Download as pdf or txt
Download as pdf or txt
You are on page 1of 36

Installation Manual

Detector Control
Generator Sets

Models
DFBF, DFCB, DFCC

Printed in U.S.A. 960-0606 1-2003


Table of Contents

SECTION TITLE PAGE


1 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
About this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Installation Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
2 SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
3 MOUNTING THE GENERATOR SET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Access to Set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Vibration Isolators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
4 MECHANICAL CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Fuel System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Exhaust System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Ventilation and Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
5 ELECTRICAL CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Transfer Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
AC Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
DC Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
6 PRESTART PREPARATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Exhaust System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Mechanical Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Electrical System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Coolant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
Fuel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
7 INITIAL START AND CHECKS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
Starting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
Engine Gauges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
AC Meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
Engine Monitor Indicator Lamps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
Exhaust System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
Fuel System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
DC Electrical System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
Cooling System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
Mechanical Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
8 WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1

i
ii
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS – This manual contains EXHAUST GASES ARE DEADLY
important instructions that should be followed during
installation and maintenance of the generator and batter- • Provide an adequate exhaust system to properly
ies. expel discharged gases away from enclosed or
sheltered areas and areas where individuals are
Before operating the generator set (genset), read the likely to congregate. Visually and audibly inspect
Operator’s Manual and become familiar with it and the the exhaust daily for leaks per the maintenance
equipment. Safe and efficient operation can be schedule. Make sure that exhaust manifolds are se-
achieved only if the equipment is properly operated cured and not warped. Do not use exhaust gases to
and maintained. Many accidents are caused by failure heat a compartment.
to follow fundamental rules and precautions.
• Be sure the unit is well ventilated.
The following symbols, found throughout this manual,
alert you to potentially dangerous conditions to the oper-
• Engine exhaust and some of its constituents are
known to the state of California to cause cancer,
ator, service personnel, or the equipment.
birth defects, and other reproductive harm.
This symbol warns of immediate
MOVING PARTS CAN CAUSE SEVERE
hazards which will result in severe personal in-
jury or death. PERSONAL INJURY OR DEATH
• Keep your hands, clothing, and jewelry away from
WARNING This symbol refers to a hazard or un- moving parts.
safe practice which can result in severe person-
al injury or death. • Before starting work on the generator set, discon-
nect battery charger from its AC source, then dis-
CAUTION This symbol refers to a hazard or un- connect starting batteries, negative (–) cable first.
safe practice which can result in personal injury This will prevent accidental starting.
or product or property damage. • Make sure that fasteners on the generator set are
secure. Tighten supports and clamps, keep guards
FUEL AND FUMES ARE FLAMMABLE in position over fans, drive belts, etc.
Fire, explosion, and personal injury or death can result • Do not wear loose clothing or jewelry in the vicinity of
from improper practices. moving parts, or while working on electrical equip-
ment. Loose clothing and jewelry can become
• DO NOT fill fuel tanks while engine is running, un- caught in moving parts.
less tanks are outside the engine compartment.
Fuel contact with hot engine or exhaust is a potential • If adjustment must be made while the unit is run-
fire hazard. ning, use extreme caution around hot manifolds,
moving parts, etc.
• DO NOT permit any flame, cigarette, pilot light,
spark, arcing equipment, or other ignition source DO NOT OPERATE IN FLAMMABLE AND
near the generator set or fuel tank.
EXPLOSIVE ENVIRONMENTS
• Fuel lines must be adequately secured and free of
leaks. Fuel connection at the engine should be Flammable vapor can cause an engine to overspeed and
made with an approved flexible line. Do not use zinc become difficult to stop, resulting in possible fire, explo-
coated or copper fuel lines with diesel fuel. sion, severe personal injury and death. Do not operate a
genset where a flammable vapor environment can be
• Be sure all fuel supplies have a positive shutoff created by fuel spill, leak, etc., unless the genset is
valve. equipped with an automatic safety device to block the air
• Be sure battery area has been well-ventilated prior intake and stop the engine. The owners and operators of
to servicing near it. Lead-acid batteries emit a highly the genset are solely responsible for operating the gen-
explosive hydrogen gas that can be ignited by arc- set safely. Contact your authorized Cummins Power
ing, sparking, smoking, etc. Generation distributor for more information.

LS-14M
iii
ELECTRICAL SHOCK CAN CAUSE GENERAL SAFETY PRECAUTIONS
SEVERE PERSONAL INJURY OR DEATH • Coolants under pressure have a higher boiling point
than water. DO NOT open a radiator or heat ex-
• Remove electric power before removing protective changer pressure cap while the engine is running.
shields or touching electrical equipment. Use rub- Allow the generator set to cool and bleed the system
ber insulative mats placed on dry wood platforms pressure first.
over floors that are metal or concrete when around
electrical equipment. Do not wear damp clothing • Used engine oils have been identified by some state
(particularly wet shoes) or allow skin surface to be or federal agencies as causing cancer or reproduc-
damp when handling electrical equipment. Do not tive toxicity. When checking or changing engine oil,
wear jewelry. Jewelry can short out electrical con- take care not to ingest, breathe the fumes, or con-
tacts and cause shock or burning. tact used oil.

