Professional Documents
Culture Documents
IEEE Standard For Seismic Qualification Testing of Protective Relays and Auxiliaries For Nuclear Facilities
IEEE Standard For Seismic Qualification Testing of Protective Relays and Auxiliaries For Nuclear Facilities
Sponsored by the
Power System Relaying Committee
and the
Nuclear Power Engineering Committee
IEEE
3 Park Avenue IEEE Std C37.98™-2013
New York, NY 10016-5997 (Revision of
USA IEEE Std C37.98-1987)
Authorized licensed use limited to: UNIVERSIDAD DE GUANAJUATO. Downloaded on December 24,2021 at 01:25:59 UTC from IEEE Xplore. Restrictions apply.
Authorized licensed use limited to: UNIVERSIDAD DE GUANAJUATO. Downloaded on December 24,2021 at 01:25:59 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.98™-2013
(Revision of
IEEE Std C37.98-1987)
Sponsor
Authorized licensed use limited to: UNIVERSIDAD DE GUANAJUATO. Downloaded on December 24,2021 at 01:25:59 UTC from IEEE Xplore. Restrictions apply.
Abstract: The methods and conditions for seismic qualification of protective relays and auxiliaries
such as test and control switches, terminal blocks, and indicating lamps for use in nuclear
facilities are described in this standard. The primary intent of this standard is to focus on fragility
testing and seismic qualification, also known as proof testing (either to generic levels or specific
levels). This standard covers relays used in nuclear facilities, but may also be applied to any area
in which the seismic response of relays is a design consideration. The prerequisites for the
seismic test are defined in IEEE Std C37.105™.
Keywords: auxiliaries, chatter, fragility, generic testing, IEEE C37.98™, nuclear, operating basis
earthquake, proof testing, protective, qualification, relay, required response spectrum, response
spectra, safe shutdown earthquake, safety function, seismic, seismic test, test, test response
spectrum
IEEE is a registered trademark in the U.S. Patent & Trademark Office, owned by The Institute of Electrical and Electronics
Engineers, Incorporated.
Authorized licensed use limited to: UNIVERSIDAD DE GUANAJUATO. Downloaded on December 24,2021 at 01:25:59 UTC from IEEE Xplore. Restrictions apply.
Important Notices and Disclaimers Concerning IEEE Standards Documents
IEEE documents are made available for use subject to important notices and legal disclaimers. These
notices and disclaimers, or a reference to this page, appear in all standards and may be found under the
heading “Important Notice” or “Important Notices and Disclaimers Concerning IEEE Standards
Documents.”
Notice and Disclaimer of Liability Concerning the Use of IEEE Standards
Documents
IEEE Standards documents (standards, recommended practices, and guides), both full-use and trial-use, are
developed within IEEE Societies and the Standards Coordinating Committees of the IEEE Standards
Association (“IEEE-SA”) Standards Board. IEEE (“the Institute”) develops its standards through a
consensus development process, approved by the American National Standards Institute (“ANSI”), which
brings together volunteers representing varied viewpoints and interests to achieve the final product.
Volunteers are not necessarily members of the Institute and participate without compensation from IEEE.
While IEEE administers the process and establishes rules to promote fairness in the consensus development
process, IEEE does not independently evaluate, test, or verify the accuracy of any of the information or the
soundness of any judgments contained in its standards.
IEEE does not warrant or represent the accuracy or content of the material contained in its standards, and
expressly disclaims all warranties (express, implied and statutory) not included in this or any other
document relating to the standard, including, but not limited to, the warranties of: merchantability; fitness
for a particular purpose; non-infringement; and quality, accuracy, effectiveness, currency, or completeness
of material. In addition, IEEE disclaims any and all conditions relating to: results; and workmanlike effort.
IEEE standards documents are supplied “AS IS” and “WITH ALL FAULTS.”
Use of an IEEE standard is wholly voluntary. The existence of an IEEE standard does not imply that there
are no other ways to produce, test, measure, purchase, market, or provide other goods and services related
to the scope of the IEEE standard. Furthermore, the viewpoint expressed at the time a standard is approved
and issued is subject to change brought about through developments in the state of the art and comments
received from users of the standard.
In publishing and making its standards available, IEEE is not suggesting or rendering professional or other
services for, or on behalf of, any person or entity nor is IEEE undertaking to perform any duty owed by any
other person or entity to another. Any person utilizing any IEEE Standards document, should rely upon his
or her own independent judgment in the exercise of reasonable care in any given circumstances or, as
appropriate, seek the advice of a competent professional in determining the appropriateness of a given
IEEE standard.
IN NO EVENT SHALL IEEE BE LIABLE FOR ANY DIRECT, INDIRECT, INCIDENTAL, SPECIAL,
EXEMPLARY, OR CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED TO:
PROCUREMENT OF SUBSTITUTE GOODS OR SERVICES; LOSS OF USE, DATA, OR PROFITS;
OR BUSINESS INTERRUPTION) HOWEVER CAUSED AND ON ANY THEORY OF LIABILITY,
WHETHER IN CONTRACT, STRICT LIABILITY, OR TORT (INCLUDING NEGLIGENCE OR
OTHERWISE) ARISING IN ANY WAY OUT OF THE PUBLICATION, USE OF, OR RELIANCE
UPON ANY STANDARD, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE AND
REGARDLESS OF WHETHER SUCH DAMAGE WAS FORESEEABLE.
Translations
The IEEE consensus development process involves the review of documents in English only. In the event
that an IEEE standard is translated, only the English version published by IEEE should be considered the
approved IEEE standard.
Authorized licensed use limited to: UNIVERSIDAD DE GUANAJUATO. Downloaded on December 24,2021 at 01:25:59 UTC from IEEE Xplore. Restrictions apply.
Official statements
A statement, written or oral, that is not processed in accordance with the IEEE-SA Standards Board
Operations Manual shall not be considered or inferred to be the official position of IEEE or any of its
committees and shall not be considered to be, or be relied upon as, a formal position of IEEE. At lectures,
symposia, seminars, or educational courses, an individual presenting information on IEEE standards shall
make it clear that his or her views should be considered the personal views of that individual rather than the
formal position of IEEE.
Comments on standards
Comments for revision of IEEE Standards documents are welcome from any interested party, regardless of
membership affiliation with IEEE. However, IEEE does not provide consulting information or advice
pertaining to IEEE Standards documents. Suggestions for changes in documents should be in the form of a
proposed change of text, together with appropriate supporting comments. Since IEEE standards represent a
consensus of concerned interests, it is important that any responses to comments and questions also receive
the concurrence of a balance of interests. For this reason, IEEE and the members of its societies and
Standards Coordinating Committees are not able to provide an instant response to comments or questions
except in those cases where the matter has previously been addressed. For the same reason, IEEE does not
respond to interpretation requests. Any person who would like to participate in revisions to an IEEE
standard is welcome to join the relevant IEEE working group.
