Professional Documents
Culture Documents
Dharan Desrt City Local
Dharan Desrt City Local
1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
Design Ventilation Airflow Rate 0 CFM
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' Bedroom 1 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1300 HEATING DATA AT DES HTG
COOLING OA DB / WB 108.4 °F / 70.2 °F HEATING OA DB / WB 45.0 °F / 37.8 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 9 ft² 415 - 9 ft² - -
Wall Transmission 267 ft² 258 - 267 ft² 166 -
Roof Transmission 132 ft² 1125 - 132 ft² 370 -
Window Transmission 9 ft² 156 - 9 ft² 132 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 132 ft² 0 - 132 ft² 0 -
Partitions 228 ft² 0 - 228 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 198 W 676 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 2 490 410 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 15% / 5% 468 21 0% 0 0
>> Total Zone Loads - 3588 431 - 668 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' Bedroom 1 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
E EXPOSURE
WALL 135 0.025 - 137 - 84
WINDOW 1 9 0.588 0.811 156 415 132
N EXPOSURE
WALL 132 0.025 - 121 - 82
H EXPOSURE
ROOF 132 0.112 - 1125 - 370
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' Bedroom 2 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 111.0 °F / 71.0 °F HEATING OA DB / WB 45.0 °F / 37.8 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 9 ft² 614 - 9 ft² - -
Wall Transmission 267 ft² 359 - 267 ft² 166 -
Roof Transmission 132 ft² 988 - 132 ft² 370 -
Window Transmission 9 ft² 168 - 9 ft² 132 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 132 ft² 0 - 132 ft² 0 -
Partitions 228 ft² 0 - 228 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 198 W 676 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 2 490 410 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 15% / 5% 494 21 0% 0 0
>> Total Zone Loads - 3787 431 - 668 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' Bedroom 2 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 132 0.025 - 133 - 82
W EXPOSURE
WALL 135 0.025 - 226 - 84
WINDOW 1 9 0.588 0.811 168 614 132
H EXPOSURE
ROOF 132 0.112 - 988 - 370
TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' kitchen '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1300 HEATING DATA AT DES HTG
COOLING OA DB / WB 108.4 °F / 70.2 °F HEATING OA DB / WB 45.0 °F / 37.8 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 48 ft² 49 - 48 ft² 30 -
Roof Transmission 36 ft² 308 - 36 ft² 101 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 36 ft² 0 - 36 ft² 0 -
Partitions 84 ft² 0 - 84 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 36 W 123 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 1 245 205 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 15% / 5% 109 10 0% 0 0
>> Total Zone Loads - 834 215 - 131 0
TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' kitchen '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
E EXPOSURE
WALL 48 0.025 - 49 - 30
H EXPOSURE
ROOF 36 0.112 - 308 - 101
TABLE 1.4.A. COMPONENT LOADS FOR SPACE '' Living room '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 110.3 °F / 70.8 °F HEATING OA DB / WB 45.0 °F / 37.8 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 9 ft² 518 - 9 ft² - -
Wall Transmission 633 ft² 716 - 633 ft² 393 -
Roof Transmission 322 ft² 2630 - 322 ft² 904 -
Window Transmission 9 ft² 164 - 9 ft² 132 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 30 ft² 278 - 30 ft² 225 -
Floor Transmission 322 ft² 0 - 322 ft² 0 -
Partitions 228 ft² 0 - 228 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 644 W 2197 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 5 1225 1025 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 15% / 5% 1159 51 0% 0 0
>> Total Zone Loads - 8887 1076 - 1654 0
TABLE 1.4.B. ENVELOPE LOADS FOR SPACE '' Living room '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
E EXPOSURE
WALL 168 0.025 - 174 - 104
W EXPOSURE
WALL 159 0.025 - 229 - 99
WINDOW 1 9 0.588 0.811 164 518 132
S EXPOSURE
WALL 306 0.025 - 312 - 190
DOOR 30 0.300 - 278 - 225
H EXPOSURE
ROOF 322 0.112 - 2630 - 904