• Use extreme caution when working on electrical • Keep multi-class ABC fire extinguishers handy.
Class A fires involve ordinary combustible materials
components. High voltages can cause injury or
such as wood and cloth; Class B fires, combustible
death. DO NOT tamper with interlocks.
and flammable liquid fuels and gaseous fuels; Class
• Follow all applicable state and local electrical C fires, live electrical equipment. (ref. NFPA No. 10).
codes. Have all electrical installations performed by • Make sure that rags are not left on or near the en-
a qualified licensed electrician. Tag and lock open gine.
switches to avoid accidental closure.
• Make sure generator set is mounted in a manner to
• DO NOT CONNECT GENERATOR SET DIRECT- prevent combustible materials from accumulating
LY TO ANY BUILDING ELECTRICAL SYSTEM. under the unit.
Hazardous voltages can flow from the generator set • Remove all unnecessary grease and oil from the
into the utility line. This creates a potential for elec- unit. Accumulated grease and oil can cause over-
trocution or property damage. Connect only heating and engine damage which present a poten-
through an approved isolation switch or an ap- tial fire hazard.
proved paralleling device.
• Keep the generator set and the surrounding area
clean and free from obstructions. Remove any de-
MEDIUM VOLTAGE GENERATOR SETS
bris from the set and keep the floor clean and dry.
(601V to 15kV) • Do not work on this equipment when mentally or
physically fatigued, or after consuming any alcohol
• Medium voltage acts differently than low voltage. or drug that makes the operation of equipment un-
Special equipment and training is required to work safe.
on or around medium voltage equipment. Operation • Substances in exhaust gases have been identified
and maintenance must be done only by persons by some state or federal agencies as causing can-
trained and qualified to work on such devices. Im- cer or reproductive toxicity. Take care not to breath
proper use or procedures will result in severe per- or ingest or come into contact with exhaust gases.
sonal injury or death.
• Do not store any flammable liquids, such as fuel,
• Do not work on energized equipment. Unauthorized cleaners, oil, etc., near the generator set. A fire or
personnel must not be permitted near energized explosion could result.
equipment. Due to the nature of medium voltage
electrical equipment, induced voltage remains even
• Wear hearing protection when going near an oper-
after the equipment is disconnected from the power ating generator set.
source. Plan the time for maintenance with autho- • To prevent serious burns, avoid contact with hot
rized personnel so that the equipment can be de-en- metal parts such as radiator, turbo charger and ex-
ergized and safely grounded. haust system.

KEEP THIS MANUAL NEAR THE GENSET FOR EASY REFERENCE

iv
1. Introduction

ABOUT THIS MANUAL Application and Installation

This manual provides installation instructions for A standby power system must be carefully planned
the DF Series generator sets. This includes the fol- and correctly installed for proper operation. This in-
lowing information: volves two essential elements: application and
installation.
Mounting Recommendations - for fastening
generator set to base and space requirements Application (as it applies to generator set installa-
for normal operation and service. tions) refers to the design of the complete standby
power system that usually includes power distribu-
Mechanical Connections - Location of con- tion equipment, transfer switches, ventilation
nection points for fuel, exhaust, ventilation, and equipment, mounting pads, and cooling, exhaust,
cooling. and fuel systems. Each component must be cor-
Electrical Connections – Location of electri- rectly designed so the complete system will function
cal connection points for the control, generator, as intended. Application and design is an engineer-
and starting system. ing function generally done by specifying engineers
or other trained specialists. Specifying engineers
Prestart – Checklist of items or procedures are responsible for the design of the complete
needed to prepare generator set for operation. standby system and for selecting the materials and
Initial Startup – Test complete system to en- products required.
sure proper installation, satisfactory perfor-
mance, and safe operation. Refer to Operators Installation refers to the actual set-up and assem-
Manual for troubleshooting information. bly of the standby power system. The installers set
up and connect the various components of the sys-
This manual DOES NOT provide application infor- tem as specified in the system design plan. The
mation for selecting a generator set or designing the complexity of the standby system normally requires
complete installation. If it is necessary to design the the special skills of qualified electricians, plumbers,
various integrated systems (fuel, exhaust, cooling, sheet metal workers, etc. to complete the various
etc.), review standard installation practices, or segments of the installation. This is necessary so
specify system materials, additional information is all components are assembled using standard
required. For engineering data specific to the gen- methods and practices.
erator set, refer to the specification and product
data sheets. For application information, refer to Safety Considerations
Application Manual T-030, ”Liquid Cooled Genera-
tor Sets”, available from Onan. The generator set has been carefully designed to
provide safe and efficient service when properly
installed and operated. However, the overall safety
INSTALLATION OVERVIEW and reliability of the complete system is dependent
on many factors outside the control of the generator
These installation recommendations apply to typi- set manufacturer. To avoid possible safety haz-
cal installations with standard model generator ards, make all mechanical and electrical connec-
sets. Whenever possible, these recommendations tions to the generator set exactly as specified in this
also cover factory designed options or modifica- manual. All systems external to the generator (fuel,
tions. However, because of the many variables in exhaust, electrical, etc.) must comply with all appli-
any installation, it is not possible to provide specific cable codes. Make certain all required inspections
recommendations for every situation. If there are and tests have been completed and all code re-
any questions not answered by this manual, contact quirements have been satisfied before certifying
an Onan distributor for assistance. the installation is complete and ready for service.