Users of IEEE Standards documents should consult all applicable laws and regulations. Compliance with
the provisions of any IEEE Standards document does not imply compliance to any applicable regulatory
requirements. Implementers of the standard are responsible for observing or referring to the applicable
regulatory requirements. IEEE does not, by the publication of its standards, intend to urge action that is not
in compliance with applicable laws, and these documents may not be construed as doing so.
Copyrights
IEEE draft and approved standards are copyrighted by IEEE under U.S. and international copyright laws.
They are made available by IEEE and are adopted for a wide variety of both public and private uses. These
include both use, by reference, in laws and regulations, and use in private self-regulation, standardization,
and the promotion of engineering practices and methods. By making these documents available for use and
adoption by public authorities and private users, IEEE does not waive any rights in copyright to the
documents.
Photocopies
Subject to payment of the appropriate fee, IEEE will grant users a limited, non-exclusive license to
photocopy portions of any individual standard for company or organizational internal use or individual,
non-commercial use only. To arrange for payment of licensing fees, please contact Copyright Clearance
Center, Customer Service, 222 Rosewood Drive, Danvers, MA 01923 USA; +1 978 750 8400. Permission
to photocopy portions of any individual standard for educational classroom use can also be obtained
through the Copyright Clearance Center.
Authorized licensed use limited to: UNIVERSIDAD DE GUANAJUATO. Downloaded on December 24,2021 at 01:25:59 UTC from IEEE Xplore. Restrictions apply.
Updating of IEEE Standards documents
Users of IEEE Standards documents should be aware that these documents may be superseded at any time
by the issuance of new editions or may be amended from time to time through the issuance of amendments,
corrigenda, or errata. An official IEEE document at any point in time consists of the current edition of the
document together with any amendments, corrigenda, or errata then in effect.
Every IEEE standard is subjected to review at least every ten years. When a document is more than ten
years old and has not undergone a revision process, it is reasonable to conclude that its contents, although
still of some value, do not wholly reflect the present state of the art. Users are cautioned to check to
determine that they have the latest edition of any IEEE standard.
In order to determine whether a given document is the current edition and whether it has been amended
through the issuance of amendments, corrigenda, or errata, visit the IEEE-SA Website at
http://ieeexplore.ieee.org/xpl/standards.jsp or contact IEEE at the address listed previously. For more
information about the IEEE SA or IEEE’s standards development process, visit the IEEE-SA Website at
http://standards.ieee.org.
Errata
Errata, if any, for all IEEE standards can be accessed on the IEEE-SA Website at the following URL:
http://standards.ieee.org/findstds/errata/index.html. Users are encouraged to check this URL for errata
periodically.
Patents
Attention is called to the possibility that implementation of this standard may require use of subject matter
covered by patent rights. By publication of this standard, no position is taken by the IEEE with respect to
the existence or validity of any patent rights in connection therewith. If a patent holder or patent applicant
has filed a statement of assurance via an Accepted Letter of Assurance, then the statement is listed on the
IEEE-SA Website at http://standards.ieee.org/about/sasb/patcom/patents.html. Letters of Assurance may
indicate whether the Submitter is willing or unwilling to grant licenses under patent rights without
compensation or under reasonable rates, with reasonable terms and conditions that are demonstrably free of
any unfair discrimination to applicants desiring to obtain such licenses.
Essential Patent Claims may exist for which a Letter of Assurance has not been received. The IEEE is not
responsible for identifying Essential Patent Claims for which a license may be required, for conducting
inquiries into the legal validity or scope of Patents Claims, or determining whether any licensing terms or
conditions provided in connection with submission of a Letter of Assurance, if any, or in any licensing
agreements are reasonable or non-discriminatory. Users of this standard are expressly advised that
determination of the validity of any patent rights, and the risk of infringement of such rights, is entirely
their own responsibility. Further information may be obtained from the IEEE Standards Association.
Authorized licensed use limited to: UNIVERSIDAD DE GUANAJUATO. Downloaded on December 24,2021 at 01:25:59 UTC from IEEE Xplore. Restrictions apply.
Participants
At the time this IEEE standard was completed, the Standard Seismic Testing of Relays Working Group had
the following membership:
Suresh Channarasappa, Chair
Marie Nemier, Co-chair
At the time this standard was balloted, Subcommittee 2 had the following membership:
John White, Chair
Robert Konnik, Vice Chair
Ed Mohtashemi, Secretary
*Corresponding member
This standard was completed in partnership with the IEEE Power System Relaying Committee, which had
the following membership:
Roger Hedding, Chair
Mike McDonald, Vice Chair
Pratap Mysore, Secretary
vi
Copyright © 2014 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSIDAD DE GUANAJUATO. Downloaded on December 24,2021 at 01:25:59 UTC from IEEE Xplore. Restrictions apply.
Zeeky Bukhala Gerald Johnson Mario Ranieri
John Burger Meyer Kao Roger Ray
Jeff Burnworth Bogdan Kasztenny Mike Reichard
Mark Carpenter Patrick Kerrigan Mohindar Sachdev
Patrick Carroll Mladen Kezunovic Sam Sambasivan
T. W. Cease Sungsoo Kim Miriam Sanders
Arvind Chaudhary Gary Kobet Mark Schroeder
Steve Conrad Ljubomir Kojovic Sam Sciacca
Rick Cornelison Prem Kumar Tony Seegers
Randy Crellin Steven Kunsman Don Sevcik
Randy Cunico Raluca Lascu Tarlochan Sidhu
Ratan Das Don Lukach Mark Simon
Bob Dempsey Vahid Madani Veselin Skendzic
Alla Deronja Amir Makki Kevin Stephan
Bill Dickerson Aaron Martin Bill Strang
Hyder DoCarmo Kenneth Martin Charlie Sufana
Paul Elkin Pierre Martin Mal Swanson
Everett Fennell Walter McCannon Jon Sykes
Dale Finney Mark McDonald Rick Taylor
Normann Fischer Peter McLaren John Tengdin
Ken Fodero Mike Meisinger Sudhir Thakur
Dominick Fontana Rene Midence Michael Thompson
Dale Fredrickson Dean Miller Demetrios Tziouvaras
Fred Friend George Moskos Joe Uchiyama
Rafael Garcia Chuck Mozina Eric Udren
Jon Gardell Brian Mugalian Benton Vandiver
Didier Giarratano Adi Mulawarman Mani Venkata
Harley Gilleland Mukesh Nagpal Ilia Voloh
Jim Hackett Marie Nemier Solveig Ward
Wayne Hartmann Damir Novosel Phil Waudby
Gene Henneberg Jim O’Brien Del Weers
Charlie Henville Russ Patterson Roger Whittaker
Juergen Holbach Robert Pettigrew Tom Wiedman
Stan Horowitz Arun Phadke Philip Winston
Yi Hu Bruce Pickett Murty Yalla
Rich Hunt Jeff Pond Ray Young
Chris Huntley Elmo Price Rich Young
Sinichi Imai Farnoosh Rahmatian Zhiying Zhang
Jerry Jodice Karl Zimmerman
At the time this standard was balloted, I Subcommittee, Relaying Practices, had the following membership:
Jeffrey Pond, Chair
Brian Mugalian, Co-chair
Authorized licensed use limited to: UNIVERSIDAD DE GUANAJUATO. Downloaded on December 24,2021 at 01:25:59 UTC from IEEE Xplore. Restrictions apply.
