OBSM - Mandatory Annexes - Nov 2015

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 41

NUMBER CONTENT ID

Build Journey - Base Build -> Acoustics


Annexure 70.1 Acoustic 327052
Annexure 70.2 Acoustic 327050
Annexure 70.3 Acoustic 387049

Annexure 71.1 Airborne sound insulation matrix 322331


Annexure 71.2 Airborne sound insulation matrix 322332
Annexure 71.3 Airborne sound insulation matrix 322333

Build Journey - Base Build -> Engineering Infrastructure -> Mechanical -> Design Criteria
Annexure-13.1 Public Areas temperatures 285138
Annexure-13.2 Public Areas air quality 386048
Annexure-13.3 Leisure Areas temperatures 386049
Annexure-13.4 Leisure Areas air quality 386050
Annexure-13.5 Private Guest Areas temperatures 386051
Annexure-13.6 Private Guest Areas air quality 386052
Annexure-13.7 Back Of House Areas temperatures 386053
Annexure-13.8 Back Of House Areas air quality 386054
Annexure-13.9 External Areas 386055
Annexure-13.10 General Notes 386056

Build Journey - Base Build -> Engineering Infrastructure -> Electrical -> Design Criteria
Annexure 38.1 Schedule of Essential/Critical Services Generator Loads 304095
Annexure 38.2 Schedule of Essential/Critical Services Generator Loads 304095
Annexure-39 Typical Power Loads for Hotel Areas 304135

Annexure 42.1 Electrical Services Requirements 304173


Annexure 42.2 Electrical Services Requirements 386057
Annexure 42.3 Electrical Services Requirements 386058
Annexure 42.4 Electrical Services Requirements 386059
Annexure 42.5 Electrical Services Requirements 386060

Build Journey - Base Build -> Engineering Infrastructure -> Electrical -> Lighting
Annexure 47.1 Design criteria lighting - public areas 304216
Annexure 47.2 Design criteria lighting - recreational areas 304218
Annexure 47.3 Design criteria lighting - guest areas 304217
Annexure 47.4 Design criteria lighting - back of house 304219
Annexure 47.5 Design criteria lighting - external areas 304220
Annexure 47.6 Explanatary Notes 386061
Build Journey - Base Build -> Engineering Infrastructure -> Extra Low Voltage -> Audio Visual
Annexure 78 Background Music system sound level 331151

Build Journey - Base Build -> Engineering Infrastructure -> Plumbing and Drainage -> Design Criteria
Annexure-49 Hot and Cold Water Design Criteria 305109
Annexure-50 Hot and Cold Water Design Criteria 305137
Annexure-51 Hot and Cold Water Design Criteria 305157

Build Journey - Base Build -> Engineering Infrastructure -> Vertical Transportation -> Design Criteria
Annexure 66 Design Criteria for Lifts 319156

Build Journey - Base Build -> Engineering Infrastructure -> Insulation


Annexure 73 Pipe insulation thickness (mm) hot face temperature 329082
Annexure 74 Insulation of chilled water pipe thickness 329089
Annexure 75 Insulation of Condenser water pipe pipework 329092

Build Journey - Base Build -> Engineering Infrastructure -> Labelling & Identification
Annexure 76 Pipe services identification colours must be as follows 338096
Annexure 77 Colours for Identification 338098

Build Journey - Base Build -> Engineering Infrastructure -> Mechanical -> Central Chilling Plant
Annexure 79 Water Cooled Chiller 338124
Annexure-13.1 Public Areas temperatures
Internal Conditions ± 1o C&5%RH Title Name: Annexure-13.1 Public Areas temperatures
Location Summer Winter Standard ID 285138
0 0
C db Max RH C db Min RH Your Name: Tobias Kunkel
Entrance Lobby – Seating Areas 23 60 21 30 Region: AMEA
Reception – General 23 60 21 30 Manual: Build
Cloakroom NC NC NC NC
24
Public Toilets (Note 60 20 30
9)
Gift Shop 23 60 21 30
Corridors 23 60 21 30
Restaurant 23 60 21 30
Coffee Shop 23 60 21 30

Cocktail Lounge 23 60 21 30

Ballrooms 23 60 21 30
Pre-Function Foyer 23 60 21 30
Function Room 23 60 21 30

Bar 23 60 21 30

Lounge – General 23 60 21 30

Meeting Rooms 23 60 22 30

Business Centre 23 60 21 30
Lifts - - - -
Stairwells 24 NC 18 NC
Annexure-13.2 Public Areas air quality
Fresh Air Quantity Title Name: Annexure-13.2 Public Areas air quality
Minimum
(notes 6 and 13) Standard ID 386048
Pressurizat NR Filtration
Location
ion Rating Standard to
EN779:2012 Your Name: Tobias Kunkel

Entrance Lobby – Seating


5% Positive - 35 F6 Region: AMEA
Areas

Reception – General 5% Positive 1.0 l/s/m2 35 F6 Manual: Build


Cloakroom Negative Note 7 35 No Filtration
10%
Public Toilets Negative, Note 8 35 G5
max 15 pa
Gift Shop 5% Positive 1.6 l/s/m2 40 F6
Corridors 5% Positive 1 AC/hr. 35 G5
Restaurant 5% positive 8.5 l/s/m2 35 F6
Coffee Shop 5% positive 8.5 l/s/m2 40 F6
5%
Cocktail Lounge Negative 10.0 l/s/person 35 F6
(Note 6)
Ballrooms 5% Positive 15 l/s/m2 40 F8
Pre-Function Foyer 5% positive 11.0 l/s/m² 40 F8
Function Room 5% Positive 20 l/s/m2 40 F8

