metal framing (entrance door)d U-1.20 U-1.20 U-1.20
Metal U-I.20 U-1.20 U-1.20
Skylight with Curb, Glass, % ~fRoof
00/0-2.0% U all-1.98 SHGC all-O.36 U a ll-1.98 SHGC alrO. 19 U a ll-L98 SHGCall"":NR
2.10/0-5.0%
Skylight with Curb, Plastic, % of Roof
00/0-2.0% U all-1.90 SHGC a ll-O.34 U a U-1.90 SHGCall-O.27 U all-1.90 SHGCall-NR
2.10/0-5.0%
Skylight without Curb, All, % ~f Roof
00/0-2.0% Ua U-1.36 SHGCall-O.36 U a U-1.36 SHGCa ll-O·19 U a ll-1.36 SHGCall-NR
*The following definitions apply: ci continuous insulafion (see Section 3.2), NR = no (insulation) requirement.
awlien using R-value compliance method, a thermal spacer block is required; otherwise use the U1aClor compliance method See Table A2.3.
~xception to SectionA3.L3.1 applies.
cNo1lllletal franling includes framing materials other than metal with or without metal reinforcing or cladding.
dMetal framing includes metal framing with or without thermil break. The "all other" subcategory includes operable windows, fixed windows, and non-entrance doors.
Insulation Entirely above Deck U-0.048 R-20.0 d. U-0.048 R-20.0 c.i. U-0.218 R-3.8 d.
Metal Buildinga V-0.055 R-13.0 + R-13.0 V-0.055 R-13.0 + R-13.0 U-0.097 R-1O.0
Attic and Other V-0.027 R-38.0 V-0.027 R-38.0 V-0.081 R-13.0
Walls, Above-Grade
Mass U-0.151 h R-5.7 d.b U-0.123 R-7.6 d. U-0.580 NR
Metal Building U-0.093 R-16.0 U-0.093 R-16.0 U-O.I13 R-13.0
Steel-Framed U-0.124 R-13.0 U-O.064 R-13.0 + R-7.5 U-0.124 R-13.0
c.i.
Wood-Framed and Other U-0.089 R-13.0 U-0.089 R-13.0 U-0.089 R-13.0
Walls, Below-Grade
Below-Grade Wall C-1.140 NR C-1.140 NR C-1.140 NR
Floors
Mass U-0.107 R-6.3 c.i. U-0.087 R-S.3 c.i. U-0.322 NR
Steel-loist U-0.052 R-19.0 V-0.052 R-19.0 U-0.069 R-13.0
Wood-Framed and Other U-0.051 R-19.0 U-0.033 R-30.0 U-0.066 R-13.0
SIab-On-Grade Floors
Unheated F-0.730 NR F-0.730 NR F-0.730 NR
Heated F-1.020 R-7.5 for 12 in. F-1.020 R-7.5 for 12 in. F-1.020 R-7.5 for 12 in.
Opaque Doors
Swinging U-0.700 U-0.700 U-0.700
Nonswinging U-1.450 U-0.500 U-1.450
Assembly Assembly Max. Assembly Assembly Max. Assembly Assembly Max.
Fenestration Max. V SHGC Max. V SHGC Max. V SHGC
Vertical Glazing,
Nonmetal framing (all)c U-0.75 SHGC-0.25 all V-0.75 SHGC-0.25 all U-1.20 SHGC-NRall
Metal framing U-0.70 U-0.70 U-1.20
(curtainwaUJstorefront)d
Metal framing (entrance door)d U-1.lO U-1.lO U-1.20
Metal U-0.75 U-0.75 U-1.20
Skylight with Curb. Glass, % of Roqf
00/0-2.0% Uall-1.98 SHGC all-O.36 Uall- L98 SHGCall-O.l9 U all-L98 SHGCall-NR
2.10/0-5.0%
Skylight with Curb, Plastic, % of Roqf
00/0-2.0% U all-1.90 SHGCall-O.39 U all-1.90 SHGCall-D.27 Uall-1.90 SHGCall-NR
2.10/0-5.0%
Skylight without Curb, All, % of Roof
0%-2.0% U all-1.36 SHGCall-O.36 U all-1.36 SHGCall-O.19 U all-1.36 SHGCall-NR
*The following definitions apply: ci continuous insulation (see Section 3.2), NR = no (insulation) requirement.
aWhen using R-value compliance method, a thennal spacer block is required; otherwise use the U:foctor compliance method See Table A2.3.
