VIBRO Replacement (Stone Columns) For Central Reservoir Dammam 5
VIBRO Replacement (Stone Columns) For Central Reservoir Dammam 5
Project Name : Dammam Water Quality Improvement Project South Strategic Network & Reservoires Dammam-5
Project Code : 12828 Reference : WQIP-D5-AWP-T-0153
Consultant : ILF Consultant Engineers Revision : V0
Contractor : Alkhorayef Water & Power Technologies Date : 30-Oct-22
We certify that the document mentioned above is in accordance with the Contract Specification and Approved Drawings.
Action
Acceptance does not relieve the contractor from his responsibility and liability concerning compliance with the contract requirement.
Project Name
Water Quality Improvement Project-South Distribution
Network & Reservoirs-Dammam Project 5
Main Contractor
Alkhorayef Water & Power Technologies
DOCUMENT TITLE:
VIBRO Replacement (Stone Columns) FOR Dammam Central RESERVOIR
Prepared For;
This document is property of Geoharbour. Its total or partial reproduction is strictly forbidden by any means,
as well as its distribution to third parties without the express written consent. Any copy of this document in
digital or paper support will be considered a not control copy. The only valid copy is the last one approve
located in the document manager tool.
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Al Khobar, KSA
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Al Khobar, KSA
CONTENTS
1. Purpose ....................................................................................................... 6
2. Scope .......................................................................................................... 6
3. Project Overview.......................................................................................... 8
3.1. Subsurface formation ....................................................................................... 9
3.2. Ground Water Condition .................................................................................10
4. Reference .................................................................................................. 10
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Al Khobar, KSA
9. Attachment ................................................................................................ 17
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Al Khobar, KSA
Abbreviations:
Owner NWC
Consultant ILF
MS Method Statement
GL Ground Level
SC Stone Column
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
1. Purpose
This method statement of construction of Stone Columns is proposed for Central Reservoir, Dammam, KSA. It
is prepared on the basis of data collected from the site as per soil condition of current site and gives an indication
of our general approach to the construction and management of the project.
In this method statement, we state our intentions for managing and supporting the project and the specific
approach that will be taken for certain key aspects. The main content includes the requirements, materials,
equipment and HSE regulations for works.
2. Scope
This document outlines the methods, required materials, equipment and quality control standards to be
performed in all operations during Stone Column construction works for Central Reservoir, specifically for two
water storage Tanks, KSA.
Stone Column extends the range of soils which can be improved by vibratory techniques, including cohesive soils.
Reinforcement of the soil with compacted granular columns or “stone columns” is accomplished by the top-feed
method. Stone columns are cylindrical columns made below ground level which is comprised of granular material
of large sizes varying from 20 to 100 mm and the small size (<20mm) content less than 10%. A hole is made in
the soft deposit by different techniques and then filled with stones in layers and compacted to form the complete
column. When a structure is placed over the area treated by stone columns, majority of the load could be borne
by stone columns. In this case, the diameter of stone column is 900 mm.
As a way forward, the testing method as indicated and is expected to demonstrate the following:
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
3. Project Overview
The project is located in Al Khobar, Eastern Province, Kingdom of Saudi Arabia and consists of two steel tank each
50m diameter, height 23.7m in addition to other facilities.
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
1) Fill layer consists of rubbish, silts, sands and gravel (this shall be cleaned by
MC)
2) Loose to medium Poorly graded SAND
3) Fractured limestone
4) Medium dense to dense poorly graded SAND
5) Hard Elastic Silt
Tanks 1 & 2
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
According to the soil condition and acceptance criteria, Stone Column would be the optimal improvement
technique in this area to enhance the soil stiffness thus to increase bearing capacity, reduce the post construction
settlement and reduce the potential of liquefaction (if any)
4. Reference
Layout Drawing provided by Al Khorayef
Ground investigation report prepared by SAFCO of ref: KSM-4458
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
5. Work Procedure
The sequence for stone column works shall be found below.
Steel pegs approx. 80 cm long shall be used to mark a Probe location and shall carry a tag identifying the Probe
number at enough intervals. Tolerance for coordinates will be not more than 200 mm.
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
The essential equipment for this process is a vibrator – a long heavy tube enclosing eccentric weights driven by
an electric motor. The vibrator is connected to a source of electric power and a high-pressure pump with
following capacity Q=120 M3/hour. Extension tubes are added as necessary and the whole assembly is
suspended from a crane.
With the electric power and water supply switched on, the vibrator is lowered into the ground. The combination
of vibration and high-pressure water jetting causes liquefaction of the soils surrounding the vibrator that assists
in penetration.