5%
Bar 10.0 l/s/person 40 F6
Negative

Lounge – General 5% positive 10.0 l/s/person 35 F6


30
Meeting Rooms 5% positive 10.0 l/s/person F6
(Note 4)
Business Centre Neutral 1.6 l/s/m2 35 F6
Lifts - - - -
Stairwells - - 35 -
Annexure-13.3 Leisure Areas temperatures
o
Internal Conditions ± 1 C&5%RH Title Name: Annexure-13.3 Leisure Areas temperatures

Summer Winter Standard ID 386049


Location
0 0
C db Max RH C db Min RH Your Name: Tobias Kunkel

Fitness Rooms 18 60 18 30 Region: AMEA

Health Club – Reception 23 60 21 30 Manual: Build


Health Club – Food &
23 60 21 30
Beverage areas

Health Club – Changing 24 NC 24 NC

Massage/Solarium/
27 60 27 30
Sauna/Jacuzzi

31 31
Indoor Swimming Pool 60 65
(Note 3) (Note 3)
Annexure-13.4 Leisure Areas air quality
Fresh Air Quantity Title Name: Annexure-13.4 Leisure Areas air quality
Minimum
Pressurizati (notes 6 and 13) Filtration Standard ID 386050
Location NR Rating
on Standard to
EN779:2012 Your Name: Tobias Kunkel

Fitness Rooms 5% Negative 4.2 l/s/m2 40 F6 Region: AMEA

Health Club – Reception 5% Positive 0.8l/s/m2 40 F6 Manual: Build


Health Club – Food & 2
5% Negative 1.6 l/s/m 40 F6
Beverage areas
10%
Health Club – Changing Negative, 10 Ac/hr. 40 F6
max 15 Pa
Massage/Solarium/
Neutral 8.0 l/s /person 35 F6
Sauna/Jacuzzi
5%
15 l/s per m2
Indoor Swimming Pool Negative, of wet area 40 G3
max 15 pa
Annexure-13.5 Private Guest Areas temperatures
Internal Conditions ± 1o C&5%RH Title Name: Annexure-13.5 Private Guest Areas temperatures
Summer Winter Standard ID 386051
Location
0 0
C db Max RH C db Min RH Your Name: Tobias Kunkel

Bedrooms – Region: AMEA


Activity Areas 23 60 22 30
Day/Night Manual: Build

Bathrooms –
- - - -
Bath Areas

Club Lounge 23 60 22 30

Corridors 23 60 21 30
Annexure-13.6 Private Guest Areas air quality

Fresh Air Quantity Minimum Title Name: Annexure-13.6 Private Guest Areas air quality
(notes 6 and 13) Filtration Standard ID 386052
Location Pressurization NR Rating Standard to
EN779:201
2 Your Name: Tobias Kunkel

Bedrooms – Region: AMEA


25 (night)
Activity Areas Positive 25 l/s Note 10 F6
30 (days)
Day/Night
Manual: Build

Bathrooms –
Negative Note 11 - -
Bath Areas

Club Lounge Neutral 6.5 l/s/m2 30 F6

Corridors Neutral - 30 -
Annexure-13.7 Back Of House Areas temperatures
Internal Conditions ± 1o C&5%RH Title Name: Annexure-13.7 Back Of House Areas temperatures
Location Summer Winter Standard ID 386053
0 0
C db Max RH C db Min RH Your Name: Tobias Kunkel
Laundry Max 30 NC 16 NC Region: AMEA
Housekeeping/linen 25 NC 18 NC Manual: Build
27
Kitchen (General) NC 18 NC
(Note 9)
21
Kitchen (Pastry) NC 18 NC
(Note 9)
20
Kitchen (Prep/Finish) NC 18 NC
(Note 9)

White Wine and


5 NC 5 NC
Beer Store

25
Staff Dining NC 21 NC
(Note 9)
25
Staff Kitchen NC 18 NC
(Note 9)
25
Staff Changing NC 23 NC
(Note 9)
Corridors 25 NC 18 NC

24
Offices 60 22 30
(Note 9)
25
Workshops NC 20 NC
(Note 9)
8
Plant Rooms 30 max NC -
(min)
Computer Room/IT 23
60 20 30
Equipment (Note 5)
Lift Motor Rooms 28 max NC 16 min NC

Refuse area 24 max NC 18 NC


Annexure-13.8 Back Of House Areas air quality
Fresh Air Minimum
Title Name: Annexure-13.8 Back Of House Areas air quality
Quantity Filtration
Location Pressurization NR Rating
Standard to
(notes 6 and 13) EN779:2012 Standard ID 386054

Laundry Negative Note 1 45 G3 Your Name: Tobias Kunkel


Housekeeping/lin
Positive 1 l/s/m² 40 F6 Region: AMEA
en
Kitchen
Negative 45 G3 Manual: Build
(General)
1.6l/s/m²
Kitchen (Pastry) Negative min 45 G3
(Note 2)
Kitchen
Negative 45 G3
(Prep/Finish)
White Wine and
- - - -
Beer Store
Staff Dining Positive 10 l/s/m2 40 F6
10AC/hr.
Staff Kitchen Negative 45 G3
(Note 2)
Staff Changing Negative 10AC/hr. 40 F6