"Exception to SectionA3.L3.l applies.
CNonmetal framing includes framing materials olller than metal with or without metal reinforcing or cladding.
dMetal framing includes metal frannug with or without thelmal break. The "all other" subcategoty includes operable windows, fixed windows, and non-entrance doors.
Insulation Entirely above Deck U-0.048 R-20.0 c.L U-0.04& R-20.0 c.i. U-0.173 R-5.0 c.i.
Metal Buildinga U-O.055 R-13.0 + R-13.0 U-O.OSS R- 13.0 + R-13.0 U-O.097 R-IO.O
Attic and Other U-0.027 R-3&.O U-O.027 R-3&.O U-0.053 R-19.0
·Walls. Above-Grade
Mass U-O.I04 R-9.5 c.i. U-O.090 R-11.4 c.i. U-0.580 NR
Metal Building U-O.084 R-19.0 U-O.0&4 R-19.0 U-O.1l3 R-13.0
R-13.0 + R-7.5
Steel-Framed U-O.064 R-13.0 + R-7.5 d. U-0.064 U-0.124 R-13.0
c.L
R-13.0 + R-3.&
Wood-Framed and Other U-0.089 R-13.0 U-0.064 U-0.089 R-13.0
c.L
Walls, Below-Grade
Below-Grade Wall C-1.140 NR C-0.119 R-7.5 c.i. C-1.140 NR
Floors
Mass U-0.087 R-8.3 d. U-0.074 R-IOA c.i. U-OJ37 R-4.2 d.
Steel-Joist U-O.038 R-30.0 U-0.038 R-30.0 U-0.069 R-13.0
Wood-Framed and Other U-0.033 R-30.0 U-O.033 R-30.0 U-O.066 R-13.0
Slab-On-Grade Floors
Unheated F-O.730 NR F-0.540 R·IO for 24 in. F-O.730 NR
Heated F-0.&60 R-15 for 24 in. F-O.860 R-15 for 24 in. F-l.020 R-7.5 for 12 in.
Opaque Doors
Sv.inging U-O.700 U-O.700 U-0.700
Nonswinging U-O.500 U-O.500 U-1.450
Assembly Assembly Max. Assembly Assembly Max. Assembly Assembly Max.
Fenestration
Max.U SHGC Max.U SHGC Max.U SHGC
Vertical Glazing, 00/0-40% of Wall
Nonmetal framing (alit V-OAO V-OAO U-1.20
Metal framing
U-O.50 U-0.50 U-1.20
(curtainwaWstorefront)d SHGC-OAO all SHGC-OAO all SHGC-NR aU
Metal framing (entrance door)d U-0.85 V-O.85 U-1.20
Metal U-0.55 V-0.55 U-1.20
Skylight with Curb, Glass, % of Roof
0%-2.0% Uall-1.17 SHGC all-o.49 Uall-O· 98 SHGC a U-O.36 UaU-1. 98 SHGCaU-NR
2.10/0-5.0%
Skylight with Curb, Plastic, % of Roof
00/0-2.0% UaU-l.30 SHGC all-o.65 Ua n-l.30 SHGC all-O.62 Ua U-1.90 SHGCaU-NR
2.10/0-5.0%
Skylight without Curb, All, % ofRoof
00/0-2.0% U all-O·69 SHGCaU-O.49 U aU-O.58 SHGCa U-O.36 U aU-l.36 SHGCall-NR
2.10/0-5.0%
*The following definitions apply: c.i. = continuous insulation (see Section 3.2), NR = no (insulation) requirement.
8When using R-value compliance method, a thennal spacer block is required; otherwise use the U-jactor compliance method See TableA2.3.
~xception to Section A3. 1.3. 1 applies.
CNonmetal framing includes framing materials other than metal with or without metal reinforcing or cladchng.
dMetal framing includes metal framing with or without thennal break The "all other" subcategory includes operable windows, fixed windows, and non-entrance doors.
Insulation above Deck U-0.048 R-20.0 c.i. U-0.048 R-20.0 c.i. U-0.119 R-7.6 d.