1-1
1-2
2. Specifications

Systems 275 DFBF 300 DFCB 350 DFCC

Cummins Model Engine NT855-G6 NTA855-G2 NTA855-G3


Coolant Capacity 66 Qt. 68 Qt. 68 QT.
Engine and Radiator (62.5L) (64.4L) (64.4L)
Oil Capacity 42 QT. 42 Qt. 42 Qt.
(40L) (40L) (40L)
Fuel Pump
Inlet Thread Size 7/8-14 UNF 7/8-14 UNF 7/8-UNF
Outlet Thread Size 3/4-16 UNF 3/4-16 UNF 3/4-16 UNF
Maximum Lift 5 ft (1.5m) 5 ft (1.5m) 5 ft (1.5m)
Exhaust
Outlet Size 5 in NPT 6 in NPT 6 in NPT
Maximum Allowable 40.8 in H20 40.8 in H20 40.8 in H20
Exhaust Back Pressure (10.2 kPa) (10.2 kPa) (10.2 kPa)
Starting System
Voltage DC 24 24 24
Battery Requirements
Battery Two, 12V Two, 12V Two, 12V
Group 8D Group 8D Group 8D
Cold Cranking Amps 975 975 975

IMPORTANT
DEPENDING ON YOUR LOCATION AND INTENDED USE, FEDERAL, STATE OR LOCAL LAWS
AND REGULATIONS MAY REQUIRE YOU TO OBTAIN AN AIR QUALITY EMISSIONS PERMIT
BEFORE BEGINNING INSTALLATION OF YOUR GENSET. BE SURE TO CONSULT LOCAL
POLLUTION CONTROL OR AIR QUALITY AUTHORITIES BEFORE COMPLETING YOUR
CONSTRUCTION PLANS.

2-1
2-2
3. Mounting the Generator Set
GENERAL • Fuel system installation
Most generator set installations must be designed • Electrical connections
so the generator set will function properly under all • Accessibility for operation and servicing
anticipated operating conditions. Use these instruc- • Noise levels
tions as a general guide only. Follow the instruc-
tions of the consulting engineer when locating or • Vibration isolation
installing any components. The complete installa- LOCATION
tion must comply with all local and state building
codes, fire ordinances, and other applicable regula- Optimum generator set location is determined by
tions. related systems such as ventilation, wiring, fuel,
and exhaust. The set should be located as near as
Requirements to be considered prior to installation possible to the main power fuse box.
(refer to Figure 3-2):
Wood floors should be covered with sheet metal ex-
• Level mounting surface
tending 12 inches (305 mm) beyond the extremities
• Adequate cooling air supply of the set.
• Adequate fresh induction air
Provide a location away from extreme ambient tem-
• Discharge of cooling air peratures. Protect the generator set from adverse
• Discharge of exhaust gases weather conditions, and unauthorized personnel.

3-1
MOUNTING
Generator sets are mounted on a steel subbase
that provides proper support. For critical installa- HEX NUT
tions, install vibration isolators between the sub-
FLAT
base and the foundation. WASHER
Mount the generator set on a substantial and level
base such as a concrete pad. For typical installa- BEVEL SKID
tions, use 3/4 inch anchored mounting bolts to se- WASHER
cure the generator set subbase to the floor to pre-
vent movement. Secure the subbase/vibration iso-
lators using flat or bevel washer and hexagonal nut
for each bolt (see Figure 3-1). For proper spacing of
mounting bolts and set mounting dimensions, see
your generator set outline drawing.
12 INCH
(305 mm)

ACCESS TO SET
Plan for access to the generator set for servicing
and provide adequate lighting around the set. For
convenience in general servicing such as the radia- MOUNTING
BOLT
tor, fan belt, and changing the crankcase oil, the
surface of the mounting base should be at least 6
inches (152 mm) above the floor. M-1627

FIGURE 3-1. TYPICAL ANCHOR BOLT DIAGRAM

3-2
DC
CONTROL
WIRING

CONDENSATION
DRAIN TAP

MUFFLER SWEEPING
ELBOW
THIMBLE

AC POWER WIRING

FLEXIBLE SEC-
TION

AIR
IN

AIR
OUTLET
DUCT

CONCRETE
BASE

VIBRATION IMPORTANT!
ISOLATORS COOLING AIR INLET MUST BE AT
LEAST 1-1/2 TIMES LARGER THAN
RADIATOR DUCT OUTLET AREA
ON RADIATOR COOLED MODELS

FLOW OF COOLING AIR AND


HEATED AIR CAN BE CONTROLLED
BY AUTOMATICALLY OPERATED
M-1808 LOUVRES

FIGURE 3-2. TYPICAL INSTALLATION

3-3
VIBRATION ISOLATORS The isolators are adjusted by inserting the lev-
eling bolt through the skid and into the isolator
Installation and Adjustment Procedure (the leveling bolt’s locking nut should be
threaded up towards the bolt head).
1. Place the isolators (Figure 3-3) on the genset
support structure. The isolators should be The leveling bolt will adjust the clearance be-
shimmed or grouted to ensure that all of the iso- tween the top plate and the isolator base. A
lator bases are within 0.25 inch (6 mm) eleva- nominal clearance of 0.25 inch (6 mm) or great-
tion of each other. The surface on which the er is desired. This will provide sufficient clear-
isolator bases rest on must also be flat. ance for the rocking that occurs during startup
2. Loosen the side snubber lock nuts so that the and shutdown. If the 0.25 inch (6 mm) clear-
top plate of the isolator is free to move vertically ance is not present, turn the leveling bolt until
and horizontally. Be sure that the top plate is the desired clearance is achieved.
correctly aligned with the base and springs. 5. The genset may not be level yet, therefore ad-
3. Place the genset onto the isolators while align- just the leveling bolts until the set is level and
ing the skid’s mounting with the threaded isola- sufficient clearance still remains. Once all iso-
tor hole. The top plates will move down and ap- lators have been set, then lock the leveling bolt
proach the base of the isolator as load is ap- in place with the lock nut.
plied. 6. The snubber nuts may remain loose and there-
4. Once the genset is in position, the isolators fore provide better isolation between the gen-
may require adjusting so that the set is level. set and support structure.