Corridors Neutral - 30 F6

Offices 5% positive 1.0 l/s/m2 35 F6

1.6 l/s/m2
Workshops Negative (Note 14)
45 G3

Plant Rooms Negative (Note 12) 65 -


Computer
Room/IT 5% Positive 1 Ac/hr. 45 F8
Equipment

Lift Motor Rooms Negative (Note 12) 45 -

Refuse area Negative 6AC/HR 40 G3


Annexure-13.9 External Areas
Temperatures
Internal Conditions ± 1o C&5%RH Title Name: Annexure-13.9 External Areas
Location Summer Winter Standard ID 386055
0 0
C db Max RH C db Min RH Your Name: Tobias Kunkel

Covered /Underground Car


- - - - Region: AMEA
Parking
Manual: Build
Air quality
Fresh Air
Minimum
Quantity
Pressurizati Filtration
Location NR Rating
on (notes 6 Standard to
and 13) EN779:2012

Covered /Underground Car 6 AC/Hr


Negative 55 -
Parking (Note 15)
Annexure-13.10 General Notes
1
10 air changes/hour or sized to dissipate heat and moisture from equipment if details are available. Title Name: Annexure-13.10 External Areas
Air change rate should depend on kitchen equipment heat output and on extract volume from canopies.
2
A minimum face velocity must be provided to each canopy, refer to the kitchen section of this Standard ID 386056
document. Use of proprietary hoods with UV filtration can reduce this.
3
Pool hall internal temperature should be designed 1°C above maximum pool water temperature. Your Name: Tobias Kunkel
4 Cross talk attenuators and any services penetrations to/from meeting rooms and guest bedrooms must
provide 50dB sound reduction through the wall, floor or roof.
Region: AMEA
Computer and IT/Telephone rooms should be provided with supplementary “split” under floor ducted air
5
conditioning systems with standby power supply, in the event that the main air conditioning system Manual: Build
fails.
Electrostatic smoke filters and negative pressure are required in the re-circulation system from Lounge
6
and Bar areas when smoking is permitted. Fresh air rates are maximums when smoking is not
permitted unless local regulations require higher rates.
7
Extract only from cloakroom with makeup from foyer, sized on 1 air change/hour
Toilet extract must be sized on 10 airchange/hour, with make-up via the toilet lobby, supplied from the
8
nearest supply air system. Extract fans must be dual fans. In “Hot climates” make up air must be
cooled and in ‘Cold Climates’ heated if the air is directly from outside e.g. pool toilets.
Ventilation to these areas should be designed to maintain internal air temperature below 25°C for 95%
9
of the year, if possible without a cooling system. If a cooling system is required the internal design
temperature should be 24°C.
Ventilation rates to be based on 8-12 l/s per guest, final figure to balance the exhaust rate. The
10 maximum number of guests per room to be utilized hence: Standard rooms, Club room, Queen, King
allow 2 persons. Allergy/disabled allow 1 person. Queen Sofa, King Sofa and Double allow 4 persons.
Supply of fresh air shall be pre-conditioned.
11 Extract volume from guest bathroom shall be minimum of 90% of the supply air volume to the
guestroom, and a minimum of 6 Ac/hr., but preferably balanced with the fresh air.
Ventilation rates to be selected to achieve the maximum summer temperature requirement. Fans to be
12
controlled from a local thermostat. Natural ventilation is an acceptable alternative if suitable control can
be demonstrated.
The fresh air quantities indicated for public spaces are the maximum to be allowed for calculations and
13
equipment selection. The actual fresh air quantity is to be controlled via air quality sensors, to maintain
a maximum CO2 level in the occupied space of 600ppm.
14 Opening windows are an acceptable alternative to mechanical ventilation in suitable climates. Exhaust
systems should be provided for processes such as welding, carpentry, painting.
Car parks requiring mechanical ventilation shall be extracted to prevent the spread of fumes to
15 adjoining spaces. Systems shall be controlled by air quality sensors (CO and N0x) to reduce energy
consumption (with override by Life Safety Controls). Ventilation rate in fire/smoke control mode to meet
local regulations.
Annexure 38.1 Schedule of Essential/Critical Services Generator Loads

Essential component
Description of load Load classification Title Name: Annexure 38.1 Schedule of Essential/Critical Services Generator Loads
(%)

Stair and exit signs 50 E Standard ID: 304095


Generator room 100 E Your Name: Tobias Kunkel
Guest room vestibule light 100 C Region: AMEA
Switchgear rooms 100 C Manual: Build
Engineer’s office 50 C
Telephone switchboard room 100 C
Service area 20 C
General Manager’s office 1 light only C
Department Head’s offices 1 light only C
Walk-in fridges/freezers and cold
100 C
Lighting

rooms including refrigeration plant


Main plant rooms 20 C
Reception 50 C
Security office 100 C
Elevator machine rooms 20 C
Guest room corridors 20 C
Public areas 20 C
Elevator car lighting 100 C
Kitchens 50 C
IT Rooms 50 C
Health Club 50 C
Disabled guest bedrooms 100 C

Notes to table:
E: Essential Load (Life Safety)
C: Critical Load (Hotel Operation)
O: Other designated load (desirable for operation)
Annexure 38.2 Schedule of Essential/Critical Services Generator Loads

Essential component
Description of load Load classification Title Name: Annexure 38.2 Schedule of Essential/Critical Services Generator Loads
(%)

