DG-1 DG-2

Generator
1,250KVA
415V, 3P4W, 50Hz
1,739A

ACB, 2,500A, 4P ACB 2,500, 4P

Power Cables
P= 3x 300mm2 single core cable
N= 1x 300mm2 single core cable

Changeover Switch
1,600A

I II

Substation

Note:
1) Power cable shall be 2x 300mm2/ phase (as minimum) for a length not more than 20m, noting
that the original design rating were 3x 630mm2/ Phase and 2x 630mm2 for Neutral
2) Manual Transfer Switch to be serviced and protected with covers (covers are missing)