Metal Buildinga U-0.055 R-13.0 + R-13.0 U-0.055 R-13.0 + R-13.0 U-0.083 R-13.0
Attic and Other U-0.027 R-38.0 U-O.027 R-38.0 U-0.053 R-19.0
Walls, Above-Grade
Mass U-0.090 R-I1A c.i. U-0.080 R-13.3 c.i. U-0.151 b R-5.7 d.b
Metal Building U-0.069 R-13.0 + R-5.6 c.i. U-0.069 R-13.0 R-5.6 c.i. U-O.I13 R-l3.0
Steel-Framed U-0.064 R-13.0 + R-7.5 d. U-0.064 R-13.0 + R-7.5 c.i. U-0.124 R-13.0
Wood-Framed and Other U-0.064 R-13.0 + R-3.8 c.i. U-0.OS1 R-13.0 + R-7.5 c.i. U-0.089 R-13.0
Walls, Below-Grade
Below-Grade Wall C-0.119 R-7.5 c.i. C-0.119 R-7.5 d. C-1.140 NR
Floors
Mass U-0.074 R-IOA c.i. U-0.064 R-12.5 c.i. U-0.l37 R-4.2 d.
Steel-Joist U-0.038 R-30.0 U-0.038 R-30.0 U-0.052 R-19.0
Wood-Framed and Other U-0.033 R-30.0 U-0.033 R-30.0 U-0.051 R-19.0
Slab-On-Grade Floors
Unheated F-0.730 NR F-0.540 R-lO for 24 in. F-0.730 NR
Heated F-O.860 R-1S for 24 in. F-0.860 R-lS for 24 in. F-1.020 R-7.5 for 12 in.
Opaque Doors
Swinging U-0.700 U-0.500 U-0.700
Nonswinging U-O.SOO U-0.500 U-1.450
Assembly Assembly Max. Assembly Assembly Max. Assembly Assembly Max.
Fenestration
Max.U SHGC Max.U SHGC Max.U SHGC
Vertical Glazing, 0%-40% of Wall
Nonmetal framing (a11)C U-0.35 U-0.35 U-1.20
Metal framing
U-OA5 U-OA5 U-1.20
(curtainwallJstorefront)d SHGC·OAO all SHGC-OAO all SHGC-NR all
Metal (entrance door)d U-0.80 U-0.80 U-1.20
Metal U-0.55 U-0.55 U-1.20
Skylight with Curb, Glass, % of Roof
00/0-2.0%
2.10/0-5.0%
Skylight with Curb, Plastic, % of Roof
00/0-2.0%
Insulation Entirely above Deck U-0.048 R-20.0 d. U-0.048 R-20.0 c.i. U-0.093 R-IO.O d.
Metal Buildinga U-0.049 R-13.0 + R-19.0 U-0.049 R-13.0 + R-19.0 u-o.on R-16.0
Attic and Other U-0.027 R-38.0 U-0.027 R-38.0 U-0.034 R-30.0
Walls, Above-Grade
Mass U-0.080 R-B.3 c.i. U-0.071 R-15.2 c.i U-0.151 b R-5.7 d. b
R-13.0 + R-5.6
Metal Building U-0.069 R-13.0 + R-5.6 d. U-0.069 U-0.1l3 R-13.0
d.
R-13.0 + R-7.5
Steel-Framed U-0.064 R-13.0 + R-7.5 c.i. U-0.064 U-0.124 R-B.O
c.i.
R-B.O + R-7.S
Wood-Framed and Other U-0.051 R-B.O + R-7.5 c.i. U-0.OS1 U-0.089 R-B.O
cj.
Walls, Belmv-Grade
Below-Grade Wall C-0.119 R-7.5 d. C-0.1l9 R-7.5 c-i. C-1.140 NR
Floors
Mass U-0.064 R-12.S d. U-0.OS7 R-14.6 d. U-0.137 R-4.2 d.
Steel-Joist U-0.038 R-30.0 U-0.032 R-38.0 U-0.052 R-19.0
Wood-Framed and Other U-0.033 R-30.0 U-0.033 R-30.0 U-0.051 R-19.0
Slab-On-Grade Floors
Unheated F-0.540 R-I0 for 24 in. F-0.520 R·15 for 24 in. F-0.730 NR
Heated F-0.860 R-15 for 24 in. F-O.688 R-20 for 48 in. F-l.020 R-7.5 for 12 in.
