Fire Life Safety


Check List – Appendix (6)
Appendix – A IHG Cause & Effect Matrix

Appendix – B Fire Prevention

Appendix – C Fire & Smoke Compartmentation

Appendix – D Detection, Alarms & Notification

Appendix – E Egress, Exits & Signage

Appendix – F Emergency Power & Lighting

Appendix – G Extinguishing Systems

Appendix – H Smoke Control

Appendix – I Other Life Safety


Appendix – A [IHG Cause & Effect Matrix]

IHG FLS Check List & Report – Rev 3.1


Appendix – B [Fire Prevention]

IHG FLS Check List & Report – Rev 3.1


Appendix – C [Fire & Smoke Compartmentation]

Examples of fire
dampers & collars

IHG FLS Check List & Report – Rev 3.1


Where a fresh air duct passes over
the entry like this, the duct must
be solid metal, not flexible duct as
shown below.

Flexible duct not allowed.

Fire Dampers must be installed


either in or as close as possible to
the wall the duct passes through.
IHG FLS Check List & Report – Rev 3.1
Vestibule into emergency escape.

30min self closing


fire door.
Two 30min self closing fire
doors with door selectors.

IHG FLS Check List & Report – Rev 3.1


M&E pipe shaft doors 1.5 hr fire rated

Door Closers on all fire


Fire/Smoke Door Drop Seals
doors (non-hold open)
on Guest Room Doors

Door Coordinators for


Double Leaf Fire Doors

Fire Rated Doors


(Guest Rooms 44mm thick,
solid core, 20 min. rated)

IHG FLS Check List & Report – Rev 3.1


Good examples of Fire Stop; Putty,
Mortar and Fire Collars

IHG FLS Check List & Report – Rev 3.1


Appendix – D [Detection, Alarms & Notification]

Horn type evacuation speakers


for locations with high
ambient noise (Eg Chiller
plant room)
Guest rooms must be fitted with
Sounder Base detectors.
Sound level = 75dB at the bedhead

Evacuation speakers provided


throughout the hotel (with
back covers).
Sound level = 85dB at 3m
One in each guest room.
Fully addressable fire alarm, Small repeater (mimic) panel Sound level = 75dB at the
detection system and located in the telephone operator’s bedhead
notification system. room (or reception desk for
Holiday Inn Express)

IHG FLS Check List & Report – Rev 3.1


Strobe lights, warning bells & manual
break glass stations in public and back of
house areas

Fireman’s Phone slot can be incorporated


with the Manual Break Glass unit

IHG FLS Check List & Report – Rev 3.1


Class “A” wiring method must be used for smoke
detectors and evacuation speakers.

IHG FLS Check List & Report – Rev 3.1


Appendix – E [Egress, Exits & Signage)
Horizontal means of escape

A = 60m
Dead-ends are measured to the end of the corridor 120m in a sprinkler protected building
Fire resistant construction
Self-closing fire doors

Example of Secondary Corridor

IHG FLS Check List & Report – Rev 3.1


Examples of exits

Fire rated doors


Fire resistant construction
Self-closing doors

Rooms opening onto a protected


corridor must not be high risk such
as kitchens or rubbish stores

IHG FLS Check List & Report – Rev 3.1


2 means of escape is required from
rooms greater than 75sqm or that
caters for more than 50 people

Each exit 1m wide

Exits must be remote from each other


so that a fire will not cut-off emergency
egress (see next page for details)

Exit Exit

Exit Exit
Larger function room showing exits
remote from each other

IHG FLS Check List & Report – Rev 3.1


NFPA Extract Depicting Remote Exits

IHG FLS Check List & Report – Rev 3.1


Exit Stairwells

Exit door with push bar

Exit Stairwell Signage:


Installed inside the exit stairwell.
Good example of stairwell railing
IHG FLS Check List & Report – Rev 3.1
3 Example of correctly located exit signs

Example of exit sign pictogram

IHG FLS Check List & Report – Rev 3.1


Example of an Emergency
Evacuation Instruction Notice

Instruction notices must be on the


back of each guest room door and
in meeting rooms IHG FLS Check List & Report – Rev 3.1
Appendix – F [Emergency Power & Lighting]

Emergency generator to support all


FLS services + minimal operations. Guestrooms:
Enough fuel for 48 hours continuous 1 light in the entry connected to
operation generator power supply

Front & back of house:


Exit & Emergency lighting connected to
generator power supply and with 90 min.
battery back up (from a central battery
bank or by individual battery units)

IHG FLS Check List & Report – Rev 3.1


Appendix – G [Extinguishing Systems]

Two Main pumps plus Jockey pump


Test line goes back to the
main water tank

Sufficient sprinkler system water


Direct read, test
storage for 60 minutes continuous
flow meter
operation (unless the supply water is
combined with the hydrant system in
which case 120 minutes is required).

Main pumps

Good examples of (dual)


pressure control switches
located near the pumps

Jockey pump

IHG FLS Check List & Report – Rev 3.1


Sprinkler system

25mm test valve and 50mm flush valve


after the flow switch on each floor

Fire Hose reel, Hydrant, Extinguisher cabinets


similar to this throughout the hotel

IHG FLS Check List & Report – Rev 3.1


Typical Schematic of Fire Sprinkler protection Plant with Wet Rising Main

IHG FLS Check List & Report – Rev 3.1


Typical Schematic of Fire Sprinkler
Distribution – High Rise Sprinklers

Typical Schematic of Fire Sprinkler


Distribution – Low Rise Sprinklers

IHG FLS Check List & Report – Rev 3.1


Design Schematic of Pre-Action Dry/Wet Sprinkler System

IHG FLS Check List & Report – Rev 3.1


High temperature
sprinklers located in
Sauna room

Viking, VK501 dry pendent fast response


fusible element type sprinkler for connection to
a wet sprinkler system.
Suitable for walk-in freezers
Guestroom Sidewall Sprinklers:
Quick response and located 150mm from
the ceiling
IHG FLS Check List & Report – Rev 3.1
Linen Chute Details

IHG FLS Check List & Report – Rev 3.1


Kitchen Exhaust System Details

ANSUL type system


installed in kitchen hoods

IHG FLS Check List & Report – Rev 3.1


Appendix – H [Smoke Control] Diagrammatic Layouts of Stair
Pressurization & Corridor Smoke Control

IHG FLS Check List & Report – Rev 3.1


Atrium & Multi-Storey Lobbies

IHG FLS Check List & Report – Rev 3.1


IHG FLS Check List & Report – Rev 3.1
Appendix – I [Other Life Safety]

IHG FLS Check List & Report – Rev 3.1


Guestroom balcony secondary child
safety latch

Swimming Pool Signage

IHG FLS Check List & Report – Rev 3.1