Life safety systems 100 E Standard ID: 304095


Security system 100 C Your Name: Tobias Kunkel
Sump pumps 100 C Region: AMEA
Sewage pumps 100 C Manual: Build
Kitchen hood extract fans 100 C
Computer equipment not connected
100 C
via UPS
Computer & Telephone Room Air
100 C
Conditioning
Point of sale terminals not connected
100 C
via UPS
UPS System 100 C
Fire pumps 100 E
Smoke control/staircase
100 E
pressurization fans
Aircraft warning lights 100 E
Sewage disposal plant & pumps 100 C
Computer and Telephone Room Air
100 C
Conditioning
Cold Water Pressure Pumps 100 C
Air compressors for pneumatic
100 C
controls (if applicable)
PA System 100 E
Selected elevator for Fire Fighting
1 only E
were provided
Telephone system 100 C
Generator fuel pumps 100 E
Kitchen Equipment 30 C
Refrigeration Cold Rooms 100 C
Cold Water Pressure Pumps 100 C
Annexure‐‐ 39 Typical Power Loads for Hotel Areas
LPD(w/m2)
Area Power (w/m2) W/m2 (max) Title Name: Annexure‐39 Typical Power Loads for Hotel Areas
(Ashrae 90.1)
Ballroom 14 46 60 Standard ID: 304135
Exhibition 14 66 80 Your Name: Tobias Kunkel
Assembly 14 36 50 Region: AMEA
Main Entrance Lobby 11.8 28.2 40 Manual: Build
Lobby 14 16 30
Guest Room 11.8 23.2 35
Restaurants 14 61 75
Meeting Rooms 14 26 40
Coffee Shop 15.1 34.9 50
Lounge 12.9 17.1 30
Night Club 14 16 30
Bar 15.1 14.9 30
Public Corridors 11.8 8.2 20
Guest Corridors 5.4 14.6 20
Service Corridors 5.4 4.6 10
Foyer 6.5 28.5 35
Front Desk 12.9 37.1 50
Offices 11.8 28.2 40
Kitchen 12.9 107.1 120
Laundry Work Area 6.5 123.5 130
Valet 9 121 130
Housekeeping Area 8.6 16.4 25
Work Shop 20.5 4.5 25
Service rooms 16.1 8.9 25
Machine Rooms 16.1 8.9 25
Employees Lockers 6.5 8.5 15
Storage 8.6 1.4 10
Concessionary Outlets 18.3 141.7 160
Telephone switchboard
16.1 13.9 30
room
Public Toilets 9.7 5.3 15
Figures exclude heating/air conditioning from central plant
Power demand for different area may vary according to case.
Annexure 42.1 Electrical Services Requirements
Electrical services by area Title Name: Annexure 42.1 Electrical Services Requirements
Light switching Power for Standard ID: 304173
Emergency
Location Loose equipment
Local Manual Auto lighting Your Name: Tobias Kunkel
remote & general
Public Areas,
Day/night + 4 Channel
Lift Lobbies/     Region: AMEA
Dimming
Reception
Day/night + Dimming to
Restaurant     Manual: Build
suit interiors
Day/night + Dimming to
Bar    
suit interiors
Day/night + 4 Channel
Lounge    
Dimming
Meeting Inc. flush
rooms &   Dimming+ Lighting control  floor boxes at
Foyer desks
Ballrooms,
Banqueting
Inc. flush
room, Lecture
  Dimming  floor boxes at
Theaters &
desks
exhibition
area
Health club
Inc. flush
reception / dry   Dimming 
floor boxes
areas
Health club IP44 or IP65
  Dimming 
wet/change as needed
Health club IP44 or IP65
  Dimming 
activity areas as needed
Shops   Day/night + Dimming  
Business
  Dimming++ Lighting control  
centre
Offices    
 PIR
Public
  control for
Restrooms
urinals
Annexure 42.2 Electrical Services Requirements
Electrical services by area Title Name: Annexure 42.2 Electrical Services Requirements
Light switching Power for Standard ID: 386057
Emergency equipment
Location Loose
Local Manual Auto lighting & general Your Name: Tobias Kunkel
remote
cleaning
BOH General     Region: AMEA
 Flex
IP65 connections
Laundry   Manual: Build
lights to
equipment
Insectocut
or fixed
Kitchen/Food  Easy
  equipment
preparation area clean
with IP54
isolators
Staff
Dining/Change    
room
Circulation    50% night 
Linen/
   
Housekeeping

Service/Delivery    

 Refer  Refer std


Guest rooms  
std layout layout
 Day/night + Lighting
Corridors   
control
 Three
Workshops   
phase
 Three
Plant rooms   
phase
 Escape/
 Three
External   Timer control Access
phase
Routes
 Escape/
Control rooms  Dimming Access 
Routes
Annexure 42.3 Electrical Services Requirements
Electrical services by area Title Name: Annexure 42.3 Electrical Services Requirements
Special PA, music &
finishes for speech with
Telephone TV power
Location switch Data outlets CCTV local Standard ID: 386058
outlets & aerial
plates & on/off/auto
outlets control
Public
Areas, Lift +
  wireless hotspot    Your Name: Tobias Kunkel
Lobbies/ Payphones
Reception
Restaurant    wireless hotspot   Region: AMEA
Bar       Manual: Build
Lounge   
Meeting
rooms &    wireless hotspot   
Foyer
Ballrooms,
Banqueting
room,
Lecture    wireless hotspot   
Theaters &
exhibition
area
Health club
reception /     
dry areas
Health club
 
wet/change
Health club
activity     
areas
Shops   
Business
 + fax    
centre
Offices  
Public