Opaque Doors
Swinging U-0.700 U-0.500 U-0.700
Nons\\Iinging U-0.500 U-O.SOO U-1.450
Assembly Assembly Max. Assembly Assembly Max. Assembly Assembly Max.
Fenestration
Max. V SHGC Max. V SHGC Max. V SHGC
Vertical Glazing, 0'Y0-40% of Wall
Nonmetal framing (all)C U-0.35 U-0.35 U-0.65
Metal framing
U-OA5 U-OA5 U-0.60
(curtainwaWstorefront)d SHGC-OAO all SHGC-OAO all SHGC-NRall
Metal framing (entrance door)d U-0.80 U-0.80 U-0.90
Metal U-0.55 U-0.55 U-0.65
Skylight with Curb, Glass, % of Roof
00/0-2.0% Uall-L17 SHGCall-O.49 Uall-O·98 SHGCall-O.46 Ualr1. 98 SHGCall-NR
2.10/0-S.0%
Skylight with Curb, Plastic, % of Roof
00/0-2.0% Uall-O.87 SHGCall-O·71 Uan-O.74 SHGCan-O·65 Uan-1. 9O SHGCan-NR
2.10/0-5.0%
Skylight without Curb, All, % ofRoof
00/0-2.0% Uall-O.69 SHGCall-O.49 Uall-O.58 SHGCall-OA9 UaU-1.36 SHGCan-NR
2.10/0-5.0%
*The follovving definitions apply: c.l. = continuous insulation (see Section 3.2), NR = no (insulation) requirement
aWhen using R-value compliance method, a thennal spacer block is required; otherwise use the U-factor compliance method. See Table A2.3.
b:Exception to Section A3. 1.3. 1 applies.
CNonmetal framing includes framing materials other than metal with or without metal reinforcing or cladding.
dMetal framing includes metal franung widl or without thermal break. The "all other" subcategory includes operable windows, fixed windows, and non-entrance doors.
Insulation Entirely above Deck U-0.048 R-20.0 c.i. U-O.048 R-20.0 c.i. U-O.093 R-lO.O c.i.
Metal Buildinga U-O.049 R-13.0 + R-19.0 U-O.049 R-13.0 + R-19.0 u-o.on R-16.0
Attic and Other U-0.027 R-38.0 U-0.027 R-38.0 U-0.034 R-30.0
Walls, Above-Grade
Mass U-O.071 R-15.2 c.i. U-O.07l R-15.2 c.i. U-0.123 R-7.6 c.i.
R-19.0 + R-5.6
Metal Building U-0.057 R-19.0 + R-5.6 c.i. U-O.057 U-O.ll3 R-13.0
d.
R-13.0 + R-15.6
Steel-Framed U-O.064 R-13.0 R-7.5 d. U-0.042 U-0.124 R-13.0
c.i.
R-13.0 + R-7.5
Wood-Framed and Other U-O.OSI R-13.0 + R-7.S c.L U-0.051 U-0.089 R-13.0
d.
Walls, Below-Grade
Below-Grade Wall C-O.119 R-7.5 c.L C-O.092 R-IO.O c.i. C-1.140 NR
Floors
Mass U-0.064 R-12.5 c.L U-0.051 R-16.7 c.i. U-0.I07 R-6.3 c.i.
Steel-Joist U-0.038 R-30.0 U-0.032 R-38.0 U-O.OS2 R-19.0
Wood-Framed and Other U-O.033 R-30.0 U-O.033 R-30.0 U-0.051 R-19.0
Slab-On-Grade Floors
Unheated F-0.520 R-15 for 24 in. F-O.520 R-15 for 24 in. F-0.730 NR
Heated F-0.843 R-20 for 24 in. F-0.688 R-20 for 48 in. F-0.900 R-IO for 24 in.
Opaque Doors
Swinging U-0.500 U-0.500 U-O.700
Nonswinging U-O.500 U-0.500 U-1.450
Assembly Assembly Max. Assembly Assembly Max. Assembly Assembly Max.