At the time this IEEE standard was balloted, the Nuclear Power Engineering Committee had the following
membership:
George A. Ballassi, Chair
James Parello, Vice Chair
Stephen A. Fleger, Secretary
Thomas Koshy, Secretary Elect
*Non-voting member
The following members of the individual balloting committee voted on this standard. Balloters may have
voted for approval, disapproval, or abstention.
William Ackerman Daryl Harmon Lorraine Padden
Ali Al Awazi Roger Hedding Mirko Palazzo
George Ballassi Hamidreza Heidarisafa James Parello
Philip Beaumont Werner Hoelzl Jan Pirrong
Kenneth Behrendt Bogdan Kasztenny Moises Ramos
Thomas Brewington Yuri Khersonsky Mario Ranieri
Daniel Brosnan Joesph L. Koepfinger Michael Roberts
Melanie Hamner Brown Thomas Koshy Fredrick Roy
Gustavo Brunello Jim Kulchisky Bartien Sayogo
Jeffrey Burnworth Chung-Yiu Lam Glen Schinzel
Nissen Burstein Raluca Lascu Nikunj Shah
Paul Cardinal Greg Luri James Smith
Robert Carruth Ahmad Mahinfallah Robert Stark
Suresh Channarasappa Michael May Gary Stoedter
Weijen Chen Daniel Mikow James Swank
Ratan Das William Moncrief John Tengdin
Robert Fletcher R. Murphy Michael Thompson
Robert Fuld Pratap Mysore Demetrios Tziouvaras
Frank Gerleve Marie Nemier Eric Udren
Mietek Glinkowski Michael Mewman John Vergis
Jalal Gohari Gary Nissen Michael Waterman
Randall Groves T. Olsen Philip Winston
Ajit Gwal Matthew Zeedyk
Authorized licensed use limited to: UNIVERSIDAD DE GUANAJUATO. Downloaded on December 24,2021 at 01:25:59 UTC from IEEE Xplore. Restrictions apply.
When the IEEE-SA Standards Board approved this standard on 11 December 2013, it had the following
membership:
John Kulick, Chair
David J. Law, Vice Chair
Richard H. Hulett, Past Chair
Konstantinos Karachalios, Secretary
*Member Emeritus
Also included are the following nonvoting IEEE-SA Standards Board liaisons:
Julie Alessi
IEEE-SA Content Publishing
Erin Spiewak
IEEE-SA Technical Community Programs
Authorized licensed use limited to: UNIVERSIDAD DE GUANAJUATO. Downloaded on December 24,2021 at 01:25:59 UTC from IEEE Xplore. Restrictions apply.
Introduction
This introduction is not part of IEEE Std C37.98™-2013, IEEE Standard for Seismic Qualification Testing of
Protective Relays and Auxiliaries for Nuclear Facilities.
This standard describes the methods and conditions for seismic qualification of protective relays and
auxiliaries such as test and control switches, terminal blocks, and indicating lamps for use in nuclear
facilities. Earlier standards had an emphasis on fragility testing of relays. The primary intent of this
standard is to focus on seismic qualification, also known as proof testing (either to generic levels or specific
levels), rather than fragility testing. This standard covers relays used in nuclear facilities, but may also be
applied to any area in which the seismic response of relays is a design consideration.
This standard is generic in nature. Required response spectra peak and ZPA levels are influenced by in-
structure response. Application-unique requirements must be considered in the testing of relays and
auxiliaries. The information presented in this standard is to be used with plant licensing basis documents
and other industry standards and requirements as applicable.
Authorized licensed use limited to: UNIVERSIDAD DE GUANAJUATO. Downloaded on December 24,2021 at 01:25:59 UTC from IEEE Xplore. Restrictions apply.
Contents
1. Overview .................................................................................................................................................... 1
1.1 Scope ................................................................................................................................................... 1
1.2 Purpose ................................................................................................................................................ 1
1.3 Use of test results ................................................................................................................................. 2
2. Normative references.................................................................................................................................. 2
3. Definitions .................................................................................................................................................. 2
7. Documentation ..........................................................................................................................................11
7.1 General ...............................................................................................................................................11
7.2 Test plan and specification .................................................................................................................11
7.3 Test report ...........................................................................................................................................12
Authorized licensed use limited to: UNIVERSIDAD DE GUANAJUATO. Downloaded on December 24,2021 at 01:25:59 UTC from IEEE Xplore. Restrictions apply.
Authorized licensed use limited to: UNIVERSIDAD DE GUANAJUATO. Downloaded on December 24,2021 at 01:25:59 UTC from IEEE Xplore. Restrictions apply.
IEEE Standard for Seismic
Qualification Testing of Protective
Relays and Auxiliaries for Nuclear
Facilities
IMPORTANT NOTICE: IEEE Standards documents are not intended to ensure safety, security, health,
or environmental protection, or ensure against interference with or from other devices or networks.
Implementers of IEEE Standards documents are responsible for determining and complying with all
appropriate safety, security, environmental, health, and interference protection practices and all
applicable laws and regulations.
This IEEE document is made available for use subject to important notices and legal disclaimers.
These notices and disclaimers appear in all publications containing this document and may
be found under the heading “Important Notice” or “Important Notices and Disclaimers
Concerning IEEE Documents.” They can also be obtained on request from IEEE or viewed at
http://standards.ieee.org/IPR/disclaimers.html.
1. Overview
1.1 Scope
This standard specifies test methods and conditions to be used in the seismic qualification testing of
protective relays and auxiliaries such as test and control switches, terminal blocks, and indicating lamps for
use in nuclear facilities.