Restrooms
Annexure 42.4 Electrical Services Requirements
Electrical services by area Title Name: Annexure 42.4 Electrical Services Requirements
Special PA, music &
finishes for speech with
Telephone TV power
Location switch Data outlets CCTV local Standard ID: 386059
outlets & aerial
plates & on/off/auto
outlets control
BOH
    Your Name: Tobias Kunkel
General
Laundry  Region: AMEA
Kitchen /
Food
 Manual: Build
preparation
area
Staff
+1
Dining/Cha 
payphone
nge room
Circulation 
Linen/
Housekeepi 
ng
Service /
 
Delivery
Guest 
   
rooms wired or hard
Corridors  
Workshops   

Plant rooms   
External 
Control
  
rooms
Annexure 42.5 Electrical Services Requirements
Electrical services by area Title Name: Annexure 42.5 Electrical Services Requirements
Fire Alarm
Panic Alarm/
Location & POS Standard ID: 386060
Disabled Alarm
Detection
Public Areas, Lift Lobbies/ Reception    Your Name: Tobias Kunkel
Restaurant   Region: AMEA
Bar   Manual: Build
Lounge 
Meeting rooms & Foyer 
Ballrooms, Banqueting room, Lecture

Theaters & exhibition area
Health club reception / dry areas   
Health club wet/change  
Health club activity areas  
Shops 
Business centre 
Offices 
Public Restrooms  
BOH General 
Laundry 
Kitchen/Food preparation area  Cooking
Staff Dining/Change room 
Circulation 
Linen/ Housekeeping 
Service/Delivery 
 Flashing
 Disabled Bar
Guest rooms light
rooms only Fridge
disabled
Corridors 
Workshops 
Plant rooms 
External 
Control rooms 
Annexure 47.1  design criteria lighting ‐ public areas Title Name: Annexure 47.1  design criteria lighting ‐ public areas
Maintained
Working
Area Location Illuminance Fitting type Standard ID: 304216
Plane
(LUX)
Entrance Lobby – Seating Areas 100-400 Floor level LE/LED/F Your Name: Tobias Kunkel
Reception – General 300-400 Floor Level CF/F/LED*# Region: AMEA
1000mm
Reception – Registration Desk 400-600 LE/LED/F Manual: Build
above floor
1000mm
Reception – Working Areas 300-400 LE/LED/F
above floor
500mm above
Cloakroom 200 F/CF/LED*#
floor
500mm above
Public Toilets 200 LE/F
floor
500mm above
Gift Shop 500 CF/LED/CC*#
floor
Corridors 150 Floor level LE/LED/F
Restaurant 100-500 Table top LE/LED/F
Coffee Shop 200 Table top CF/LED*#
Public Areas

Cocktail Lounge 50-400 Table top CF/LED/CC*#


Ballrooms 200-400 Table top CF/HID/CC*#
Pre-Function Foyer 200 Floor level CF/LED/CC*#
Function Room 200-500 Table top CF/LED/HID/CC*#
Bar 200-400 Table top LE/LED/F
Housekeeping 150 Floor level LE/F
Lounge – General 100-400 Floor level F/CF
Table top –
Lounge – Function Areas 50-400 LE
dimmed
Table top –
Meeting Rooms 500 LE/LED/F
dimmed
Min day 150
Stairwells-accommodation Floor level DLE/LED
Min night 100
Stairwells-escape 100 Floor level LE/F
Table top -
Business Centre 200/500 CF/LED/HID/CC
dimmed
Lifts 100 Floor level LE/F
Stairwells 300 Floor level F/CF
Annexure 47.2  design criteria lighting ‐ recreational areas Title Name: Annexure 47.2  design criteria lighting ‐ recreational areas
Maintained
Working
Area Location Illuminance Fitting type Standard ID: 304218
Plane
(LUX)
1000mm
Health Club - Recreational 300 CF/F Your Name: Tobias Kunkel
above floor
Fitness Facility – General 300 Floor level LE/F Region: AMEA
Recreation Areas

Health Club – Reception 200 Table top LE/F Manual: Build


Health Club – Food & Beverage
200 Table top CF/LED*#
areas
Health Club – Changing 200 Floor level LE/F
Fitness Rooms 300 Floor level LE/F
Massage / Solarium / Sauna / 100mm above
200 CF/F/LED
Jacuzzi floor
Indoor Swimming Pool 300 Pool Deck MW/MH
Annexure 47.3  design criteria lighting ‐ guest areas
Maintained
Working
Area Location Illuminance Fitting type Title Name: Annexure 47.3  design criteria lighting ‐ guest areas
Plane
(LUX)
Bedrooms – General 150-200 Floor level DLE/LED Standard ID: 304217
Beside table
Bedrooms – Sleeping area 300 DLE/LED Your Name: Tobias Kunkel
top
Bedrooms – Desk area 400 Table top DLE/LED Region: AMEA
Bedrooms – Activity areas 300 Table top DLE/LED Manual: Build
Guest Areas

Bedrooms – TV/drawer unit 250 Table top DLE/LED


Low
Bathrooms – General 150 Floor level
energy/decorative

Bathrooms – bath area 200 1m above floor Low energy

Bathrooms – vanity areas 400 Vanity unit top Low energy


Min day 150
Corridors Floor level DLE/LED
Min night 100
Annexure 47.4  design criteria lighting ‐ back of house
Maintained
Working
Area Location Illuminance Fitting type Title Name: Annexure 47.4  design criteria lighting ‐ back of house
Plane
(LUX)
1000m above
Offices 300-400 LE/F Standard ID: 304219
floor
Laundry 300-500 Floor level F Covered Your Name: Tobias Kunkel
Housekeeping/linen 300 Floor level F Covered Region: AMEA
Kitchen general 500 Work surfaces F Covered Manual: Build
Back of House Areas

