1 2 3 4 5 6 7 8

A A
CMMXU1 RDRE
BLOCK HIGH_ALARM OR PHLPTOC1_OPERATE C1 TRIGGERED LED7_DR_TRIGGERED
HIGH_WARN PHIPTOC1_OPERATE C2
LOW_WARN EFLPTOC1_OPERATE B1 O C3
LOW_ALARM B2 C4
TCSSCBR1_ALARM C5
C6
C7
C8
OR6 C9
C10
VMMXU1 PHPTUV1_OPERATE B1 O C11
PHPTUV2_OPERATE B2 C12
BLOCK HIGH_ALARM PHPTUV3_OPERATE B3 C13
HIGH_WARN C14
LOW_WARN C15
LOW_ALARM C16
C17
B C18 B
C19
C20
PEMMXU1 C21
C22
RSTACM C23
C24
C25
C26
C27
C28
C29
FMMXU1 C30
C31
C32
C33
C34
C35
FLTMSTA C36
C37
BLOCK C38
C C39 C
C40
C41
C42
C43
C44
C45
C46
C47
C48
C49
C50
C51
C52
C53
C54
C55
C56
C57
C58
C59
D C60 D
C61
C62
C63
C64

E E

Main Application: MEASUREMENT, Page: 1

1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
Backup 2022 ABB Ltd. Graphical Application Configuration AA1J1Q01A1
Replacing Created by Title Document id.

Backup 2022.Power Station.MCC SWGR 235 -ES-01 / 0.4 REF615


Approved by Rev. Rel. date Lang.
Rev. Modification Rel. date Created by Based on Kv.ACB_04 REF615 0 10/2/2021 en
1/5
1 2 3 4 5 6 7 8

A CBXCBR1 A
INC_OPEN POSOPEN SELECTED
INC_CLOSE POSCLOSE EXE_OP CBXCBR_EXE_OP
ENA_OPEN EXE_CL CBXCBR_EXE_CL
ENA_CLOSE OPENPOS
BLK_OPEN CLOSEPOS
BLK_CLOSE OKPOS
AU_OPEN OPEN_ENAD
AU_CLOSE CLOSE_ENAD
ITL_BYPASS

DCSXSWI1
B INC_TEST POSOPEN OPENPOS B
INC_SERVICE POSCLOSE CLOSEPOS
OKPOS

C C

OR6 AND
CBXCBR_EXE_OP B1 O B1 O
LINEA_TRIP B2 INC_CLOSE B2
LINEB_TRIP B3 X100 (PSM).X100-PO3
INC_OPEN_PB B4

D D

E E

Main Application: CONTROL, Page: 1

1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
Backup 2022 ABB Ltd. Graphical Application Configuration AA1J1Q01A1
Replacing Created by Title Document id.

Backup 2022.Power Station.MCC SWGR 235 -ES-01 / 0.4 REF615


Approved by Rev. Rel. date Lang.
Rev. Modification Rel. date Created by Based on Kv.ACB_04 REF615 0 10/2/2021 en
2/5
1 2 3 4 5 6 7 8

TRPPTRC1_TRIP
OR6
PHLPTOC1_OPERATE B1 O PROTECTION TRIP
PHIPTOC1_OPERATE B2 TRPPTRC1
EFLPTOC1_OPERATE B3
EFHPTOC1_OPERATE B4 BLOCK TRIP
A OPERATE CL_LKOUT A
RST_LKOUT X100 (PSM).X100-PO2

TRPPTRC2_TRIP
OR6
PHPTUV1_OPERATE B1 O PHPTUV_OPERATE
PHPTUV2_OPERATE B2
PHPTUV3_OPERATE B3 TRPPTRC2
AND
BLOCK TRIP
B1 O OPERATE CL_LKOUT
B2 RST_LKOUT X100 (PSM).X100-SO2

NOT
B UNDERVOLTAGE_BYPASS IN OUT B

OR
CBXCBR_EXE_CL B1 O PHPTUV_OPERATE
INC_CLOSE_PB B2 AND6 X110 (BIO).X110-SO1
B1 O
INC_OPEN B2
INC_TEST B3

NOT
OR6 AND
PROTECTION TRIP IN OUT
C B1 O B1 O C
B2 B2
B3 X100 (PSM).X100-PO1

OR NOT
LINEA_TRIP B1 O IN OUT AND6
LINEB_TRIP B2
B1 O
B2
B3
B4

NOT
PHPTUV_OPERATE IN OUT
NOT
AND6
IN OUT
PHPTUV_OPERATE B1 O
INC_CLOSE_PB B2
D AND6 INC_SERVICE B3 D
UNDERVOLTAGE_BYPASS B4
INC_SERVICE B1 O
B2
INC_OPEN B3

AND6
DOWN_STREAM_ACB_CLOSE B1 O
INC_OPEN B2
B3

NOT
PHPTUV_OPERATE IN OUT

E E

Main Application: CONTROL, Page: 2

1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
Backup 2022 ABB Ltd. Graphical Application Configuration AA1J1Q01A1
Replacing Created by Title Document id.