Fenestration
Max.U SHGC Max. V SHGC Max. V SHGC
Vertical Glazing, Orcr-40%
Nonmetal framing (al1)c U-0.35 U-O.35 U-0.65
Metal framing
U-0.40 U-0.40 U-0.60
(curtainwaWstorefront)d SHGC-0.45 all SHGC-NRall SHGC-NRall
Metal framing (entrance door)d U-O.80 U-0.80 U-0.90
Metal U-O.45 U-0.45 U-0.65
Skylight "with Curb, Glass, % of Roof
00/0-2.0% U alr1.l7 SHGCa11-0.68 Ua11-1.17 SHGCall-O·64 U a ll-1.98 SHGC a11-NR
2.10/0-5.0%
Skylight with Curb, Plastic, % of Roof
u -0.87 SHGCa 11-o.77 u a 11-0.61 SHGCa ll-0.77 U aU-1.90 SHGCaU-NR
00/0-2.0% all
2.10/0-S.0%
Skylight without Curb, All, % of Roof
00/0-2.0% U ll-0.69
a SHGC a 11-O· 68 Ua ll-O.69 SHGC all-O·64 U a 11-1.36 SHGCall-NR
2.10/0-S.0%
*The following definitions apply: c.i. = continuous insulation (see Section 3.2), NR = no (insulation) requirement
8When using R-value compliance method, a thermal spacer block is required; otherwise use the U1actor compliance method. See Table A2.3.
~xceptioll to Section A3.1.3.1 applies.
CNonmetal framing includes framing materials other than metal with or without metal reinforcing or cladding.
dMetai framing includes metal framing with or without thermal break. The "all other" subcategory includes operable windows, fixed windows, and non-entrance doors.
Insulation Entirely above Deck U-0.048 R-20.0 c.i. U-0.048 R-20.0 c.L U-0.063 R-15.0 d.
R-11.0 + R-19.0 R-l1.0 + R-19.0
Metal Buildinga U-0.035 U-0.035 U-0.065 R-19.0
Ls Ls
Attic and Other U-0.021 R-49.0 U-0.021 R-49.0 U-0.034 R-30.0
Walls, Above-Grade
Mass U-O.071 R-15.2 c.i. U-0.052 R-25.0 c.L U-0.104 R-9.5 d.
R-19.0 + R-5.6 R-19.0 + R-5.6
Metal Building U-0.057 U-0.057 U-0.113 R-13.0
c.i. c.i.
R-13.0 + R-7.5 R-I3.0 + R-18.8
Steel-Framed U-0.064 U-0.037 U-0.084 R-13.0 + R-3.8 c.i.
c.L c.i.
R-I3.0 R-15.6 R-I3.0 + R-15.6
Wood-Framed and Other U-0.036 U-0.036 U-0.089 R-13.0
c.i. d.
Walls, Below-Grade
Below-Grade Wall C-0.119 R-7.5 d. C-0.075 R-12.5 d. C-l.l40 NR
Floors
Mass U-0.057 R-14.6 d. U-0.051 R-16.7 c.i. U-0.087 R-8.3 c.i.
Steel-Joist U-0.032 R-38.0 U-0.032 R-38.0 U-0.052 R-19.0
Wood-Framed and Other U-0.033 R-30.0 U-0.033 R-30.0 U-0.033 R-30.0
Slab-On-Grade Floors
Unheated F-0.5Z0 R-15 for 24 in. F-0.510 R-ZO for 24 in. F-0.730 NR
Heated F-0.688 R-20 for 48 in. F-0.688 R-20 for 48 in. F-0.900 R-IO.O for 24 in.
Opaque Doors
Swinging U-0.500 U-0.500 U-0.700
Nonswinging U-0.500 U-0.500 U-0.500
Assembly Assembly Max. Assembly Assembly Max. Assembly Assembly Max.
Fenestration
Max.U SHGC Max.U SHGC Max.U SHGC
2.10/0-5.0%
*The following definitions apply: c.i. = continuous insulation (see Section 3.2), Ls = Liner S.vstem (See Section A 2.3.2.4), NR = no (insulation) requirement
3When using R-value compliance method, a thermal spacer block is required; othervvise use the U-jactor compliance method. See Table A2.3
i>r:xception to Section A3. 1.3.1 appli es.
CNonmetal franung includes framing materials other than metal with or without metal reinforcing or cladding.
dMetal framing includes metal framing with or without thermal break. The "all other" subcategory includes operable windows, fixed windows, and non-entrance doors
5.5.3.1 Roof Insulation. All roofs shall comply with Product Rating Program, and shall be labeled and celiified by
the insulation values specified in Tables 5.5-1 through 5.5-S. the manufacturer.