GENSET SKID

LEVELING BOLT

LOCK NUT

CLEARANCE
SNUBBER

BASE

M1828–1s

FIGURE 3-3. VIBRATION ISOLATORS

3-4
4. Mechanical Connections
GENERAL supply line to provide vibration isolation. Refer to
your generator set outline drawing for sizes and
The generator set mechanical system installation locations.
includes connecting the fuel, exhaust, ventilation
and cooling systems (Figure 3-2). Before starting CAUTION Never use galvanized or copper fuel
any type of fuel installation, all pertinent state and lines, fittings or fuel tanks. Condensation in the
local codes must be complied with and the installa- tank and lines combines with the sulfur in diesel
tion must be inspected before the unit is put in ser- fuel to produce sulfuric acid. The molecular
vice. structure of the copper or galvanized lines or
tanks reacts with the acid and contaminates the
FUEL SYSTEM fuel.
Cummins engines used on DF series generator An electric solenoid shutoff valve in the supply line
sets normally use ASTM No. 2 Diesel fuel. They will, is recommended for all installations and required for
however, operate on alternate diesel fuels within indoor automatic or remote starting installations.
the specifications shown in engine manual. Connect the solenoid wires to the battery run circuit
to open the valve during genset operation.
In all fuel system installations, cleanliness is of the
upmost importance. Make every effort to prevent Supply Tank
entrance of moisture, dirt or contaminants of any
kind. Clean all fuel system components before Locate the fuel tank as close as possible to the gen-
installing. set and within the 5 foot (1.5 m) lift capacity of the
fuel pump. Install a fuel tank that has sufficient ca-
Use only compatible metal fuel lines to avoid elec- pacity to keep the genset operating continuously at
trolysis when fuel lines must be buried. Use a flex- full load for at least 36 hours. Refer to product Spec-
ible section of tubing between the engine and fuel ification sheet for fuel consumption data.

INJECTOR FUEL
All models require a fuel return
RETURN LINE
line from injectors to tank.
VENTED
FILL CAP CONNECT TO
AC OUTPUT
FUEL PUMP
WATER/SEDIMENT VENT LINE
SEPARATOR

DAY TANK FLOAT


SWITCH FILL PIPE

FUEL TRANSFER SUPPLY


PUMP - ELECTRIC LINE
MOTOR DRIVEN

LARGER
OVERFLOW
LINE

FUEL TANK

ES-1214-2

FIGURE 4-1. TYPICAL FUEL SUPPLY INSTALLATION

4-1
WARNING Fuel leaks create fire and explosion The supply tank top must be below the day tank top
hazards which can result in severe personal in- to prevent siphoning from the fuel supply to the day
jury or death. Always use flexible tubing be- tank.
tween engine and fuel supply to avoid line fail-
ure and leaks due to vibration. The fuel system Provide a return line from the engine injection sys-
must meet applicable codes. tem return connection to the day tank (near the top).
Provide a day tank overflow line to the supply tank in
If the main fuel tank is installed below the lift capabil- case the float switch fails to shut off the fuel transfer
ities of the standard fuel transfer pump, a transfer pump.
tank (referred to as a day tank) and auxiliary pump
will also be required. If an overhead main fuel tank is WARNING Spilled fuel presents the hazard of
installed, a transfer tank and float valve will be re- fire or explosion which can result in severe per-
quired to prevent fuel head pressures from being sonal injury or death. Provide an overflow line
placed on the fuel system components. See Day to the supply tank from the day tank.
Tank and Figure 4-1.
Supply Tank Higher Than Engine: Install the day
Day Tank (If Used) tank near the generator set, but below the fuel injec-
tion system. Use fuel line at least as large as the fuel
Fuel day tanks are used when the standard engine pump inlet. The engine fuel return line must enter
fuel pump does not have the capacity to draw the the day tank.
fuel from the supply tank; or the supply tank is over-
head and presents problems of high fuel head pres- Include a shutoff valve in the fuel line between the
sure for the fuel return. fuel supply tank and the day tank to stop fuel flow
when the generator set is off.
Supply Tank Lower Than Engine: With this instal-
lation, the day tank is installed near the generator Engine Fuel Connections
set and within the engine fuel pump lift capability,
but below the fuel injection system. Install an auxil- Identification tags are attached to the fuel supply
iary fuel pump as close as possible to the supply line and fuel return line connections by the factory.
tank to pump fuel from the supply tank to the day Flexible lines for connecting between the engine
tank. A float switch in the day tank controls opera- and the stationary fuel line are supplied as standard
tion of the auxiliary fuel pump. equipment.

4-2
EXHAUST SYSTEM
Pipe exhaust gases to the outside of any enclosure. DRIP CAP
Locate the exhaust outlets away from any air inlets RAIN CAP
to avoid gases re-entering the enclosure. Exhaust HOLES IN
installations are subject to various detrimental con- END OF
INNER SLEEVE
ditions such as extreme heat, infrequent operation
and light loads. Regularly inspect the exhaust sys-
9 INCH MIN
tem both visually and audibly to see that the entire (230 mm)
system remains fume tight and safe for operation. VERTICAL
ROOF
WARNING Inhalation of exhaust gases can re-
sult in severe personal injury or death. Use ex-
treme care during installation to provide a tight 9 INCH MIN
exhaust system. Terminate exhaust pipe away (230 mm)
from enclosed areas, windows, doors and
vents.