1.2 Purpose
The purpose of this standard is to establish test methods and conditions for determining the seismic
capability and to demonstrate seismic qualification of protective relays and auxiliaries specified in
IEEE Std C37.105™-2010. The prerequisites for the qualification testing are defined in
IEEE Std C37.105™-2010. These test methods are divided into three main categories, as described in
IEEE Std 344™-2004; fragility, proof, and generic testing. To define the specific conditions for seismic
testing of protective relays, the following parameters shall be specified:
a) The settings and electrical inputs to the protective relay and auxiliaries, and other pertinent
information as detailed in this standard required to define its condition during the test
Authorized licensed use limited to: UNIVERSIDAD DE GUANAJUATO. Downloaded on December 24,2021 at 01:25:59 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.98-2013
IEEE Standard for Seismic Qualification Testing of Protective Relays and Auxiliaries for Nuclear Facilities
b) The unintentional change in state, contact chatter, deviation in operating conditions, tolerances, or
other change in performance of the relay that constitutes failure
c) The seismic levels (required response spectra) to be imposed during the test
This standard provides guidance to establish the test parameters listed above, determine seismic capacity,
and to demonstrate the ability of protective relays and auxiliaries to perform their safety function during
and/or after the specified seismic motion. In addition, this standard provides the requirements for
documenting the necessary seismic qualification of protective relays and auxiliaries.
The end user shall confirm the applicability of the test methods, conditions, and results for the intended
application of the relay.
2. Normative references
The following referenced documents are indispensable for the application of this document (i.e., they must
be understood and used, so each referenced document is cited in text and its relationship to this document is
explained). For dated references, only the edition cited applies. For undated references, the latest edition of
the referenced document (including any amendments or corrigenda) applies.
IEEE Std 323™-2003(R2008), IEEE Standard for Qualifying Class 1E Equipment for Nuclear Power
Generating Stations. 1,2
IEEE Std 344™-2004(R2010), IEEE Recommended Practice for Seismic Qualification of Class 1E
Equipment for Nuclear Power Generating Stations.
IEEE Std C37.105™-2010, IEEE Standard for Qualifying Class 1E Protective Relays and Auxiliaries for
Nuclear Power Generating Stations.
IEEE Std C37.90™-2005, Standard for Relays and Relay Systems Associated with Electric Power
Apparatus.
3. Definitions
For the purposes of this document, the following terms and definitions apply. The IEEE Standards
Dictionary Online should be consulted for terms not defined in this clause. 3
auxiliary relay: A relay whose function is to assist another relay or control device in performing a general
function by supplying supplementary actions.
1
The IEEE publications are available from the Institute of Electrical and Electronics Engineers, 445 Hoes Lane, Piscataway, NJ
08854, USA (http://standards.ieee.org/).
2
The standards or products referred to in this clause are trademarks of the Institute of Electrical and Electronics Engineers, Inc.
3
IEEE Standards Dictionary Online subscription is available at:
http://www.ieee.org/portal/innovate/products/standard/standards_dictionary.html.
4
Notes in text, tables, and figures of a standard are given for information only and do not contain requirements needed to implement
this standard.
Authorized licensed use limited to: UNIVERSIDAD DE GUANAJUATO. Downloaded on December 24,2021 at 01:25:59 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.98-2013
IEEE Standard for Seismic Qualification Testing of Protective Relays and Auxiliaries for Nuclear Facilities
NOTE 2—The operating coil or the contacts of an auxiliary relay may be used in the control circuit of another relay or
other control device. For example, an auxiliary relay may be applied to the auxiliary contact circuits of a circuit breaker
to coordinate closing and tripping control sequences.
NOTE 3—A relay may be auxiliary in its functions even though it may derive its driving energy from the power
system current or voltage; for example, a timing relay operating from current or potential transformers.
NOTE 4—Relays which, by direct response to power system input quantities, assist other relays to respond to such
quantities with greater discrimination, are not auxiliary relays; for example, fault-detector relays.
NOTE 5—Relays that are limited in function by a control circuit but are actuated primarily by system input quantities
are not auxiliary relays; for example, torque-controlled relays.
biaxial test: The relay under test is subjected to acceleration in one principal horizontal axis and the
vertical axis simultaneously.
dependent biaxial test: The horizontal and the vertical acceleration components are derived from a single-
input signal.
fragility level: The highest level of input excitation, expressed as a function of input frequency, that an
equipment can withstand and still perform the required Class 1E functions.
fragility response spectrum (FRS): A test response spectrum obtained from tests to determine the
fragility level of equipment.
independent biaxial test: The horizontal and vertical acceleration components are derived from two
different input signals that are phase incoherent.
octave: The interval between two frequencies that have a frequency ratio of two. For example, 1 Hz to 2
Hz, 2 Hz to 4 Hz, and 4 Hz to 8 Hz.
one-third octave: The interval between two frequencies that have a frequency ratio of 2 to the 1/3 power.
For example, 1 Hz to 1.26 Hz, 1.26 Hz to 1.59 Hz, and 1.59 Hz to 2.0 Hz.
operating basis earthquake (OBE): An earthquake that could reasonably be expected to occur at the plant
site during the operating life of the plant considering the regional and local geology and seismology and
specific characteristics of local subsurface material. It is that earthquake that produces the vibratory ground
motion for which those features of the nuclear power plant, necessary for continued operation without
undue risk to the health and safety of the public, are designed to remain functional.
operating time: The time interval from occurrence of specified input conditions to a specified operation.
Authorized licensed use limited to: UNIVERSIDAD DE GUANAJUATO. Downloaded on December 24,2021 at 01:25:59 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.98-2013
IEEE Standard for Seismic Qualification Testing of Protective Relays and Auxiliaries for Nuclear Facilities
protective relay: A relay whose function is to detect defective lines or apparatus or other power system
conditions of an abnormal or dangerous nature and to initiate appropriate control circuit action.