Skylight curbs shall be insulated to the level of roofs with 5.5.3.2 Above-Grade Wall Insulation. All above-
insulation entirely above deck or R-5.0, whichever is less. grade walls shall comply with the insulation values specified
5.5.3.1.1 Roof Solar Reflectance and Thermal in Tables 5.5-1 through 5.5-S. When a wall consists of both
Emittance. Roofs, in climate zones 1 through 3 shall above-grade and below-grade pOliions, the entire wall for
have one of the following: that story shall be insulated on either the exterior or the inte-
rior or be integral.
a. a minimum three-year-aged solar reflectance of 0.55
when tested in accordance with ASTM C1549 or ASTM a. If insulated on the interior, the wall shall be insulated to
E191S, and in addition, a mininmm three-year-aged ther- the above-grade wall reqiurrements.
mal emittance of 0.75 when tested in accordance with b. If insulated on the exterior or integral, the below-grade
ASTM C1371 or ASTM E408. 11mll portion shall be insulated to the below-grade wall
b. a minimum three-year-aged Solar Reflectance Index of requirements, and the above-grade wall portion shall be
64 when detennined in accordance with the Solar Reflec- insulated to the above-grade wall requirements.
tance Index method in ASTM E19S0 using a convection
coefficient of2.1 BtuJh·ft2.oF 5.5.3.3 Below-Grade Wall Insulation. Below-grade
c. increased roofinsulation levels fOlmd in Table 5.5.3.1.2. walls shall have a rated R-value of insulation no less than the
insulation values specified in Tables 5.5-1 through 5.5-S.
Exceptions: Exception: Where framing, including metal and wood
studs, is used, compliance shall be based on the maxi-
a. Ballasted roofs with a minimum stone ballast of mum assembly C-factor.
17 Ibs/ft2 or 23 Ibs/ft2 pavers.
5.5.3.4 Floor Insulation. All floors shall comply with
b. Vegetated Roof Systems that contain a minimum
thickness of2.5 in. medium and covering the insulation values specified in Tables 5.5-1 through 5.5-S.
a minimum of 75% of the roof area with durable 5.5.3.5 Slab-on-Grade Floor Insulation. All slab-on-
plantings. grade floors, including heated slab-an-grade floors and
c. Roofs, where a minimum of75% of the roofarea: unheated slab-on-gradefloors, shall comply with the insula-
tion values specified in Tables 5.5-1 through 5.5-8.
1. Is shaded during the peak sun angle on June 21 by
permanent components or features of the building, 5.5.3.6 Opaque Doors. All opaque doors shall have a
or U-factor not greater than that specified in Tables 5.5-1
2. Is covered by off-set photovoltaic arrays, building- through 5.5-S.
integrated photovoltaic arrays, or solar air or water 5.5.4 Fenestration
collectors, or
5.5.4.1 General. Compliance with U-factors andSHGC
3. Is permitted to be interpolated using a combination
of parts i and ii above. shall be demonstrated for the overall fenestration product.
Gross wall areas and gross roof areas shall be calculated sep-
d. Steep sloped roofs. arately for each space-conditioning category for the purposes
e. Low sloped metal building roofs in climate zones 2 of detennining compliance.
and 3. Exception: If there are multiple assemblies within a single
f. Roofs over ventilated attics or roofs over semi-heated class ofconstruction for a space-conditioning cate-
spaces or roofs over conditioned spaces that are not g01Y, compliance shall be based on an area-weighted
cooled spaces. average U-factor or SHGC. It is not acceptable to do an
g. Asphaltic membranes in climate zones 2 and 3. area-weighted average across multiple classes of con-
struction or multiple space-conditioning categories.
The values for three-year-aged solar reflectance and
three-year-aged thennal emittance shall be determined by a
5.5.4.2 Fenestration Area
laboratory accredited by a nationally recognized accreditation 5.5.4.2.1 Vertical Fenestration Area. TI1e total vertical
organization, such as the Cool Roof Rating COlll1cil CRRC-l fenestration area shall be less than 40% of the gross wall area.