Use an approved thimble (Figure 4-2) where ex-


haust pipes pass through wall or partitions. Refer to
NFPA 37, Section 6-3. “Stationary Combustion En- HORIZONTAL
gines and Gas Turbines” for accepted design prac-
tices. Build according to the code requirements in
effect at the installation site.
WALL OR PARTITION
WARNING Inhalation of exhaust gases can re- EXS-1036
sult in severe personal injury or death. Do not
use exhaust heat to warm a room, compartment
or storage area.
FIGURE 4-2. MOUNTING EXHAUST THIMBLE
Rain caps are available for the discharge end of ver-
tical exhaust pipes. The rain cap clamps onto the
end of the pipe and opens due to exhaust discharge
force from the generator set. When the generator
set is stopped, the rain cap automatically closes,
protecting the exhaust system from rain, snow, etc.

Use a section of flexible exhaust pipe between the


engine and remainder of exhaust system. Support
exhaust system to minimize weight applied to en-
gine exhaust outlet elbow/turbocharger connec-
tion.

CAUTION Weight applied to the engine man-


ifold can result in turbocharger damage. Sup-
port the muffler and exhaust piping so no
weight or stress is applied to engine exhaust el-
bow.

4-3
Avoid sharp bends by using sweeping, long radius IF EXHAUST LINE MUST BE
elbows and provide adequate support for muffler PITCHED UPWARD, CONSTRUCT
and tailpipe. Pitch a horizontal run of exhaust pipe A TRAP AT POINT OF RISE
DOWNWARD to allow any moisture condensation
to drain away from the engine. If an exhaust pipe
must be turned upward, install a condensation trap
at the point where the rise begins (Figure 4-3).
AVOID
Shield or insulate exhaust lines if there is danger of SHARP
personal contact. Allow at least 12 inches (305 mm) BENDS
of clearance if the pipes pass close to a combustible
wall or partition.
WARNING Exhaust pipes are very hot and they DRAIN CONDENSATION
can cause severe personal injury or death from TRAP PERIODICALLY
direct contact or from fire hazard. Shield or in-
sulate exhaust pipes if there is danger of per- EXS-1046s
sonal contact or when routed through walls or
near other combustible materials. FIGURE 4-3. CONDENSATION TRAP

VENTILATION AND COOLING


Generator sets create considerable heat that must
be removed by proper ventilation. Outdoor installa-
tions rely on natural air circulation but indoor instal-
lations need properly sized and positioned vents for
required airflow.

Vents and Ducts


For indoor installations, locate vents so incoming air
passes through the immediate area of the installa-
tion before exhausting. Install the air outlet higher
than the air inlet to allow for convection air move-
ment.

Size the vents and ducts so they are large enough to


allow the required flow rate of air. The “free area” of
ducts must be as large as the exposed area of the
radiator. Refer to the DF series Product Data
Sheets for the airflow requirements.

Wind will restrict free airflow if it blows directly into


the air outlet vent. Locate the outlet vent so the ef- CS-1366
fects of wind are eliminated. See Figure 4-4.

For operation outside a building, a shelter housing FIGURE 4-4. WIND BARRIER
with electrically operated louvers is available as an
option. Transformers connected across the genera-
tor output supply current to the motors.

4-4
Dampers nuts so duct can be removed for maintenance pur-
poses. The duct prevents circulation of heated air.
Dampers or louvers protect the genset and equip- Before installing the duct, remove the radiator core
ment room from the outside environment. Their op- guard.
eration of opening and closing should be controlled
by operation of the genset. Standard Radiator Cooling uses a set mounted
radiator and engine pusher fan to cool engine water
In cooler climates movable or discharge dampers jacket. Air travels from the generator end of the set,
are used. These dampers allow the air to be recircu- across the engine and out through the radiator. An
lated back to the equipment room. This enables the integral discharge duct adapter flange surrounds
equipment room to be heated while the genset en- the radiator grille.
gine is still cold, increasing the engine efficiency.
Remote Radiator Cooling (Optional) substitutes
Radiator Set Requirements a remote mounted radiator and an electrically driv-
en fan for the set mounted components. Removal of
Radiator set cooling air is drawn past the rear of the the radiator and the fan from the set reduces noise
set by a pusher fan that blows air through the radia- levels without forcing dependence on a continuous
tor (Figure 4-5). Locate the air inlet to the rear of the cooling water supply. The remote radiator installa-
set. Make the inlet vent opening 1-1/2 times larger tion must be completely protected against freezing.
than the radiator area.
Remote radiator plumbing will vary with installation.
Locate the cooling air outlet directly in front of the ra- Follow recommendations given in Application
diator and as close as possible. The outlet opening Manual T-030. See product data sheet for friction
must be at least as large as the radiator area. head and static head limits.
Length and shape of the air outlet duct should offer
minimum restriction to airflow. Before filling cooling system, check all hardware for
security. This includes hose clamps, capscrews, fit-
The radiator has an air discharge duct adapter tings and connections. Use flexible coolant lines
flange. Attach a canvas or sheet metal duct to the with heat exchanger, standpipe or remote mounted
flange and the air outlet opening using screws and radiator.