NOTE—A protective relay may be classified according to its operating principle or performance characteristics.
relay capacity level: The acceleration level in gs used to catalog the seismic capacity of the relay,
understood to refer to the required response spectra shape as defined in Annex B, Figure B.1 and not the
zero period acceleration (ZPA) of the test response spectrum.
required response spectrum (RRS): The response spectrum issued by the user or the user’s agent as part
of the specifications for proof testing, or artificially created to cover future applications. The RRS
constitutes a requirement to be met.
response spectrum (as applied to relays): A plot of the peak acceleration response of damped, single-
degree-of-freedom bodies at a damping value expressed as a percentage of critical damping of different
natural frequencies when these bodies are rigidly mounted on the surface of interest.
safe shutdown earthquake (SSE): An earthquake that is based upon an evaluation of the maximum
earthquake potential considering the local and regional geology and seismology and specific characteristics
of local subsurface material. It is that earthquake that produces the maximum vibratory ground motion for
which certain structures, systems, and components are designed to remain functional. These structures,
systems, and components are those necessary to ensure the following:
test response spectrum (TRS, as applied to relays): The acceleration response spectrum that is
constructed using analysis or derived using spectrum analysis equipment based on the actual motion of the
shake table.
transitional mode: The change from the non-operating to the operating mode, caused by switching the
input to the relay from the non-operating to the operating input, or vice versa.
triaxial test: The relay under test is subjected to simultaneous independent acceleration in three orthogonal
axes (two horizontal and one vertical).
zero period acceleration (ZPA) (ZPA as defined by IEEE 344™-2004): The acceleration level of the
high frequency, non-amplified portion of the response spectrum. This acceleration corresponds to
maximum peak acceleration of the time history used to generate the spectrum.
zero period acceleration (ZPA) (ZPA, as applied to relays): The acceleration level in gs as shown in
Annex B, Figure B.1.
4. Test preparation
All relay seismic tests shall be conducted within the operating temperature range of the relay under test.
Authorized licensed use limited to: UNIVERSIDAD DE GUANAJUATO. Downloaded on December 24,2021 at 01:25:59 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.98-2013
IEEE Standard for Seismic Qualification Testing of Protective Relays and Auxiliaries for Nuclear Facilities
The test specimens shall be randomly selected from production and shall conform to
IEEE Std C37.90™-2005 and manufacturer’s applicable standards of quality assurance and control. They
shall have all calibrated quantities recorded along with manufacturer’s product specifications and
applicable tolerances. The test sample size shall be at least three. Additional test samples beyond three may
be used to meet the contact configuration requirements in 5.2.1. For plant-specific type testing, the number
of test specimens can be reduced if appropriate justifications including common mode failures are
provided. If the samples are selected to represent a family of relays, the requirements as specified in Clause
8 shall be considered.
Reference shall be made to IEEE Std C37.105™-2010 for pre-seismic tests and evaluations when the relays
are being considered for Class 1E functions. Additional considerations for pre-seismic vibration shall be
taken into account for plant-specific non-seismic vibration tests that shall be performed before the seismic
tests.
The test specimen shall be mounted on a test fixture that duplicates the specimen’s normal mounting in
service using recommended mounting hardware. The effect of normal electrical connections shall be
considered. The test fixture must be a rigid structure to minimize amplification and spurious motion within
the frequency range of the test. A test fixture may be determined to be rigid by performing a resonance
search test and verifying that the fixture has no natural frequencies below the cutoff frequency of the
required response spectrum (RRS).
Various techniques may be used to attach the relay to the test fixture such as socket, 19 in rack, DIN rail, or
PC board. Some relays are mounted directly to another component (such as a breaker) that is being tested.
When developing the test procedure for generic qualification, consideration shall be made for relays with
various mounting methods and orientations. The worst-case mounting method shall be selected or multiple
mounting methods tested since the directional nature of the excitation input may impact the relay
performance.
4.4 Instrumentation
Sufficient instrumentation and data acquisition equipment such as accelerometers, meters, and recorders
shall provide the following:
a) Acceleration at mounting surface of relay and/or auxiliary and table. If a rigid test fixture is used,
an accelerometer is not required at the mounting surface.
b) Electrical inputs to device under test.
c) Output change of state.
d) Operating time of device under test, if applicable.
e) Test response spectrum.
Authorized licensed use limited to: UNIVERSIDAD DE GUANAJUATO. Downloaded on December 24,2021 at 01:25:59 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.98-2013
IEEE Standard for Seismic Qualification Testing of Protective Relays and Auxiliaries for Nuclear Facilities
All test equipment used to monitor the tests in 4.4.1 shall be checked and calibrated periodically in
accordance with an established quality assurance program. The accuracy of the measurements made to
monitor the parameters listed in 4.4.1 shall be as listed below. If it is noted during the evaluation that the
device under test requires a greater accuracy to assure proper operation, then the appropriate accuracy
specification shall be included in the test plan and included in the test report.
5. Test setup
All relays shall be tested in the non-operating, transition, and operating modes. The auxiliaries shall be
tested similarly in order to test all operating states, i.e., on-off, open-closed, energized-de-energized. For
each of these tests, Table 1 lists (by relay characteristic) the required relay settings and inputs. Relays with
seal-in or holding coil function shall be tested in the transition from the non-operating to operating mode as
specified in Table 1, and all other relays shall be tested in the transition from the non-operating to operating
and operating to non-operating modes. The relay shall be transitioned during strong motion of the
acceleration time history. During the seismic simulation, the relay input shall be changed to the value
specified under operating input in Table 1 and the relay operate time measured as defined in 5.2.4. The
percentage deviation from a static test of the same operating input shall be included in the documentation.
Table 1 shall be used to establish seismic test setup parameters for single protective relaying functions. For
multifunction relays, it shall be determined what minimum set of functions that will properly address all of
the seismically sensitive sub-components and/or functions of the relay, and those functions shall be tested.
For those relays it may not be necessary to exercise all of the functions listed in the table that are included
in the multifunction relay. When not testing all included functions, adequate justification shall be properly
documented. To properly address all the seismically sensitive sub-components, the tests may be combined
into a single test; in some cases, more than one test may be required. The parameters listed in Table 1 can
be modified to minimize unnecessary stress on the equipment, simulate actual applications, or other reasons
as can be justified. In such case, adequate justification shall be properly documented.
Authorized licensed use limited to: UNIVERSIDAD DE GUANAJUATO. Downloaded on December 24,2021 at 01:25:59 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.98-2013
IEEE Standard for Seismic Qualification Testing of Protective Relays and Auxiliaries for Nuclear Facilities
Authorized licensed use limited to: UNIVERSIDAD DE GUANAJUATO. Downloaded on December 24,2021 at 01:25:59 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.98-2013
IEEE Standard for Seismic Qualification Testing of Protective Relays and Auxiliaries for Nuclear Facilities
While the focus of this section is protective relays, the intent is for the user of this standard to understand
that the auxiliaries (e.g., switches, lights, etc.) downstream may have the same inputs/outputs as the
protective relays. The protective relays and auxiliaries shall operate as a system. All multi-contact relays
that can have a variation of contact formations shall be tested with a contact arrangement that is the most
severe with respect to contact chatter.
For contacts that do not have a seal-in or holding coil function, contact chatter is more likely to occur when
the monitoring voltage and load current are at the lowest acceptable limits. The sensitivity to the seismic
events is greater during these conditions since only the minimum spring and electromagnetic forces are
maintaining the contacts open or closed. Thus, for these types of contacts, loading shall be applied at the
lowest acceptable limits for voltage and/or current.
