Specifications
The new inverter stations of the Bosch Power Tec BPT-IS series are complete systems for large PV sys-
tems. The stations, made up of central inverters of the Bosch Power Tec BPT-C series, high-power
medium voltage transformers and the BPT-M Touch monitoring system, achieve a system effectiveness
of over 98 %.
Ready-for-connection comprehensive system tive”. The entire inverter stations are design approved
The new BPT-IS 400–1200 inverter stations are pre- and comply in dimension and layout with the European
assembled complete solutions, available in the power standard requirements.
classes 400 kVA to 1.2 MVA. They have been developed
especially for the quick and error-free planning and Long maintenance intervals
installation of large-scale PV power plants and contain Bosch Power Tec inverter stations significantly reduce
Bosch Power Tec BPT-C series central inverters and a planning, transport and assembly costs. Besides the
highly efficient medium voltage transformer. An optional medium voltage connection, only the solar generator, a
medium voltage switch gear can be integrated ex works. remote transmission line for the data telecommunication
All connection and ventilation devices as well as the and any given optional components have to be con-
monitoring system are pre-installed and tested ex works. nected. Moreover, the integrated ventilation system has
This allows an on-site plug & play installation. generous air flow and filter volume reserves, which allow
very long maintenance intervals.
Future-proof
The Bosch Power Tec inverter stations allow the opera- Flexibility
tors of PV plants a high return throughout the entire For project-specific adaptations the inverter stations can
service life. The central inverters of the Bosch Power Tec be equipped with various optional equipment ex works.
BPT-C series comply with all European legal norms and For example, dry type transformers are available in addi-
standards, such as the German “Medium Voltage Direc- tion to medium voltage switch gears.
BPT-IS 400–1200 | Specifications
Inverter
Interference emission (EMV) DIN EN 61000-6-4:2007-09
Interference-resistance (EMV) DIN EN 61000-6-2:2006-03
Electrical safety IEC 62109-1 Ed 1.0 2010-04; IEC 62103:2003, DIN EN 50178:1998
Pre-configured standards RD1565, EN50438:2007, BDEW MS guidelines, A 70 Terna
Station design
Material wu lightweight concrete LC 25 / 28 in acc. with DIN 1045:2001-07
Exposition class for exterior parts XC4, XF1, XA1 in accordance with DIN 1045:2001-07
Exposition class for interior parts XC1 in accordance with DIN 1045:2001-07
Exterior walls Washed-out concrete, granularity 8/16 (other options available)
Roof Concrete, floating design
Oil tray Integrated oil-proof metal oil pan (optionally)
Exhaust air hood Aluminium
Air grilles / doors / frames Aluminium
Attachment points 4 x Deha anchors, type 20 T
Number of cable inputs Hauff HSI 150 system
Earthing bushing Hauff HEA-I-M12
Standards
Grid quality DIN EN 61000-3-11:2001-04 / DIN EN 61000-3-12:2005-09
CE Mark compliant Yes
Design approval Yes (Bureau Veritas)
Conformity with German Renewable Yes
Energies Act § 6 EEG 2012 §6.1 (1)
Type: BPT-IS 400 500 600 700 800 900 1000 1100 1200
Item no.: B1-120- 005 006 007 008 009 010 011 013 014
AC Rated power 400 500 600 700 800 900 1000 1100 1200
(inverter) (Sac, r) kVA kVA kVA kVA kVA kVA kVA kVA kVA
Recommended DC output (kWp) 440 550 660 770 880 990 1100 1210 1320
Maximum DC Power (kWp) 480 600 720 840 960 1080 1200 1320 1440
AC rated current (A) 11.55 14.43 17.32 20.20 23.10 25.98 28.87 31.75 34.64
System efficiency factor 4, 7
Maximum efficiency factor 98.1 % 98.1 % 98.1 % 98.1 % 98.1 % 98.1 % 98.1 % 98.1 % 98.1 %
European efficiency factor 97.6 % 97.7 % 97.8 % 97.6 % 97.7 % 97.8 % 97.7 % 97.7 % 97.8 %
Californian efficiency factor 97.9 % 98.0 % 98.0 % 97.9 % 98.0 % 98.0 % 98.0 % 98.0 % 98.0 %
Auxiliary supply 2
Stand-by / nighttime performance 220 W 330 W 440 W
(Pnight)
Power consumption (Pday) 3, 7 220 W to 4,400 W 330 W to 6,500 W 440 W to 8,700 W
Medium Voltage transformer
Rated output 600 kVA 900 kVA 1250 kVA
Vector group Dyn5 Dyn5 Dyn5
Short circuit voltage 6 6% 6% 6%
No-load losses 6 320 W 400 W 580 W
Dimensions / weight
Dimensions (W x H x D) 5 2,880 x 2,950 x 5,280 mm 2,880 x 2,950 x 6,880 mm 2,880 x 2,950 x 6,880 mm
Weight of entire station 6, 7 28 t 35 t 35 t
BPT-IS 400–1200 | Specifications
100
90
80 VIS 400
70 VIS 500
VIS 600
in %
60
in %
VIS 700
factor
50 VIS 800
Efficiency
Efficiency
VIS 900
40
VIS 1000
30
VIS 1100
20 VIS 1200
10
0
0 10 20 30 40 50 60 70 80 90 100
% AC %
ofofrated power
AC rated power
BPT-IS 400 500 600 700 800 900 1000 1100 1200
Pr
5% 93.10 % 94.00 % 95.00 % 93.70 % 94.40 % 95.00 % 94.00 % 94.60 % 95.00 %
10 % 96.00 % 96.40 % 96.80 % 96.30 % 96.60 % 96.80 % 96.40 % 96.60 % 96.80 %
20 % 96.80 % 97.20 % 97.50 % 97.00 % 97.30 % 97.50 % 97.20 % 97.30 % 97.50 %
25 % 97.40 % 97.70 % 98.00 % 97.60 % 97.80 % 98.00 % 97.70 % 97.90 % 98.00 %
30 % 97.90 % 98.00 % 98.00 % 97.90 % 98.00 % 98.00 % 98.00 % 98.00 % 98.00 %
50 % 98.10 % 98.10 % 98.10 % 98.10 % 98.10 % 98.10 % 98.10 % 98.10 % 98.10 %
75 % 98.10 % 98.10 % 98.10 % 98.10 % 98.10 % 98.10 % 98.10 % 98.10 % 98.10 %
100 % 97.80 % 97.80 % 97.80 % 97.80 % 97.80 % 97.80 % 97.80 % 97.80 % 97.80 %
Efficiency
BPT-IS 1000 – 1200
DC 530 – 1000V
DC 530 – 1000V
P υ
P υ
L1 / L2 / L3
L1 / L2 / L3
L1 / L2 / L3
400 V 14 kVA
[L1 / L2 / L3 / N]
400V 14kVA
[L1 / L2 / L3 / N]