In-Line Releasing Device

Installation Instructions

Effective: September 2010


S/N 70000309
DESCRIPTION PROCEDURE
The In-Line Releasing Device, P/N 70101338, is used to 1. The In-Line Releasing Device is polarity-sensitive
make a single-or dual-solenoid releasing circuit power and must be connected as shown in Figure 2 for a
limited. See Figure 1. single-solenoid circuit or as shown in Figure No. 3
for a dual-solenoid circuit.
2. The red lead of the In-Line Releasing Device must
be connected to the field wiring from Terminal 1 of
the releasing circuit. The black lead must be con-
Figure 1. In-Line Releasing Device nected to the control head or solenoid valve.
3. Use wire nuts to connect the In-Line Releasing
Device to field wiring and leads from control heads
SUPPLIED PARTS
and solenoid valves.
• In-Line Releasing Device, P/N 70101338

REQUIRED TOOLS
• No. 2 Flat-Head Screwdriver
• Small Flat-Head Screwdriver

Red Black Control Head for Agent Storage


Red Container
1
or
2 In-Line Releasing Device Black Solenoid Valve for Sprinkler
System
3
4

Release- or Combo-
Circuit Terminals

JUNCTION BOX
(enlarged for clarity)

Note:
Junction box for In-Line Releasing Device must be close nippled to control head or enclosure for solenoid valve.

Figure 2. Single-Control-Head or Solenoid Releasing Circuit


Release-Circuit
Terminals
Red Black Control Head for Agent Storage
Red Container
1
or
2 In-Line Releasing Device Black Solenoid Valve for Sprinkler
System
3
4
Red Black

In-Line Releasing Device


.

Control Head for Agent Storage


Red Container
JUNCTION BOX or
(enlarged for clarity) Black Solenoid Valve for Sprinkler
System

Note:
Junction box for In-Line Releasing Device must be close nippled
to control head or enclosure for solenoid valve.

Use separate junction boxes when control heads or solenoid


valves are remote from each other.

Figure 2. Dual-Control-Head or Solenoid Releasing Circuit

These instructions do not purport to cover all the details or variations in the equipment
described, nor do they provide for every possible contingency to be met in connection with
installation, operation and maintenance. All specifications are subject to change without
notice. Should further information be desired or should particular questions arise which are
not covered sufficiently for the purchaser’s purposes, the matter should be referred to 4801 Southwick Drive, 3rd Floor
CHEMETRON Fire Systems, Matteson, IL 60443. Telephone: (708) 748-1503. Matteson, IL 60443
Ph: 708-748-1503
S/N 70000309 Rev AA © 2010 Chemetron. Printed in USA Fax: 708-748-2847