THERMOSTATIC AIR
RECIRCULATING
DAMPER *

WIND/
NOISE
BARRIER
INLET
AIR
DAMPER

HOT
AIR
COOL
AIR
D

* Louvers should close when DISTANCE SHOULD NOT


room ambient is above 60° F RADIATOR BE LESS THAN HEIGHT
FLEXIBLE DUCT
(16° C) OF RADIATOR
CONNECTOR CS-1382c

FIGURE 4-5. TYPICAL RADIATOR SET INSTALLATION

4-5
Water Jacket Heater (Optional) tubes. Engine coolant and raw water do not mix.
This type of cooling separation is necessary when
An optional water jacket heater can be installed to the raw water contains scale forming lime or other
keep the engine warm for starting under adverse impurities.
weather conditions. Connect the heater to a power
source that will be on when the engine is NOT run- This system can reduce set enclosure airflow re-
ning. quirements and noise levels. Proper operation de-
pends on a constant supply of raw water for heat re-
Heat Exchanger (Optional)
moval. Adjust the flow to maintain engine coolant
The optional heat exchanger (Figure 4-6) uses a temperature between165° F and 195° F (74° C and
shell and tube type heat exchanger instead of the 91° C) while viewing the water temperature gauge.
standard radiator and fan. Engine jacket coolant cir- The engine coolant side of the system can be pro-
culates through the shell side of the heat exchanger tected from freezing; the raw water side cannot be
while the cooling water is pumped through the protected.
VENTILATING
FAN

WATER WARM FLEXIBLE WA-


SOLENOID AIR TER
VALVE CONNECTIONS

MOUNTED HEAT
COOL AIR EXCHANGER

RAW WATER
SUPPLY
RAW WATER
DISCHARGE

FIGURE 4-6. TYPICAL HEAT EXCHANGER INSTALLATION

4-6
Coolant Filter
One spin-on type corrosion filter (Figure 4-7) is
standard equipment. This precharge filter is com-
patible with plain water and all ethylene glycol base
permanent antifreeze coolants. Refer to engine
manufacturer’s manual for instructions if a methoxy
propanal base antifreeze is desired. Replace filter
periodically as recommended in the Maintenance
section of the Operator’s manual.

Coolant Heater
A coolant heater is used to keep the engine coolant
warm when the engine is shut down. It heats and cir- COOLANT
culates the coolant within the engine. This reduces FILTER
startup time and lessens engine wear caused by SHUTOFF
VALVES
cold starts. It is electrically operated and thermo-
statically controlled. FILTER

WARNING The coolant heater must not be op-


NOTE: OPEN COOLANT FILTER SHUTOFF VALVES
erated while the cooling system is empty or BEFORE OPERATING GENERATOR SET.
when the engine is running or damage to the
CS-1198
heater will occur.
Figure 4-8 shows the heater line connections. Con- FIGURE 4-7. TYPICAL COOLANT FILTER
nect the heater to a source of power that will be on
during the time the engine is not running. Be sure
the voltage rating is correct for the heater element THERMOSTAT
rating.

1/2 NPT

OUTLET
(FOR 1” ID HOSE)

DRAIN

INLET
(FOR 1” ID HOSE)

CS-1367

FIGURE 4-8. TYPICAL COOLANT HEATER

4-7
4-8
5. Electrical Connections
GENERAL
The genset electrical system includes connecting LOAD
the load, installing the control wiring and connecting
the batteries. Connect the batteries last to avoid ac-
cidental starting of the unit during installation. NORMAL
SOURCE GENSET
WARNING Accidental starting of the generator
set while working on it can cause severe per-
sonal injury or death. Prevent accidental start-
ing by disconnecting the starting battery cables
(negative [–] first). NOTE: SHOWN WITH LINE
CONNECTED TO LOAD SC-1101-1

Arcing can ignite the explosive hydrogen gas


given off by batteries, causing severe personal
injury. Arcing can occur if the negative (–) bat- FIGURE 5-1. TYPICAL LOAD TRANSFER SWITCH
tery cable is connected and a tool being used to
connect or disconnect the positive (+) battery
cable accidentally touches the frame or other
grounded metal part of the set. To prevent arc-
ing, always remove the negative (–) cable first,
and reconnect it last.
CAUTION To prevent arcing, always discon-
nect a battery charger from its AC source before
disconnecting the battery cables. Otherwise,
disconnecting the cables can result in voltage
spikes high enough to damage the DC control
circuits of the set.
Most local regulations require that wiring connec-
tions be made by a licensed electrician and the
installation be inspected and approved before op-
eration. All connections, wire sizes, etc. must con-
form to the requirements of all electrical codes in ef-
fect at the installation site.

WARNING Improper wiring can cause a fire or


electrocution, resulting in severe personal inju-
ry or death and/or property and equipment dam-
age.

TRANSFER SWITCH
If the installation is for standby service, a transfer
switch is required for switching the load from the
normal power source to the generator set (Figure
5-1). Either a manual or automatic switch can be
used. Follow the installation instructions provided
with the transfer switch when connecting the load
and control wiring.