5.5.4.4.2 SHGC of Skylights. Skylights shall have an a. the proposed building satisfies the provisions of Sections
SHGC not greater than that for "all" orientations in 5.1,5.4,5.7, and 5.8, and
Tables 5.5-1 through 5.5-8 for the appropriate total slylight b. the envelope performance factor of the proposed building
area. is less than or equal to the envelope performancefactor of
the budget building.
Exception: Skylights are exempt from SHGC requirements
provided they:
5.6.1.1 The envelope performancefactor considers only
the building envelope components.
a. Have a glazing material or diffuser with a measured
haze value greater than 90% when tested according 5.6.1.2 Schedules of operation, lighting power, equipment
to ASTM D1003. power, occupant density, and mechanical systems shall be the
b. Have a Skylight VT greater than 0.40, and; same for both the proposed building and the budget building.
c. Have all general lighting in the daylight area under 5.6.1.3 Envelope pelformancefactor shall be calculated
skylights controlled by multilevel photo controls in using the procedures of Nonnative Appendix C.
accordance with Section 9.4.1.5.
5.7 Submittals
d. For dynamic glazing, the minimum SHGC shall be
used to demonstrate compliance with this section. 5.7.1 General. The authority having jurisdiction may
Dynamic shall be considered separately require submittal of compliance documentation and supplemen-
from other vertical fenestration, and area- tal infonnation, in accordance with Section 4.2.2 of this standard.
weighted averaging with other vertical fenestra- 5.7.2 Submittal Document Labeling of Space Condi-
tion that is not dynamic glazing shall not be per- tioning Categories. For buildings that contain spaces that
mitted. will be only semiheated or unconditioned, and compliance is
sought using the "semiheated" envelope criteria, such spaces
5.5.4.5 Fenestration Orientation. The vertical fenes- shall be clearly indicated on the floor plans that are submitted
tration area shall meet the following requirement: for review.
5.7.3 Visible Transmittance. Test results required in
5.8.2.6 for skylight glazing or diffusers shall be included with
In all cases, air leakage through or around the recessed a. U-factors from Section AS.l shall be an acceptable
equipment to the conditioned space shall be limited in accor- altemative for detennining compliance with the u-
dance with Section 5.4.3. factor criteria for skylights. Where credit is being
5.8.1.7 Insulation Protection. Exterior insulation shall taken for a low-emissivity coating, the emissivity of
be covered with a protective material to prevent damage from the coating shall be determined in accordance with
sunlight, moisture, landscaping operations, equipment main- NFRC 300. Emissivity shall be verified and certi-
tenance, and wind. fied by the manufacturer.
I -- ----
6,2 - Oefinition of Compliance Paths
I
6.2 Compliance Path(s)
6.2.1 Compliance with Section 6 shall be achieved by
6,3 Simplified Approach
I 6,5
P ----
' f P Ih
rescflp Ive a
. .1.
II Section 11 - Energy Cost
Bud!=let Method
I meeting all requirements for Section 6.1, General; Section 6.7,
Submittals; Section 6.8, Minimum Equipment Efficiency; and
I 6.7 - Submittals I either:
TABLE 6.4.3.4.3 Maximum Damper Leakage, cfm per ft2 at 1.0 in. w.g.
1,2
any height 20 4 20 4
any height 20 10 20 10
4~5b,5c
TABLE 6.5.1 B Minimum Fan-Cooling Unit Size for Which an Economizer is Required
for Computer Rooms
humidified above 35°F dew-point temperature to 4. less than 600,000 Btulh of computer room cool-
comply with applicable codes or accreditation stan- ing equipment capacity is being added to an
dards. In all other buildings, where more than 25% existing building
of the air designed to be supplied by the system is to
spaces that are designed to be humidified above k. Dedicated systems for computer rooms where a mini-
35°F dew-point temperature to satisfy process mum of7S% of the design load serves:
needs. This exception does not apply to computer
1. those spaces classified as an essential facility
rooms.