Following penetration of the vibrator and its withdrawal after reaching the required depth the resulting cavity is
filled with coarse-grained materials (stone). This supply of material is itself in turn compacted. A stone column is
thus formed in which the stone is laterally pressed into the soil. The stone column and the in-situ soil form an
integrated system having low compressibility and high shear strength. The excess pore water can readily dissipate
through the stone columns that act simultaneously as drains. For this reason, settlement occurs faster than
normal in cohesive soils.
An indication of the effectiveness of the treatment is the quantity of backfill material used. Other control
procedures are available, such as load or penetration tests.
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
6. Operation Condition
6.1. Construction Personnel
Single or extended shift are considered for ground improvement works; the proposed manpower is listed in the
below table.
Management
Corporation Managers
1 Project Director 1
2 Technical Director 1
3 Corporate/Legal Director 1
4 Commercial Director 1
1 Project Manager 1
2 Site manager 1
3 HSE Manager 1
4 Document Controller 1
5 Safety Officer 1
6 Logistics 1
7 supervisor 1
Sub-total 11
Labor
1 Technician 2
3 Loader Driver 1
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
4 Welder 1
5 Auxiliary Workers 3
6 Electrician 1
7 Maintenance 1
Sub-total 10
6.3. Material
The material shall be suitable for the ground conditions for the ground conditions in which the stone columns
are formed and have no adverse effect on other work on the site. Grading shall be a nominal single-size material
within the range of 20mm-100mm and small size (<20mm) content less than 10%.
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
9. Attachment
Appendix 1: Daily Report Form
Appendix 2: Risk Assessment for Stone Column Works
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
Likelihood
consequen remedial actions / ADDITIONAL department /
Risk rate
Severity
Likelihood
nor in sequence Hazardous event as as
Risk rate
ce/ risk control measures CONTROL MEASUREES person
Severity
possibl possible)
e)
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
Constantly monitor
and frequent
consultation for
assign duty
including the
provision of
competent
supervision.
Avoid lonely
working for
new/young
appointed workers
Conducting Pre
start briefing , tool
box talks and H.S.E
training for
personnel to adopt
the necessary site
safe practices and
procedures
Awareness training
of access/egress,
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
2 Mobilization of Collision with Personnel 4 3 12 Safety induction , 2 3 6 NO Installation of radars YES GEOHARBOUR
tools and other vehicles minor equipment / tool and visible signage’s
equipment to or earth injuries , inspection prior to showing speed limit
the work place moving electrocuti enter any personnel of 20kmph .
machinery / on , , equipment or tools
equipment Major into the work place Installation of goal
injuries , posts if any
Hit by / struck Fatality , Supervisor/foreman overhead power
by moving Property to monitor the work lines .
pedestrians damage , force vigilantly for
moving vehicles and Segregation of
Trailing / pedestrians pedestrian
overhead walkways and
cables / wet Ensure that the area vehicle routes.
ground is clean and safe for
work with adequate Provision of well
Failure to lighting prior to compacted and
follow site safe mobilize the leveled ground for
access & egress equipment off loading materials
/ speed limits .
Machinery must be
Over speeding securely anchored
of loaded to the van / trailer
trucks.
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
Ground to be
securely plane and
compact to the
crane when the
machinery or tools
is being mobilizing.
Personnel’s are
trained regarding
the site safe access
and egress and
speed limits to
avoid accidents
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
3 Assembling Failure of Personnel 5 4 20 Moment and 2 4 8 NO Ensure safe working YES GEOHARBOUR
and loading and minor positioning of crane load must be
dissembling of unloading of injuries , (H must be sited in (M indicated on the
) )
cranes machinery/equi Major well compacted crawler crane .
pment or tools injuries , surface away from
Fatality , other structures and Crane shall be
Failure of lifting Property excavated areas . tested and
equipment and damage examined by a
accessories Assembling / competent 3rd party
dissembling area examiner in
Collision with must be barricaded accordance with the
other and installed statutory
equipments signage to requirements.
and nearby indication Before these tests
structures. and examinations
Crane must be are carried out,
Fall from height mounted /
, being struck dismounted and Inspect and color
by p plant / configured by code of all
machinery adequately trained accessories used to
and competent loading and
persons unloading of
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
Crane must be
erected and jib set
up accordance with
the manufacturer's
Instructions, Care
should be taken to
ensure that the jib
sections are
assembled in their
correct order and
relative positions.
it is recommended
that a visual
inspection of the
crane be made by
the competent
person supervising
the erection.
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
Lifting of boom Cuts, 3 3 9 Crane and all lifting 2 3 6 NO Provision of harness YES GEOHARBOUR
4 Boom sections Bruises, accessories belts and fall
Assembly Crushing ( inspected and (M arresters for the
M )
Falling pins, hands, certified by workers working at
hammer and Broken ) government- height.