5-1
AC WIRING ers are labeled CT21, CT22 and CT23 on the wiring
diagram. Refer to Wiring Diagram section to identi-
Generator Voltage Connections fy the output leads that must be routed through each
current transformer, and also appropriate trans-
The generator output voltage and maximum current former post selection for meter lead harness con-
rating are specified on the generator set nameplate. nection. Use cable ties to secure the loose trans-
Line-to-neutral voltage is always the lower voltage formers to the generator output leads.
shown and line-to-line voltage is the higher rating.
Load Balancing
These generators can be configured for the volt-
ages shown in Wiring Diagram section. Most of When connecting loads to the generator set, bal-
these voltages must be reconnected by the installer ance the loads so the current flow from each line ter-
to give the voltage required by the installation. Be- minal (L1, L2 and L3) is about the same. This is es-
fore shipping, the factory tests the generator set pecially important if both single phase and three
output by connecting the generator to produce a phase loads are connected. Any combination of
particular test voltage. The generator may be con- single phase and three phase loading can be used
nected at the factory to produce a specified voltage as long as each line current is about the same, with-
per customer order. The installer must always in 10 percent of median value and no line current
check the stator lead terminal block connections exceeds the nameplate rating of the generator.
and perform any necessary reconnect to obtain the Check the current flow from each line after connec-
voltage desired. tions by observing the control panel ammeter.
Refer to Wiring Diagram section when reviewing Grounding
the voltage connection information; and use the
electrical schematic supplied with your generator Grounding involves making a conducting connec-
set when actually performing load connections. tion between the metal parts of the generator set or
one of its electrical circuits and the earth. The de-
CAUTION Reconnecting factory connected sign and installation of a grounding system is af-
generator sets to lower voltages can reduce set fected by many factors such as the use of multiple
ratings, and also render line circuit breakers too transformers, ground fault protection requirements
small. Consult with your distributor before per- and physical location of the generator. Follow the
forming reconnection for a different voltage. recommendations of the consulting engineer when
installing the grounding system.
Load Connections
WARNING Contact with electrical equipment
Connecting the Load: All loads are connected to can result in severe personal injury or death. It
the generator by bolting the load wires to the ap- is extremely important that bonding and equip-
propriate terminals on the generator terminal block. ment grounding be properly done. All metallic
The terminals are stamped U, V, W and N to indicate parts that could become energized under ab-
the line and neutral connections. (Reference: U, V, normal conditions must be properly grounded.
and W correspond with L1, L2 and L3; and N with L0
respectively). Typical requirements for bonding and grounding
are given in the National Electrical Code, Article
When installing sets with AC meters, the generator 250. All connections, wire sizes, etc. must conform
output leads must be routed through current trans- to the requirements of the electrical codes in effect
formers for proper meter operation. The transform- at the installation site.

5-2
DC WIRING inducing currents that could cause problems within
the control.
Remote Control Connections
Provisions are made inside the control box for add- Remote Monitor Connections
ing optional remote starting stations and alarms.
Connections are made on the terminal block (TB1) Provisions are made inside the control box for add-
located on the engine monitor circuit board (A11). ing optional remote monitoring on these gensets
Connect one or more remote switches across re- employing optional Detector 12 (12 lamp panel).
mote terminal and B+ terminal. Refer to Figure 5-2. Connections are made on the terminal block (TB2)
located on the engine monitor circuit board A11. Re-
If the distance between the generator set and re- fer to Figure 5-2.
mote stations is less than 1000 feet (305 m), use 18
gauge stranded copper wire. If the distance is 1000 CAUTION Do not install DC control wiring in
to 2000 feet (305 to 610 m), use 16 gauge stranded the same conduit as the AC power. AC voltage
copper wire. Always run control circuit wiring in a induced currents can create operational prob-
separate conduit from the AC power cables to avoid lems with electronic solid-state devices.
TB2
1 FAULT 2 - INPUT NON-TIMED
SHUTDOWN
2 FAULT 2 - OUTPUT
TB1 3 FAULT 1 - INPUT TIMED
7 B+ (DC POWER) 4 FAULT 1 - OUTPUT SHUTDOWN
6 RMT (REMOTE START) 5 LAMP TEST/RESET
5 GND (GROUND) 6 OVERCRANK
4 ALM (COMMON ALARM) 7 OVERSPEED
8 HIGH ENGINE TEMPERATURE
9 LOW OIL PRESSURE
10 PRE-HIGH ENGINE TEMPERATURE
11 PRE-LOW OIL PRESSURE
12 SWITCH OFF
13 LOW ENGINE TEMPERATURE

ENGINE 14 LOW FUEL - INPUT


CONTROL CONTROL 15 LOW FUEL - OUTPUT
PANEL BOX TB1 MONITOR 16 SHUTDOWN
A11

GROUND STUD
(USE GROUND
STUD OR A11-TB1-5
FOR CONTROL
GROUND WIRES)

A13 A14
INTERFACE
TB2
RELAY MODULES
ES-1561

FIGURE 5-2. REMOTE CONTROL AND REMOTE MONITOR CONNECTION POINTS

5-3
Battery Connections
Starting the unit requires 24 volt battery current.
Use two, 12 volt (Type 8D) batteries for a normal
installation (Figure 5-3). Connect the batteries in
series (negative post of first battery to the positive
post of the second battery) as shown in Figure 5-3.
POSITIVE
Necessary battery cables and rack are on the unit.
Service batteries as necessary. Infrequent use (as
in emergency standby service), may allow battery
to self-discharge to the point where it cannot start
the unit. If installing an automatic transfer switch
that has no built-in charge circuit, connect a sepa-
rate trickle charger. Onan automatic transfer
switches include such a battery charging circuit.
NEGATIVE
WARNING Ignition of explosive battery gases
can cause severe personal injury. Always con- TWO, 12 VOLT
nect battery negative last to prevent arcing. BATTERIES