2. those spaces having a mechanical cooling design
d. Systems that include a condenser heat recovery sys- of Tier IV as defined by ANSIITIA-942
tem with a minimllll capacity as defined in 6.5.6.2.2a 3. those spaces classified under NFPA 70 Article
or 6.5.6.2.2b. 708 - Critical Operations Power Systems (COPS)
4. those spaces where core clearing and settlement
e. Systems that serve residential spaces where the sys-
services are pelfomled such that their failure to
tem capacity is less than five times the requirement
settle pending financial transactions could present
listed in Table 6.S.1A.
systemic risk as described in "The Interagency
f. Systems that serve spaces whose sensible cooling Paper on Sound Practices to Strengthen the Resil-
load at design conditions, excluding transmission ience of the us Financial System, April 7, 2003"
and irifiltration loads, is less than or equal to trans-
mission and irifiltration losses at an outdoor tempera- 6.5.1.1 Air Economizers
ture of 60°F. 6.5.1.1.1 Design Capacity. Air economizer systems
g. Systems expected to operate less than 20 hours per shall be capable of modulating outdoor air and return air
week. dampers to provide up to 100% of the design supply air quan-
h. Where the use of outdoor air for cooling will affect tity as outdoor air for cooling.
supermarket open refrigerated casework systems. 6.5.1.1.2 Control Signal. Economizer danlpers shall be
i. For comfort cooling where the cooling efficiency capable of being sequenced with the mechanical cooling equip-
meets or exceeds the efficiency improvement require- ment and shall not be controlled by only mixed air temperature.
ments in Table 6.3.2. Exception: The use of mixed air temperature limit control
j. Systems primarily serving computer rooms where: shall be permitted for systems controlled from space
temperature (such as single-zone systems).
1. the total design cooling load of all computer 6.5.1.1.3 High-Limit Shutoff. All air economizers
rooms in the building is less than 3,000,000 BtuIh shal1 be capable of automatically reducing outdoor air intake
and the building in which they are located is not to the design minimum outdoor air quantity when outdoor air
served by a centralized chilled water plant, or intake will no longer reduce cooling energy usage. High-limit
2. the room total design cooling load is less than shutoff control types for specific climates shall be chosen
600,000 BtuIh and the building in which they are from Table 6.S.1.1.3A. High-limit shutoff control settings for
located is served by a centralized chilled water these control types shall be those listed in Table 6.S.1.1.3B.
plant., or 6.5.1.1.4 Dampers. Return, exhaust/relief, and out-
3. the local water authority does not allow cooling door air dampers shall meet the requirements of Section 6.4.3
towers, or Ventilation System Controls.
Fixed enthalpy
Electronic enthalpy I"ixed dry bulb
la, 2a, 3a, 4a
Differential enthalpy Differential dry bulb
uew-tJOlJllt and
Fixed dry bulb
Differential dry bulb
Fixed enthalpy
5a,6a
Electronic enthalpy a
Differential enthalpy
Dew-point and dry-bulb temperatures
8Electroruc enthalpy controllers are devices that use a combination of humidity and dry-bulb temperature in their switching algorithm.
6.5.1.1.5 Relief of Excess Outdoor Air. Systems shall b. Systems primarily serving computer rooms with dry
provide a means to relieve excess outdoor air during air econ- cooler water economizers which satisfy 100% of the
omizer operation to prevent overpressurizing the bUilding. expected system cooling load at 35°P dry bulb.
TIle relief air outlet shall be located to avoid recirculation into c. Systems where dehumidification requirements can-
the building. not be met using outdoor air temperatures of 500P
dry bulb/45°P wet bulb and where 100% of the
6.5.1.2 Water Economizers
expected system cooling load at 45°F dry bulb/400P
6.5.1.2.1 Design Capacity. Water economizer sys- wet bulb is met with evaporative water economizers.
tems shall be capable of cooling supply air by indirect evapo-
ration and providing up to 100% of the expected system 6.5.1.2.2 Maximum Pressure Drop. Precooling coils
cooling load at outdoor air temperatures of 50 0P dry bulbi and water-to-water heat exchangers used as part of a water
45°P wet bulb and below. economizer system shall either have a water-side pressure
drop of less than 15 ft of water or a secondary loop shaH be
Exceptions:
created so that the coil or heat exchanger pressure drop is not
a. Systems primarily serving computer rooms in which seen by the circulating pumps when the system is in the nor-
100% of the expected system cooling load at 40°F mal cooling (noneconomizer) mode.
dry bulb/35°P wet bulb is met with evaporative water 6.5.1.3 Integrated Economizer Control. Economizer
economizers. systems shall be integrated with the mechanical cooling sys-