Fixing pins and hand tools bones, accredited 3rd party
bolts for from height Personal inspector. Provide suitable
connecting injury, portable ladders to
boom at height Personnel Fall Property Crane operator with easy access to the
from height damage valid license and 3rd boom for fixing the
party assessment pins or bolts
Lifting roof Mechanical certificate.
beams, failure
Lifting angle Crane inspection
bracing. checklist filled up
Lifting purloins. (including crane
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
Slinging of loads
only by certified
rigger/slinger and
tag lines available.
Ensure temporary
guys/bracings are
securely anchored.
Supervisor to
monitor and
supervise lifting
activity.
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
Collapse of 6
5 Assembling 3 3 9 Tagline should be 2 3 NO A supporting mobile YES GEOHARBOUR
materials due
vibro cat Personnel used to handling the crane should be
to lack of un (M
equipment to injury, ( ( vibro cat while provided while
stable ground )
the crane minor / M fixing , assembling the
level ,
major ) ) No personnel’s are vibrators to support
Fall of vibro cat Electrocuti allowed n the radius lifting the vibrator .
while lifting on , of crane .
Over turning of property Provide a suitable
equipment due damage. All work to be rope or belt for
unstable completed under tagline to control
ground or the guidance and the handling of load
improper control of the Crane .
signaling Lifting supervisor.
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
Ground conditions
to be assessed by
crane driver and
Crane
Lifting supervisor
and signed off by
Crane Lifting
supervisor prior to
set up
Crane to be checked
in accordance with
legal requirements
Driver to check
safety system daily
using checklist.
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
Workers personnel
protective
equipment should
be ensured prior to
work ( hand gloves
hard hat , high
visible west , safety
shoes and if nay
required rubber
gloves )
Vibrocat cables
should be secured
and handled
properly while
installation process
6 Lifting of cat Hit persons Severe 4 2 8 Technicians are 2 2 4 YES YES GEOHARBOUR
vibrator near by personnel advised to securely
injuries , ( fix the cat vibrator
Hit equipment Fatality , M to the crane hook
or structures Property ) and lock properly .
around. damage.
A supporting tagline
should be used to
control the load to
avoid hitting men
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
Operators are
advised to lift the
vibrators slow and
move smoothly
without jerking to
avoid collisions .
Surrounding areas
to be barricaded ad
installed with
warning signs to
prior to lifting.
Certified operators
and riggers only
should be allowed
to the workplace ,
all others are
restricted to come
around the working
radius of crane.
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
Experiences
electrician /
technicians are
appointed to carry
out the activities .
Avoid storage of
water for long time
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
Implementation of
one way routes to
avoid collisions
Allow well
maintained trucks
and competent
operators for safe
delivery.
9 Setting survey Slip /trip & falls Minor 2 3 6 Work procedure 1 3 3 YES YES GEOHARBOUR
point & on uneven personnel and safety
installation of ground. injuries measures to be
communicated with
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
Rebar caps /
reflecting caps
should be installed
on rebar to warn
others falling on
that.
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
Lifting slings/gears
to be inspected
daily by user and
thoroughly
examined 6-
monthly by
competent person
including the use of
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
No unauthorized
person should come
around / beneath of
the crane radius .
Regular
maintenance should
be done to the
crane for safe work .
11 Moment of Collide with Minor / 3 4 12 Daily maintenance 2 4 8 NO Third party YES GEOHARBOUR
shovel / wheel workers , other major of pre use checklist certification for the
injuries for the equipment. operator and flag
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
Barricading and
signage should be
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
12 Stone column Collapse of Minor / 3 4 12 Safe distance shall 1 4 4 YES Ensure that auxiliary YES GEOHARBOUR
works ground major be maintained to safety devices are in
personnel avoid contact with place and in good
Damage to injuries vibro Probe. order.
hearing Property
damage Water barriers shall Load charts MUST
Loss of stability be provided to be in cab of crane.
avoid contact with
Bursting of vibro at least 5 Loads must not be
water pipes meter near the suspended by the
and electrical center of crane. crane if unattended.
wires
Ear plugs shall be Crane
Noise and provided to must be
vibration decrease the effect immobilized when
of noise. left unattended.
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
Grinding/cutting
machine operators
shall ensure that
they wear suitable
respiratory
equipment’s.
Personnel shall
ensure that all discs
are adequately
fitted to grinders.
All electrical
connections should
be routed through'
ELCB of 30 mA.
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
Adequate
supervision at all
times
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
Noise/vibration 8
16 Using Power 3 4 12 roper guards must 2 4 NO Cable management YES
/dust/ electrical injury,
tools be in place should be
hazards breathing
maintained while
problem, Competent persons
cuts/tears working with power
exposure for the job role.
sprains etc tools.
to high Adequate
Electrical organic supervision.
shocks and Power tools
vapors,
burns checklist to be
fire,
Adequate provided at
dermatitis
Illuminating source. workplace and
Induction and maintain it everyday
training
Special training for
the fresher
Appropriate
working platform
Remove all trailing
cables from access.