Kitchen pastry 500 Work surfaces F

Kitchen prep/finish 500 Work surfaces F

White Wine and Beer Store 200 Work surfaces F


Staff Dining 300 Table top CF/LED/F
Staff Kitchen 500 Work surfaces F Covered
Staff Changing 200 Floor level CF/F/LED
1000m above
Workshops 500 F
floor
1000m above
Plant Rooms 300 F
floor
Annexure 47.5  design criteria lighting ‐ external areas
Maintained
Working
Area Location Illuminance Fitting type Title Name: Annexure 47.5  Schedule of Lighting Levels and Fitting Types
Plane
(LUX)

50-200 max at
External Areas

corners/ non-
Pathways/Parking Ground Level HID Standard ID: 304220
circulation
space

Covered/Underground Parking 100 Ground Level F Your Name: Tobias Kunkel

Outdoor Pools 100 Pool Deck MH/HID Region: AMEA


Manual: Build
Annexure 47.6 Notes to tables
* Includes chandeliers, wall brackets, etc, decorative effect lighting.
# Subject to special lighting effects/local decorative lighting. Title Name: Annexure 47.6 Notes to tables
I Incandescent  ID: 386061
F Fluorescent Your Name: Tobias Kunkel
CF Compact Fluorescent Energy Saving Lamp Region: AMEA
HID High Intensity Discharge (High pressure sodium, metal halide, etc). Manual: Build
CC Cold Cathode
LED Light Emitting Diode
MV Mercury Vapour
LV Low Voltage/Halogen

All compact fluorescent (CF) and fluorescent (F) should be colour temperature 2700 K
instant on and a colour rendition of equal to or greater than 85 with a lumen output
Note 1:
retention of no less than 80% of rated operating hours. All guestroom CF bulbs must be
dimmable.

Note 2: To convert Lux to Ft. Candles, divide the Lux by a factor of 10.
Annexure-49 Hot and Cold Water Design Criteria Title Name: Annexure-49 Hot and Cold Water Design Criteria.
Pressure
Service Storage Shower Flow Rate Standard ID: 305109, 305137, 305157
Range *

410 liters/guest / day w/o laundry Your Name: Tobias Kunkel


560 liters/ Guest /day with laundry 5.5bar max Region: AMEA
900 liters/guest /day with all facilities
1.5bar min
Cold Water

Manual: Build
in tropical climate
9.4 liter per
Restaurant: 35 liters/cover minute
Maintain below 20°C to prevent
SWA: 4bar min
Legionella

23°C in tanks for UAE

30 liters / guest room/ day


Restaurant: 14 liters/cover 5.5bar max
Kitchen & Laundry: Based on
equipment at higher temperature
Hot Water

1.5bar min
(60‐70°C) with two hours minimum 9.4 liter per
recovery. minute
Minimum return temperature 55°C SWA: 4bar min

Anti‐scald fittings on washbasins to


limit hot water
supply temperature to 41°C

* Pressure requirements typically based on shower requirements.


All rooms and all services to have same/balanced pressure.
Annexure 66 Design Criteria for Lifts Title Name: Annexure 66 Design Criteria for Lifts
Guest Lift Guest Lift Guest Lift Service Lift Goods Lift Standard ID: 319156, 322081, 335205

Full service
HI Express Resort Your Name: Tobias Kunkel
Hotel
Speeds Region: AMEA
Levels 2-3
1.25 mps 1.25 mps 1.25 mps 1.25 mps 1.25 mps Manual: Build
served
Levels 4-12
1.75 mps 1.75 mps 1.75 mps 1.75 mps 1.75 mps
served
Levels 13-22
2.5 mps 2.5 mps 2.5 mps 2.5 mps N/A
served
Levels 23-32
4.5 mps 4.0 mps 4.0 mps 4.0 mps N/A
served

Levels 33 + 5+ mps 5+ mps 5+ mps 5+ mps N/A

Door

Width 1100 mm 1100 mm 1100 mm 1200 mm 2200 mm

Height 2100 mm 2100 mm 2100 mm 2100 mm 2100 mm

Type Centre Open Centre Open Centre Open Centre Open Vertical Bi-part

Compensation
Manufacturer
1.25 mps 1.25 mps 1.25 mps All duties All duties
’s Standard
Whisperflex 2.5 mps 2.5 mps 2.5 mps - -

Rope 3.5 mps 3.5 mps 3.5 mps - -

Lockdown +4 mps +4 mps +4 mps - -


Annexure 70.1 Acoustic Title Name: Room Information
Maximum internal noise levels Specification ID: 327052

Location External noise Services noise Your Name: Tobias Kunkel

Public spaces 40 dB LAeq NR 35 Region: AMEA

Guestrooms – nighttime 27 dB LAeq, 45 dB LAmax NR 25 Manual: Build

Guestrooms – daytime 32 dB LAeq NR 25 Brand IC and ICR

Meeting facility 35 dB LAeq, 50 dB LAmax NR 30

Leisure and fitness 40 dB LAeq NR 40


Annexure 70.2 Acoustic Title Name: Room Information
Maximum internal noise levels Standard ID: 327050

Location External noise Services noise Your Name: Tobias Kunkel

Public spaces 42 dB LAeq NR 37 Region: AMEA

Guestrooms – nighttime 32 dB LAeq, 47 dB LAmax NR 27 Manual: Build

Guestrooms – daytime 35 dB LAeq NR 27 Brand all other brands (excl IC, ICR and HIEX)