TABLE 1.5.A. COMPONENT LOADS FOR SPACE '' Toilet '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1300 HEATING DATA AT DES HTG
COOLING OA DB / WB 108.4 °F / 70.2 °F HEATING OA DB / WB 45.0 °F / 37.8 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 60 ft² 69 - 60 ft² 37 -
Roof Transmission 50 ft² 428 - 50 ft² 140 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 50 ft² 0 - 50 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 84 ft² 0 - 84 ft² 0 -
Overhead Lighting 38 W 128 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 1 245 205 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 15% / 5% 131 10 0% 0 0
>> Total Zone Loads - 1001 215 - 178 0
TABLE 1.5.B. ENVELOPE LOADS FOR SPACE '' Toilet '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
W EXPOSURE
WALL 60 0.025 - 69 - 37
H EXPOSURE
ROOF 50 0.112 - 428 - 140
TABLE 1.6.A. COMPONENT LOADS FOR SPACE '' WIC 1 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1200 HEATING DATA AT DES HTG
COOLING OA DB / WB 105.5 °F / 69.4 °F HEATING OA DB / WB 45.0 °F / 37.8 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 72 ft² 76 - 72 ft² 45 -
Roof Transmission 42 ft² 357 - 42 ft² 118 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 42 ft² 0 - 42 ft² 0 -
Partitions 168 ft² 0 - 168 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 42 W 143 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 1 245 205 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 15% / 5% 123 10 0% 0 0
>> Total Zone Loads - 945 215 - 163 0
TABLE 1.6.B. ENVELOPE LOADS FOR SPACE '' WIC 1 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
E EXPOSURE
WALL 72 0.025 - 76 - 45
H EXPOSURE
ROOF 42 0.112 - 357 - 118
TABLE 1.7.A. COMPONENT LOADS FOR SPACE '' WIC 2 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 110.3 °F / 70.8 °F HEATING OA DB / WB 45.0 °F / 37.8 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 60 ft² 86 - 60 ft² 37 -
Roof Transmission 35 ft² 287 - 35 ft² 98 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 35 ft² 0 - 35 ft² 0 -
Partitions 168 ft² 0 - 168 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 26 W 90 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 1 245 205 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 15% / 5% 106 10 0% 0 0
>> Total Zone Loads - 815 215 - 135 0
TABLE 1.7.B. ENVELOPE LOADS FOR SPACE '' WIC 2 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
W EXPOSURE
WALL 60 0.025 - 86 - 37
H EXPOSURE
ROOF 35 0.112 - 287 - 98
ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°F) (°F) (%) (CFM) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr)
0000 91.4 82.8 - 0.0 12578.5 0.0 0.0 0.0 0.0
0100 90.2 82.8 - 0.0 12303.4 0.0 0.0 0.0 0.0
0200 89.0 76.0 64 1083.6 12043.0 15123.4 0.0 0.0 0.0
0300 88.1 75.8 65 1083.6 11804.8 14571.7 0.0 0.0 0.0
0400 87.3 76.1 68 1083.6 11596.3 13409.8 0.0 0.0 0.0
0500 87.1 76.1 68 1083.6 11650.1 13360.8 0.0 0.0 0.0
0600 87.6 75.9 65 1083.6 12800.3 14824.2 0.0 0.0 0.0
0700 88.8 76.0 63 1083.6 14346.7 15891.7 0.0 0.0 0.0
0800 90.9 76.1 60 1083.6 15730.5 16981.9 0.0 0.0 0.0
0900 94.0 76.2 59 1083.6 16902.5 17676.9 0.0 0.0 0.0
1000 97.6 76.5 59 1083.6 17833.4 17946.0 0.0 0.0 0.0
1100 101.7 76.3 57 1083.6 18533.3 18983.7 0.0 0.0 0.0
1200 105.5 76.4 56 1083.6 19109.5 19261.8 0.0 0.0 0.0
1300 108.4 76.4 56 1083.6 19583.6 19629.6 0.0 0.0 0.0
1400 110.3 76.3 55 1083.6 19729.1 19747.5 0.0 0.0 0.0
1500 111.0 76.3 56 1083.6 19430.4 19408.2 0.0 0.0 0.0
1600 110.3 76.3 57 1083.6 18636.1 18545.4 0.0 0.0 0.0
1700 108.6 76.0 59 1083.6 17240.4 17715.0 0.0 0.0 0.0
1800 106.0 76.3 64 1083.6 15567.8 15342.6 0.0 0.0 0.0
1900 102.9 76.3 65 1083.6 14670.1 14502.5 0.0 0.0 0.0
2000 99.8 76.2 66 1083.6 14131.5 14009.2 0.0 0.0 0.0
2100 97.1 82.3 - 0.0 13677.3 0.0 0.0 0.0 0.0
2200 94.7 82.6 - 0.0 13263.0 0.0 0.0 0.0 0.0
2300 92.8 82.7 - 0.0 12894.3 0.0 0.0 0.0 0.0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.078 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4737.2 BTU/(hr-CFM)
Site Altitude = 55.0 ft
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.078 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4737.2 BTU/(hr-CFM)
Site Altitude = 55.0 ft
0.016
0.012
3
12
0.010
0.008
0.006
0.004
0.002
0.000
30 40 50 60 70 80 90 100
Temperature ( °F )