Proper PPE
All power tools
should be inspected
by competent
person and color
coded prior to work
Damaged and not in
use equipments
should be
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
individuals to wear
a hat and
appropriate clothing
to help protect from
UV rays
No working at
heights externally
takes place
Consider
rescheduling
activities.
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
Appropriate
clothing is worn
Means of services
back up are
considered in case
of power failure.
Weather forecasts
are checked and the
Environment
Agency
If premises are
located within an
identified flood
zone.
An emergency plan
is in place.
Provisions are in
place to protect
services to
premises.
Weather should be
checked and
reported every time
and should not
allow any activities
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
Rest room to be
provided
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
Supervisor/foreman
to be monitors the
team accordingly
Appropriate dust
mask to be worn as
per the task
requirements
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
Smoking should be
strictly prohibited in
areas of refueling
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
Fire explosion Fire burns 3 5 15 A double mounted 2 5 10 NO Should follow safety YES GEOHARBOUR
and oil spillage , diesel tanks should Rules and
Fire be installed for regulations of
explosions storing the oil and government
, fuel. regarding storage of
Fatality highly flamed fuels.
Environme Dip trays should be
ntal provided for the Third party certified
impact storage tanks to fuel containers are
Fuel and oil
22 control the spillage only to be used at
storage
which effects soil the workplace.
contamination.
Sufficient fire
extinguishers to be
provided
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
Barricading and
signage should be
installed to warn
the unauthorized
persons entering
into the site .
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
Collapse of 6
3 3 9 Tagline should be 2 3 NO A supporting mobile YES GEOHARBOUR
materials due
Personnel used to handling the crane should be
to lack of un (M
injury, ( ( vibro cat while provided while
stable ground )
minor / M fixing , assembling the
level ,
major ) ) No personnel’s are vibrators to support
Fall of vibro cat Electrocuti allowed n the radius lifting the vibrator .
while putting on , of crane .
down property Provide a suitable
Over turning of damage. All work to be rope or belt for
equipment due completed under tagline to control
unstable the guidance and the handling of load
ground or control of the Crane .
dissembling
improper Lifting supervisor.
vibro cat
24 signaling Trained and
equipment to
Under any certified technicians
the crane Fall of persons circumstances “NO are allocated for
or materials MOBILE PHONE” fixing the vibrators.
while fixing during
vibro cat operation.
Ground conditions
to be assessed by
crane driver and
Crane
Lifting supervisor
and signed off by
Crane Lifting
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
Crane to be checked
in accordance with
legal requirements
Driver to check
safety system daily
using checklist.
Workers personnel
protective
equipment should
be ensured prior to
work ( hand gloves
hard hat , high
visible west , safety
shoes and if nay
required rubber
gloves )
Vibrocat cables
should be secured
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
Dissembling of Failure of Personnel 5 4 20 Moment and 2 4 8 NO Ensure safe working YES GEOHARBOUR
cranes loading and minor positioning of crane load must be
unloading of injuries , (H must be sited in (M indicated on the
)
machinery/equi Major ) well compacted crawler crane .
pment or tools injuries , surface away from
Fatality , other structures and Crane shall be
Failure of lifting Property excavated areas . tested and
equipment and damage examined by a
accessories Assembling / competent 3rd party
dissembling area examiner in
Collision with must be barricaded accordance with the
other and installed statutory
25
equipments signage to requirements.
and nearby indication Before these tests
structures. and examinations
Crane must be are carried out,
Fall from height mounted /
, being struck dismounted and Inspect and color
by p plant / configured by code of all
machinery adequately trained accessories used to
and competent loading and
persons unloading of
equipment and
Prior to crane tools
operation it must be
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
Crane must be
erected and jib set
up accordance with
the manufacturer's
Instructions, Care
should be taken to
ensure that the jib
sections are
assembled in their
correct order and
relative positions.
it is recommended
that a visual
inspection of the
crane be made by
the competent
person supervising
the erection.
Proper conditioned
and inspected crane
should be used to
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
Ground to be
securely plane and
compact to the
crane when the
machinery or tools
is being mobilizing.
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group
Ground Improvement for Central Reservoir, Dammam, KSA
P. O. Box: 391662, Dubai – U.A.E. | Tel: +971 4 447 0945 | Fax: +971 4 447 2190 | P.O.Box:5100648 |Tel:+9712 510 2400|Fax:+9712 558 9961
E-mail: dubai@geoharbour.com | www.geoharbour.ae
Member of Shanghai Geoharbour Group