If a contact circuit between a pair of external terminals has a seal-in or holding coil function, the contact
load circuit shall be such that it draws twice rated seal-in or holding current from the source voltage. The
load shall have a series L/R ratio of 0.04 s. This load shall be applied for non-operating and operating mode
tests. The source voltage for all contact loadings shall be 125 V dc or rated, whichever is less.
If the relay uses external control power, it shall be applied during the test at 80% rated voltage or
manufacturer-specified minimum value, whichever is greater.
Relay operate time shall be the time measured from initiation of electric input to completion of 2 ms
sustained electrical output minus 2 ms. The operation is considered to have been completed when the
required contact state has been maintained for the minimum required duration. The sustained electrical
output duration may be changed if justification is provided and documented.
Any adjustments performed on a relay during a test program shall be classified into maintenance or repair.
Examples of acceptable maintenance activities during testing include calibration of the relay and retorquing
of mounting and structural fasteners. Examples of acceptable repair activities include replacing damaged
components such as sheared bolts and retightening loose electrical terminals.
Authorized licensed use limited to: UNIVERSIDAD DE GUANAJUATO. Downloaded on December 24,2021 at 01:25:59 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.98-2013
IEEE Standard for Seismic Qualification Testing of Protective Relays and Auxiliaries for Nuclear Facilities
While the preferred approach is to make no adjustments (neither maintenance nor repair) during testing,
adjustments may be performed if properly noted and documented, allowing the user to evaluate the impact
of the adjustments on their potential applications. The relay would then be “qualified with a limitation” and
adjustments and limitations shall be recorded per list item h) in 7.3.
At the completion of a testing series (whether fragility or proof), it is permissible to inspect the relay and
make adjustments to ensure the relay’s physical and functional integrity before continuing to a subsequent
series of tests. Any adjustments made shall be recorded per list item h) in 7.3.
5.3.1 Maintenance
When maintenance is performed during qualification, it shall be included in the post-earthquake field
maintenance checks and procedures for the equipment.
5.3.2 Repairs
When repairs are necessary after the operating basis earthquake (OBE) testing, the general requirement is
to retest unless justified otherwise.
When the condition requiring repair during the safe shutdown earthquake (SSE) testing meets the following
criteria, continuation without retest may be justifiable:
Does not interfere with the performance of the safety function during or after the test,
The SSE can be shown to be not cumulative due to testing in other axes,
Does not unacceptably affect equipment performance in subsequent qualification tests, such as the
loss-of-coolant accident (LOCA).
When repairs constitute a design change, the equipment must be retested, unless justified otherwise. When
repairs are made, the details shall be included in the test report per list item h) in 7.3.
Fragility testing is used to determine the ultimate capability of protective relays and auxiliaries to perform
their intended function. The fragility data will aid the user in the selection of relays for various
requirements and applications.
A fragility test shall subject protective relays and auxiliaries to one of the multi-frequency multi-axis tests
described in 8.6.3 and 8.6.6 of IEEE Std 344™-2004. Other seismic test methods described in 8.6 of IEEE
Std 344™-2004 may be used if justified. It is noted that variations in the seismic environment have been
shown to influence the fragility level.
Authorized licensed use limited to: UNIVERSIDAD DE GUANAJUATO. Downloaded on December 24,2021 at 01:25:59 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.98-2013
IEEE Standard for Seismic Qualification Testing of Protective Relays and Auxiliaries for Nuclear Facilities
The tests shall be initially conducted at a target response spectrum. An example of a target response
spectrum is provided in Annex B. The test level and frequency range shall be adjusted until operability and
structural integrity requirements of the protective relay and auxiliaries are met. The test duration shall be in
accordance with 8.6.5 of IEEE Std 344™-2004.
Fragility test data may be equivalent to seismic qualification when generic or proof test methods as detailed
in 6.2 and 6.3 are met, and provided that a minimum of five OBE tests have been conducted. The OBE test
level shall be performed at a minimum of one half of the full level.
Proof testing is used to qualify protective relays and auxiliaries for a particular requirement. A proof test
requires protective relays and auxiliaries to be subjected to one of the multi-frequency multi-axis tests
described in 8.6.3 and 8.6.6 of IEEE Std 344™-2004. Other seismic test methods described in 8.6 of IEEE
344™-2004 may be used if justified. The protective relays and auxiliaries must be subjected to the
particular response spectrum, time history, or other parameters defined for the mounting location. The test
duration shall be in accordance with 8.6.5 of IEEE Std 344™-2004.
No attempt need be made to explore the failure thresholds of the protective relays and auxiliaries.
Therefore, the proof test requires the preparation of a detailed specification. The specification is usually
written by the ultimate user as an application requirement. The protective relays and auxiliaries are tested to
the specified performance requirement and not to their ultimate capability.
Generic testing of protective relays and auxiliaries may be considered a special case of proof testing. The
test requirements of 6.2 apply. The specification is usually written to encompass most, or all, of the known
requirements. The objective is to show qualification for a wide variety of applications during one test
program. The resultant generic RRS typically encompasses a wide frequency bandwidth with relatively
high acceleration levels. The user is cautioned that the enveloping of a variety of requirements can produce
a very severe test motion.
The output change of state shall be considered failed if either (1) it is unable to transition during seismic
testing or (2) it exhibits contact chatter.
Relay contact chatter is the unauthorized intermittent closure or opening of contacts. Furthermore, relay
contact chatter is quantified as an unauthorized change of state equal to, or greater than, 2 ms unless a more
restrictive length of time (less than 2 ms) is warranted due to the component or system requirements.
Alternatively, the unauthorized operation of a defined external auxiliary device operated by the relay under
test will also be considered as a failure. Annex C provides examples on various forms of contact chatter and
guidance on the measurement of the chatter duration.
The time measuring circuit shall have a reset time of less than 200 µs to avoid integration of a number of
short pulses or a sample rate of minimum of 5000 samples/s. The time measuring circuit shall have an
Authorized licensed use limited to: UNIVERSIDAD DE GUANAJUATO. Downloaded on December 24,2021 at 01:25:59 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.98-2013
IEEE Standard for Seismic Qualification Testing of Protective Relays and Auxiliaries for Nuclear Facilities
operating point of no less than 50% of applied voltage unless a more restrictive voltage excursion limit is
warranted due to the component or system requirements.
Structural members of the protective relay and auxiliaries exhibiting any fracture damage or plastic
yielding that might cause misalignment or failure of the relay to perform its safety function shall be
classified as a test failure.