Meeting facility 37 dB LAeq, 50 dB LAmax NR 32

Leisure and fitness 42 dB LAeq NR 40


Annexure 70.3 Acoustic Title Name: Room Information
Maximum internal noise levels Standard ID: 387049

Location External noise Services noise Your Name: Tobias Kunkel

Public spaces 45 dB LAeq NR 40 Region: AMEA

Guestrooms – nighttime 35 dB LAeq, 50 dB LAmax NR 30 Manual: Build

Guestrooms – daytime 40 dB LAeq NR 30 Brand HIEX only

Meeting facility 40 dB LAeq, 50 dB LAmax NR 35

Leisure and fitness 45 dB LAeq NR 40


Annexure 71.1 Airborne sound insulation matrix Title Name: Annexure 71.1 Airborne sound insulation matrix
Guestroom Corridor Corridor (+door) Public areas Standard ID: 322331
Guestroom 50 dB DnT,w + Ctr 50 dB DnT,w 40 dB DnT,w 50 dB DnT,w Your Name: Tobias Kunkel
Corridor 50 dB DnT,w N/a N/a 50 dB DnT,w Region: AMEA
Corridor
40 dB DnT,w N/a N/a 50 dB Rw Manual: Build
(+door)
Public areas 50 dB DnT,w 50 dB DnT,w 50 dB Rw N/a Brand IC ICR
Meetings /
50 dB DnT,w + Ctr 50 dB DnT,w 50 dB Rw 50 dB DnT,w
Conference
Bar /
Restaurant /
Banquet / 60 dB DnT,w + Ctr 60 dB DnT,w 40 dB DnT,w N/a
Leisure
facility
Back of
55 dB DnT,w + Ctr 50 dB DnT,w 40 dB DnT,w 50 dB DnT,w
house

Bar /
Restaurant /
Meetings / Conference Banquet / Back of house
Leisure
facility
60 dB DnT,w +
Guestroom 50 dB DnT,w + Ctr
Ctr
55 dB DnT,w + Ctr
60 dB DnT,w +
Corridor 50 dB DnT,w 50 dB DnT,w
Ctr
Corridor
50 dB Rw 40 dB DnT,w 40 dB DnT,w
(+door)
Public areas 50 dB DnT,w N/a 50 dB DnT,w
Meetings / 60 dB DnT,w +
50 dB DnT,w + Ctr 55 dB DnT,w + Ctr
Conference Ctr
Bar /
Restaurant /
60 dB DnT,w +
Banquet / 60 dB DnT,w + Ctr
Ctr
55 dB DnT,w
Leisure
facility
Back of
55 dB DnT,w + Ctr 55 dB DnT,w N/a
house
Annexure 71.2 Airborne sound insulation matrix Title Name: Annexure 71.2 Airborne sound insulation matrix
Guestroom Corridor Corridor (+door) Public areas Standard ID: 322332
Guestroom 45 dB DnT,w + Ctr 45 dB DnT,w 35 dB DnT,w 45 dB DnT,w Your Name: Tobias Kunkel
Corridor 45 dB DnT,w N/a N/a 45 dB DnT,w Region: AMEA
Corridor
35 dB DnT,w N/a N/a 45 dB Rw Manual: Build
(+door)
Public areas 45 dB DnT,w 45 dB DnT,w 45 dB Rw N/a Brand all brands except IC ICR and HIEX
Meetings /
45 dB DnT,w + Ctr 45 dB DnT,w 45 dB Rw 45 dB DnT,w
Conference
Bar /
Restaurant /
Banquet / 55 dB DnT,w + Ctr 55 dB DnT,w 35 dB DnT,w N/a
Leisure
facility
Back of
50 dB DnT,w + Ctr 45 dB DnT,w 35 dB DnT,w 45 dB DnT,w
house

Bar /
Restaurant /
Meetings / Conference Banquet / Back of house
Leisure
facility
55 dB DnT,w +
Guestroom 45 dB DnT,w + Ctr 50 dB DnT,w + Ctr
Ctr
55 dB DnT,w +
Corridor 45 dB DnT,w
Ctr
45 dB DnT,w
Corridor
45 dB Rw 35 dB DnT,w 35 dB DnT,w
(+door)
Public areas 45 dB DnT,w N/a 45 dB DnT,w
Meetings / 55 dB DnT,w +
45 dB DnT,w + Ctr 50 dB DnT,w + Ctr
Conference Ctr
Bar /
Restaurant /
55 dB DnT,w +
Banquet / 55 dB DnT,w + Ctr 50 dB DnT,w
Ctr
Leisure
facility
Back of
50 dB DnT,w + Ctr 50 dB DnT,w N/a
house
Annexure 71.3 Airborne sound insulation matrix Title Name: Annexure 71.3 Airborne sound insulation matrix
Guestroom Corridor Corridor (+door) Public areas Standard ID: 322333
Guestroom 40 dB DnT,w + Ctr 40 dB DnT,w 30 dB DnT,w 40 dB DnT,w Your Name: Tobias Kunkel
Corridor 40 dB DnT,w N/a N/a 40 dB DnT,w Region: AMEA
Corridor
30 dB DnT,w N/a N/a 40 dB Rw Manual: Build
(+door)
Public areas 40 dB DnT,w 40 dB DnT,w 40 dB Rw N/a Brand HIEX
Meetings /
40 dB DnT,w + Ctr 40 dB DnT,w 40 dB Rw 40 dB DnT,w
Conference
Bar /
Restaurant /
Banquet / 50 dB DnT,w + Ctr 50 dB DnT,w 30 dB DnT,w N/a
Leisure
facility
Back of
45 dB DnT,w + Ctr 40 dB DnT,w 30 dB DnT,w 40 dB DnT,w
house