Backup 2022.Power Station.MCC SWGR 235 -ES-01 / 0.4 REF615


Approved by Rev. Rel. date Lang.
Rev. Modification Rel. date Created by Based on Kv.ACB_04 REF615 0 10/2/2021 en
3/5
1 2 3 4 5 6 7 8

A INC_CLOSE LINEA_TRIP SPARE5 A


X120 (AIM).X120-Input 1 X130 (AIM).X130-Input 3 X110 (BIO).X110-Input 5

INC_OPEN LINEB_TRIP SPARE6


X120 (AIM).X120-Input 2 X130 (AIM).X130-Input 4 X110 (BIO).X110-Input 6

INC_TEST SPARE2 INC_OPEN_PB


X120 (AIM).X120-Input 3 X110 (BIO).X110-Input 1 X110 (BIO).X110-Input 7

INC_SERVICE UNDERVOLTAGE_BYPASS INC_CLOSE_PB


X120 (AIM).X120-Input 4 X110 (BIO).X110-Input 2 X110 (BIO).X110-Input 8

SPARE1 SPARE3
X130 (AIM).X130-Input 1 X110 (BIO).X110-Input 3 DOWN_STREAM_ACB_CLOSE

VT_TRIP SPARE4 X110 (BIO).X110-Input 3


B X130 (AIM).X130-Input 2 X110 (BIO).X110-Input 4 B

OR
TRPPTRC1_TRIP B1 O
B2
LEDS.Programmable LED 1
C C
TCSSCBR1_ALARM
LEDS.Programmable LED 7

PHIPTOC1_OPERATE LINEB_TRIP
LEDS.Programmable LED 2 LEDS.Programmable LED 8

PHLPTOC1_OPERATE LEDS.Programmable LED 9

LEDS.Programmable LED 3

OR
EFLPTOC1_OPERATE B1 O
B2
EFHPTOC1_OPERATE LEDS.Programmable LED 4

D D

OR6
PHPTUV1_OPERATE B1 O
PHPTUV2_OPERATE B2
PHPTUV3_OPERATE B3 LEDS.Programmable LED 5

UNDERVOLTAGE_BYPASS
LEDS.Programmable LED 6

E E

Main Application: SIGNAL, Page: 1

1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
Backup 2022 ABB Ltd. Graphical Application Configuration AA1J1Q01A1
Replacing Created by Title Document id.

Backup 2022.Power Station.MCC SWGR 235 -ES-01 / 0.4 REF615


Approved by Rev. Rel. date Lang.
Rev. Modification Rel. date Created by Based on Kv.ACB_04 REF615 0 10/2/2021 en
4/5
1 2 3 4 5 6 7 8

A PHLPTOC1 A
BLOCK OPERATE PHLPTOC1_OPERATE PHPTUV1
ENA_MULT START PHLPTOC1_START
BLOCK OPERATE PHPTUV1_OPERATE
START PHPTUV1_START

PHHPTOC1
BLOCK OPERATE PHHPTOC1_OPERATE PHPTUV2
ENA_MULT START PHHPTOC1_START
BLOCK OPERATE PHPTUV2_OPERATE
START PHPTUV2_START

PHHPTOC2
BLOCK OPERATE PHHPTOC2_OPERATE
ENA_MULT START PHHPTOC2_START PHPTUV3
B B
BLOCK OPERATE PHPTUV3_OPERATE
START PHPTUV3_START

PHIPTOC1
BLOCK OPERATE PHIPTOC1_OPERATE
ENA_MULT START PHIPTOC1_START

TCSSCBR1
BLOCK ALARM TCSSCBR1_ALARM

EFLPTOC1
C BLOCK OPERATE EFLPTOC1_OPERATE C
ENA_MULT START EFLPTOC1_START

NOT
EFLPTOC2 IN OUT

BLOCK OPERATE X100 (PSM).X100-SO1


ENA_MULT START

EFHPTOC1
BLOCK OPERATE EFHPTOC1_OPERATE
ENA_MULT START

D D

E E

Main Application: PROTECTION, Page: 1

1 2 3 4 5 6 7 8
Project Responsible department Technical reference Document kind Doc. designation
Backup 2022 ABB Ltd. Graphical Application Configuration AA1J1Q01A1
Replacing Created by Title Document id.

Backup 2022.Power Station.MCC SWGR 235 -ES-01 / 0.4 REF615


Approved by Rev. Rel. date Lang.
Rev. Modification Rel. date Created by Based on Kv.ACB_04 REF615 0 10/2/2021 en
5/5