During the post-seismic test inspection, if the protective relay and auxiliary does not perform without
adjustment and within accepted tolerances defined by IEEE Std C37.105™-2010, it shall be classified as a
failure.
7. Documentation
7.1 General
The documentation for seismic qualification of protective relays and auxiliaries shall consist of a
qualification specification and a qualification report as described in 7.2 and 7.3, respectively. The
documentation shall demonstrate that the protective relay and auxiliaries are qualified to perform their
safety function when subjected to the earthquake motions.
Authorized licensed use limited to: UNIVERSIDAD DE GUANAJUATO. Downloaded on December 24,2021 at 01:25:59 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.98-2013
IEEE Standard for Seismic Qualification Testing of Protective Relays and Auxiliaries for Nuclear Facilities
a) Identification of the relays and auxiliaries being qualified including applicable safety functions.
b) Test performance specification and acceptance criteria during and after seismic testing.
c) Equipment mounting details, including all interface connections.
d) RRS levels.
e) Test method and procedures including monitoring for operability, relay electrical inputs, and
settings.
f) Test data (including proof of performance, TRS plots, time histories, PSD or Fourier analysis,
coherence checks as necessary, number of OBEs and SSEs applied, duration, etc.), type of multi-
frequency testing employed, and the acceleration time history of the input motion shall be provided
in addition to the TRS. As a minimum, a time history of the SSE table motion shall be provided for
one test in each of the three directions of excitation.
g) Test facility information including location, test equipment, and calibration.
h) Test results and conclusions, including functional test data and statement of any anomalies and
limitations.
i) Documentation including references to all drawings, bills of material, instruction manuals,
applicable QA procedures, etc., as necessary to perform an adequate review.
j) An approval signature and date.
Authorized licensed use limited to: UNIVERSIDAD DE GUANAJUATO. Downloaded on December 24,2021 at 01:25:59 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.98-2013
IEEE Standard for Seismic Qualification Testing of Protective Relays and Auxiliaries for Nuclear Facilities
Annex A
(informative)
IEC 60255-21-2-1988-10
Provides a description of the seismic test
input and method for performing a shock
type seismic test on an energized or non-
energized relay and a bump test on a non-
energized relay. The standard provides
the peak acceleration, pulse duration, and
number of pulses required for shock and
bump tests.
IEC 60255-21-3-1993-09
Provides a description of the seismic test
input and method for performing a single
axis sine sweep seismic test and a biaxial
multi-frequency random seismic test.
Authorized licensed use limited to: UNIVERSIDAD DE GUANAJUATO. Downloaded on December 24,2021 at 01:25:59 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.98-2013
IEEE Standard for Seismic Qualification Testing of Protective Relays and Auxiliaries for Nuclear Facilities
Table A.1—IEC protective relay standards relevant to IEEE Std C37.98™ (continued)
IEEE Std C37.98™ clause(s) IEC standard Comments
6.0 Test methods IEC 60255-21-3-1993-09 Part 4.3 The broad band seismic test input
The seismic test input level is based on specified is not based upon the
the severity class of the relay. severity class of the relay. The
seismic test methods defined are for
random multi-frequency seismic test
inputs only and for single frequency
seismic test inputs.
6.1 and Annex B Fragility testing IEC 60255-21-3-1993-09 Part 3.4 Standard response spectrum shape is
Standard Response Spectrum defined as follows: peak g value
(250%) from 4 Hz-16 Hz and ZPA
Standard response spectrum shape is value (100%) from 33 Hz-100+ Hz.
defined as follows: peak g value (300%) The damping value is 5% and the
from 2 Hz-~12 Hz and ZPA value starting frequency for the shape 1 Hz.
(100%) from ~22 Hz-35 Hz. The 1 Hz point is defined as 25% of the
damping value is 5% and the starting ZPA.
frequency for the shape 1 Hz. No value is
provided for 1 Hz.
6.1 and Annex B SSE and OBE, IEC 60255-21-3-1993-09 Part 5.3.1 The duration of each OBE and SSE
and the Duration of testing Time-history used for the test test shall be 30 s with a minimum of
15 s strong motion.
The time history shall have a duration of A pause between tests is not
20 s with a tolerance of ±5 s. 50% of the specified. Pause between tests should
duration of the total duration of the test be sufficient to perform required
shall be within ±10%. functional monitoring.
Authorized licensed use limited to: UNIVERSIDAD DE GUANAJUATO. Downloaded on December 24,2021 at 01:25:59 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.98-2013
IEEE Standard for Seismic Qualification Testing of Protective Relays and Auxiliaries for Nuclear Facilities
Annex B
(informative)
Fragility test
B.1 Introduction
This annex provides guidance to develop seismic test levels to conduct fragility testing. A normalized
generic broadband spectrum (Figure B.1) is provided in this annex for conducting fragility testing. The
seismic fragility test details are provided in 6.1.
The use of fragility testing data will assist in the selection of protective relays and auxiliaries. One number,
the relay capacity level, will be used to catalog the fragility of the relay. This relay capacity level (a value
expressed in gs) is understood to refer to the required response spectrum shape as defined in this standard
(see Figure B.1) and not the ZPA of the test response spectrum.
If the generic broadband RRS shape provided in this annex is used for relay testing, similar relays may be
easily compared by reviewing the relay capacity levels. The use of that data will help designers of
generating stations, substations, and various power system installations in their selection of relays to
consider for use. Note, however, that relay capacity level is an indication of fragility testing level and may
or may not represent full qualification.
To define the seismic conditions for fragility tests, a number of practical considerations should be taken
into account. One approach is to construct a spectra that is sufficiently broadband in its frequency content
that it envelopes, within practical limitations, the individual requirements for most locations. Using this
broadband spectrum it may be possible to meet most seismic requirements.
A suggested broadband normalized response spectrum is shown in Figure B.1. The broadband normalized
response spectrum is defined by four key points in Figure B.1:
It should be noted that the horizontal and vertical table input motion for the test should be equal within the
limitations of the seismic test table.
Authorized licensed use limited to: UNIVERSIDAD DE GUANAJUATO. Downloaded on December 24,2021 at 01:25:59 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.98-2013
IEEE Standard for Seismic Qualification Testing of Protective Relays and Auxiliaries for Nuclear Facilities
The range of maximum acceleration, 4.0 Hz to 16.0 Hz, has been suggested to envelop the range of peak
acceleration input to the relays by the equipment and panels on which they are mounted. Below 4.0 Hz, it is
possible to encounter building frequencies to as low as 1.5 Hz. The resulting panel motions would probably
be enveloped by the line AD since the amplification of panels at these low frequencies is small. Above
16Hz, there are equipment and panel resonances; however, the seismic energy input in this range is
generally reduced and, therefore, the motions would probably be enveloped by the line EG. The end user of
the spectrum shall ensure that the required response spectrum is modified as required to address any high
frequency components (e.g., hard rock high frequency and/or hydrodynamic loads).
