WIND CALCULATIONS KOHLER GENERATORS 2012-03-05 风载荷
WIND CALCULATIONS KOHLER GENERATORS 2012-03-05 风载荷
qz= 0.00256*Kz*Kzt*Kd*V^2*I 56.57 PSF (4) 3/8" DIA 1 1/2" LONG ZINC COATED SET IN 4" SOLID CONCRETE
F= qz*G*Cf*Af (Eq. 6-28)
G= 0.85 PULLOUT = 3899# ULT PER TEST (ASTM E-488-96 SEE NOTE 6)
Cf= (Figure 6-21)ASCE 1.30 PULLOUT = 974# SERVICE (FS=4.0)
NOTES:
INSTALL BOLTS THROUGH UNIT BASE PER 1 LOAD COMBINATION ASD PER 2.4.1 ASCE 7-10
MANUFACTURE'S SPECIFICATIONS 0.6 x DEAD + 0.6 x WIND (ASCE 7-10; 2.4.1)
Wind Pressure 62.51 PSF 2 DESIGN IS BASED ON SECTION 29.5 OF ASCE 7-10 "OTHER STRUCTURES"
F= Wind Pressure *Af See Tables UNITS ARE TO BE LOCATED ON THE GROUND.
Af = L x H 3 ALL OTHER UNITS NOT SHOWN MUST BE DESIGNED ON A
CASE BY CASE BASIS.
4 LARGER HURRICANE PAD USED IN SOME COMBINATIONS TO SATISFY
DESIGN CHECK.
5 WIND PRESSURE ON UNITS IN ACCORDANCE WITH ASCE 7-10 FIGURE 29.5-1
GENPAD HURRICANE PAD 4" THICK 6 ANCHOR TEST DATA BASED ON ARCHITECTURAL TESTING REPORT
MODEL # WEIGHT L W NUMBER A7207.01-106-31 DATED 03/04/2011.
WIND SPEED Pressure
175.00 62.51 PSF FG3154-4K 275 54 31
FG3154-4K PAD