Bar /
Restaurant /
Meetings / Conference Banquet / Back of house
Leisure
facility
50 dB DnT,w +
Guestroom 40 dB DnT,w + Ctr 45 dB DnT,w + Ctr
Ctr
50 dB DnT,w +
Corridor 40 dB DnT,w 40 dB DnT,w
Ctr
Corridor
40 dB Rw 30 dB DnT,w 30 dB DnT,w
(+door)
Public areas 40 dB DnT,w N/a 40 dB DnT,w
Meetings / 50 dB DnT,w +
40 dB DnT,w + Ctr 45 dB DnT,w + Ctr
Conference Ctr
Bar /
Restaurant /
50 dB DnT,w +
Banquet / 50 dB DnT,w + Ctr 45 dB DnT,w
Ctr
Leisure
facility
Back of
45 dB DnT,w + Ctr 45 dB DnT,w N/a
house
Annexure 73 Pipe insulation thickness (mm) hot face temperature Title Name: Annexure 73 Pipe insulation thickness (mm) hot face temperature
PIPE OD SERVICE (mm)
PIPE BORE Hot water 800°C Standard ID: 329082
thickness

15 21 30 Your Name: Tobias Kunkel

20 27 30 Region: AMEA

25 34 40 Manual: Build

32 42 40

40 48 40

50 60 40

65 76 50

80 89 50

100 114 50
Annexure 74 Insulation of chilled water pipe thickness Title Name: Annexure 74 Insulation of chilled water pipe thickness
OD pipe (mm) intallation Insulation thickness Standard ID: 329089
21 30 Your Name: Tobias Kunkel
27 30 Region: AMEA
34 40 Manual: Build
42 40
48 40
60 40
76 50
89 50
Over 89mm and including
40
flat surfaces
Annexure 75 Insulation of Condenser water pipe pipework Title Name: Annexure 75 Insulation of Condenser water pipe pipework
OD pipe (mm) installation Insulation thickness Standard ID: 329092
21 20 Your Name: Tobias Kunkel
27 20 Region: AMEA
34 20 Manual: Build
42 20

48 20

60 20

76 25

89 25
Annexure 76 Pipe services identification colours must be as follows Title Name: Annexure 76 Pipe services identification colours must be as follows
Service Basic Colour Colour Bands Standard ID: 338096
1 Fuel Oil : Diesel Brown White Your Name: Tobias Kunkel
2 Hydraulic Oil Brown Salmon Pink Region: AMEA
3 Transformer Oil Brown Crimson Manual: Build
4 Lubricating Oil Brown Emerald Green
5 Natural Gas Yello Other Yellow
6 Electrical Orange …..
7 Antifreeze
BSM Coolant Green Violet
8 Drinking Water Green Auxialiary Blue
9 Heating > 100°C Green Crimson/Blue/Crimson
10 Heating < 100°C Green Blue/Crimson/Blue
11 Pump Cooling Water Green White
12 Hot Water Green
13 Drinking Water Green Blue
14 Cold Water Green
15 Rain Water Black
16 Electrical Neutral Black
17 Earthing Black
18 Fire alarm Red
Annexure 77 Colours for Identification Title Name: Annexure 77 Colours for Identification
White 00E55 Salmon Pink 04C33 Standard ID: 338098
Black 00E53 Emerald Green 14E53 Your Name: Tobias Kunkel
Light Blue 20E51 Crimson 04D45 Region: AMEA
Orange 06E51 Yellow Ochre 08C35 Manual: Build
Green 12D45 Auxiliary Blue 18E53
Violet 22C37 Brown 06C39
Yellow 10E53 Silver Grey 10A03
Red 04E53 Grey 10A07
Annexure 78 Background Music system sound level Title Name: Annexure 78 Background Music system sound level
1 Restaurants SPL 92dB Standard ID: 331151
2 High Level Bars SPL 111 dB Your Name: Tobias Kunkel
3 Medium Level Bars SPL 101dB Region: AMEA
4 Club Lounge SPL 93dB Manual: Build
5 SPA Relaxation Zones SPL 94dB

6 GYM and fitness facilities SPL 89dB

7 Movement Studio SPL 89dB

8 Treatment rooms SPL 89dB


Annexure 79 Water Cooled Chiller Title Name: Annexure 79 Water Cooled Chiller
1 Below 500 TR screw chiller (In/out temperature 14/ 7 deg C) Standard ID 338124
COP- 5.8 Your Name: Tobias Kunkel
IPLV- 0.5 Region: AMEA
NPLV- 0.52 Manual: Build
SPLV -0.65 (Includes chiller, chilled water pump, condenser water pump
brands all brands
and cooling tower fans)
2 Below 500 TR centrifugal chiller (In/out temperature 14/ 7 deg C)
COP- 6.3
IPLV- 0.35
NPLV- 0.37
SPLV -0.57 (Includes chiller, chilled water pump, condenser water pump
and cooling tower fans)
3 Above 500 TR centrifugal chiller (In/out temperature 14/ 7 deg C)
COP- 6.35
IPLV- 0.345
NPLV- 0.365
SPLV -0.55 (Includes chiller, chilled water pump, condenser water pump
and cooling tower fans)