The fragility test response spectrum will in all probability not have a shape that exactly matches the RRS of
Figure B.1. A relay will be assigned an acceleration ‘g’ rating based on the lower value of the horizontal or
vertical ZPA, or point G of Figure B.1, when the fragility test response spectrum has completely enveloped
the shape of Figure B.1. Figure B.2 illustrates the use of this method of seismically rating a relay. In this
example, note that the point G on the RRS defines the g rating of the relay as 2.68.
Authorized licensed use limited to: UNIVERSIDAD DE GUANAJUATO. Downloaded on December 24,2021 at 01:25:59 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.98-2013
IEEE Standard for Seismic Qualification Testing of Protective Relays and Auxiliaries for Nuclear Facilities
Figure B.2—Fitting the required response spectrum to a fragility test response spectrum
The seismic environment, both in terms of the levels and frequencies of vibration, vary from one situation
to another and from one relay mounting location to another. It is not practical to perform fragility testing
for every conceivable set of operating conditions and seismic environments. It may be possible to use the
fragility data described above in the qualification of a relay when the electrical settings, the failure criteria,
and the seismic conditions employed in fragility testing satisfy the requirements of the specific application.
When the fragility data cannot be extended or otherwise justified to be applicable, it shall be necessary to
qualify the relay using proof or generic testing for specific applications.
Authorized licensed use limited to: UNIVERSIDAD DE GUANAJUATO. Downloaded on December 24,2021 at 01:25:59 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.98-2013
IEEE Standard for Seismic Qualification Testing of Protective Relays and Auxiliaries for Nuclear Facilities
Annex C
(informative)
C.1 Introduction
Subclause 6.4.1 defines relay contact chatter as the unauthorized intermittent closure or opening of
contacts. It further quantifies that the unauthorized change of state equal to or greater than 2 ms as
constituting a failure. This annex provides examples of the various forms of contact chatter that may be
digitally recorded during seismic testing of relays and provides guidance on the measurement of the chatter
duration.
Figure C.1 shows an ideal recorded chatter of a normally closed contact. The reference wetting voltage
(Vref) would be constant until the chatter initiates and then would return to its steady state value after the
chatter event. The 2 ms contact chatter duration is readily established by measuring the delta time between
when the voltage dropped below reference voltage (Vref) to when the voltage returned to reference voltage
(Vref).
A digitally recorded relay chatter event seldom appears as the ideal signal shown in Figure C.1. Typical
relay contact chatter events recorded during seismic testing are like the traces shown in Figure C.2, Figure
C.3, and Figure C.4.
Figure C.2 shows contact chatter for a normally closed relay contact where two pulses occur. The reference
voltage drops for just less than 2 ms before it returns to the reference voltage (Vref) but then immediately
drops again for about 0.5 ms before it returns to the reference voltage (Vref). In this case, the chatter
duration is considered to be less than 2 ms since the signal returned to reference voltage (Vref) before it
dropped again. Therefore, the relay would be considered to have exhibited two independent chatter events
each less than 2 ms and therefore met the acceptance criterion.
Authorized licensed use limited to: UNIVERSIDAD DE GUANAJUATO. Downloaded on December 24,2021 at 01:25:59 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.98-2013
IEEE Standard for Seismic Qualification Testing of Protective Relays and Auxiliaries for Nuclear Facilities
Figure C.3 shows contact chatter for a normally open relay contact where three pulses occur in succession.
The signal voltage returns to Vref (which is zero volts) between each pulse. In this case, the chatter duration
is considered to be less than 2 ms since the signal returned to the reference voltage between each pulse.
Therefore, the relay would be considered to have exhibited three chatter events, each less than 2 ms and
therefore met the acceptance criterion.
Authorized licensed use limited to: UNIVERSIDAD DE GUANAJUATO. Downloaded on December 24,2021 at 01:25:59 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.98-2013
IEEE Standard for Seismic Qualification Testing of Protective Relays and Auxiliaries for Nuclear Facilities
Figure C.4 shows relay contact chatter for a normally closed contact where the chatter event recorded
begins to return to Vref after about 1.5 ms but then drops back to zero volts for an additional 1 ms. For this
example, the chatter duration is considered to be 2.5 ms. Therefore, the relay would be considered to have
exhibited chatter events greater than 2 ms and therefore did not meet the acceptance criterion.
Digital techniques are commonly used to evaluate contact chatter duration. The input to chatter detection
software requires a reference voltage be specified along with the threshold deviation from the reference
voltage to determine the onset of the chatter event. Selection of this threshold will affect the chatter
duration that is determined by the software. The threshold should allow for slight variations in the reference
voltage so that any ripple or noise component is not considered in the chatter evaluation. A conservative
value for the selection of the threshold voltage would be 10%. The digital chatter monitoring system will
start determining the chatter duration when the voltage drops 10% below reference voltage and end when
the reference voltage returns to 90% Vref. Lower threshold values may be used, but this will result in shorter
chatter duration. For example, if 50% threshold had been used in the example shown in Figure C.4, then the
chatter detection software would have reported this event as two events of less than 2 ms instead of a single
event equal to or greater than 2 ms, which is considered as a failure.
Authorized licensed use limited to: UNIVERSIDAD DE GUANAJUATO. Downloaded on December 24,2021 at 01:25:59 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.98-2013
IEEE Standard for Seismic Qualification Testing of Protective Relays and Auxiliaries for Nuclear Facilities
Annex D
(informative)
Bibliography
Bibliographical references are resources that provide additional or helpful material but do not need to be
understood or used to implement this standard. Reference to these resources is made for informational use
only.
[B1] IEC 255-21-1-1988, Electrical Relays, Part 21: Vibration, shock, bump and seismic tests on
measuring relays and protection equipment, Section One – Vibration tests (sinusoidal).
[B2] IEC 255-21-2-1988, Electrical Relays, Part 21: Vibration, shock, bump and seismic tests on
measuring relays and protection equipment, Section Two – Shock and bump tests.
[B3] IEC 255-21-3-1993, Electrical Relays, Part 21: Vibration, shock, bump and seismic tests on
measuring relays and protection equipment, Section Two – Seismic tests.
[B4] IEEE Std 627TM-2010, IEEE Standard for Qualification of Equipment Used in Nuclear Facilities.
Authorized licensed use limited to: UNIVERSIDAD DE GUANAJUATO. Downloaded on December 24,2021 at 01:25:59 UTC from IEEE Xplore. Restrictions apply.