Setting the Pressure Indication to Zero

using the Pfister Handheld PHT


this presentation is a standard procedure to set the pressure compensation
to zero without carrying out a complete calibration
the shown steps are examples only and may vary for each individual plant
if the prehopper is depressurized and the indication of the
pressure influence is not exactly on zero
here is how to zero the indication without carrying out
a complete new calibration
the load cell of the pressure compensation is located
on top of the prehopper
to set the pressure compensation to zero
the following preconditions are required

> pressure in the system must be zero

> equipment is not running

> blower must be shut off

> equipment is in local mode


Pfister Handheld PHT

PHT = Pfister Handheld Terminal


link the PHT to the CSC controller or to the LCB

PHT connection at the


CSC controller -X17
PHT connection at the
LCB

LCB = Local Control Box


Pfister-Terminal
899.430.63.00
when the PHT is connected wait until
Vers. 1.2
Ctrl Y > Connect
Ctrl Y > Connect
is being displayed then press key Ctrl
Y to establish communication
if the PHT is connected to the LCB
HAUPTMENU CPI1 press key arrow down until
3 CPI -> Server
Operational 3 CPI -> Server
is being displayed

then press key Enter


to get into the CSC menu

if the PHT is connected to the CSC


skip this page
CSC MAIN MENU
the PHT now will show one
of the main menu lines
X xxxxxx
if not press Ctrl A to get there
CSC MAIN MENU press key arrow down until
7 Configuration
7 Configuration
is being diplayed

press key Enter


CONFIGURATION
18.10.2005 11:32
the PHT now will show
1 Syst-Parameter 1 Syst-Parameter

press key Enter


SYSTEM SETTINGS
Entry free
the PHT now will show
<. . . . . . . . . . . . . no Entry free

press key Enter


SYSTEM SETTINGS
Entry free
press key arrow down
<. . . . . . . . . . . . . yes to change to yes

press key Enter


CONFIGURATION
18.10.2005 12:45 press key 0 to go up one directory
1 Syst-Parameter

1 Syst-Parameter
is being displayed now
CONFIGURATION
press key arrow down until
18.10.2005 12:45 9 Pressure comp.
9 Pressure comp.
is being displayed

press key Enter


MEAS. PARAMET. CP
press key arrow down until line
>> Zero setting
>> Zero setting
is being displayed

press key Enter


at this point the pressure in the prehopper must be

!!! ZERO !!!


indication of the current load of the
+ 0,0276 t pressure compensation load cell
Set to zero
Keys -> Cr,1,C>
display will show
+ 0,0276 t Set to zero
Set to zero
Keys -> Cr,1,C>

press keys Enter 1 Enter


to set the pressure indication to zero
the pressure indication will now indicate
+ 0,0000 t 0,0000 t
Set to zero
Keys -> Cr,1,C>

press key Ctrl A to leave this menu


ZEROING THE INDICATION OF THE PRESSURE INFLUENCE
DONE