WARNING Do not smoke while servicing the


ES-1865–1s
batteries. Explosive gases are emitted from bat-
teries in operation. Ignition of these gases can
cause severe personal injury. FIGURE 5-3. BATTERY CONNECTIONS

Control Heater (Optional)


A control heater provides a means of humidity/tem-
perature control of the control box interior. It pro- THERMOSTAT
tects the components and ensures their effective-
ness when the generator set is subjected to varying
ambient air conditions during extended periods of
non-use. The element is controlled by an adjustable
thermostat (Figure 5-4).
TO 120 VAC
SUPPLY

HEATER
ELEMENT
ES-1563s–3

FIGURE 5-4. OPTIONAL CONTROL HEATER

5-4
6. Prestart Preparation
GENERAL EXHAUST SYSTEM
Check the exhaust system for proper installation.
Before attempting the initial starting of the genera- Verify there is at least 12 inches (305 mm) clear-
tor set, be sure it is serviced and ready for operation ance between exhaust pipes and combustible ma-
(Figure 6-1). Perform the following: terials, and all connections are tight.

• Check ventilation and exhaust systems MECHANICAL CHECKS


• Check all mechanical connections Check the generator set for loose or damaged com-
• Fill the coolant, lubrication and fuel systems ponents and repair or replace as required.

• Prime the lubrication and fuel systems ELECTRICAL SYSTEM


• Check the fuel system for leaks Verify all electrical connections are secure and all
• Check the lubrication system for leaks wiring is complete and inspected. Replace and se-
cure any access panels that may have been re-
VENTILATION moved during installation.

Load Connections
Verify all air vents and ducts are open and free from
any obstructions. Verify dampers, if used, operate Check that load cables from generator set are prop-
properly. erly connected to either a transfer switch or circuit
breaker panel.

EXHAUST
SYSTEM

AIR INLET

AIR OUTLET
CHECK THAT ALL ASPECTS
• FILL COOLANT SYSTEM OF INSTALLATION ARE
• FILL AND PRIME LUBRICATION SYSTEM READY FOR OPERATION
• FILL AND PRIME FUEL SYSTEM
M-1808

FIGURE 6-1. TYPICAL INSTALLATION

6-1
Battery Connections
OIL SUPPLY INLET
LINE. DISCONNECT AT
Use two 12 volt batteries for a normal installation. THIS POINT TO PRIME
Connect the negative (-) battery cable last to reduce
the risk of arcing.

Service the batteries as necessary. If an automatic


transfer switch is not used or installed without a
built-in charge circuit, connect a separate float char-
ger to the battery.

COOLANT
TURBOCHARGER
Engine coolant is drained prior to shipment. Before HOUSING
starting, fill the cooling system with the recom-
mended coolant. See Operator’s manual Mainte-
nance section for more information.
PRIMING
PLUG
LUBRICATION
Engine oil is drained prior to shipment. Before start-
ing, fill and prime the lubrication system as follows:
1. Remove oil inlet line from turbocharger hous-
ing (Figure 6-2), fill bearing housing with clean OIL
FILTER
engine lubricating oil; replace line and secure.
2. Fill crankcase to “L” (low) mark on dipstick (Fig-
ure 6-3) and refer to Maintenance section in
B-342-3s
Operator’s manual for oil recommendations.
3. Remove plug from head of oil filter housing. FIGURE 6-2. PRIMING TURBOCHARGER
Connect a hand or motor driven priming pump,
equipped with pressure gauge, from a source
OIL
of clean lubricating oil to the plug boss in the fil- DIPSTICK
ter housing.
4. Prime until a 30 psi (207 kPa) pressure is ob-
tained.
5. Disconnect wire from fuel solenoid valve (Fig-
ure 6-4).
B3
6. On the engine control panel, depress the RUN
switch to crank the engine, while maintaining
an oil priming pressure of 15 psi (103 kPa) for
15 seconds, at filter head priming port.
7. Stop engine cranking, remove external priming STARTER
equipment, reinstall plug in filter housing and
torque to 15 to 20 ft lb (20 to 27 N•m).
8. Reconnect wire to fuel solenoid valve. B342–7s

9. Complete oil fill to “H” (high) mark on dipstick. FIGURE 6-3. OIL DIPSTICK LOCATION

6-2
FUEL
Fill the fuel tanks with the recommended fuel. En- FUEL SOLENOID
gine fuel may not be primed at the fuel filters after
shipment. To verify and reprime the fuel system per-
form the following procedure:
1. Remove each fuel filter and fill with clean fuel
(Figure 6-5).
CAUTION Due to the precise tolerances of
diesel injection systems, it is extremely im-
portant the fuel be kept clean and free of
water. Dirt or water in the system can cause
severe damage to both the injection pump
and the injection nozzles.
2. Put a light coat of fuel on the sealing gasket.
3. Install and tighten by hand until the gasket just
touches the filter head.
4. Tighten the filter an additional one-half to three-
fourths turn. FS1692s

FIGURE 6-4. FUEL SOLENOID VALVE LOCATION

SUPPLY LINE,
FILTER TO
INJECTION
PUMP

FUEL SUPPLY
INLET

FUEL FILTERS
FS1803s

FIGURE 6-5. FUEL FILTERS

6-3
6-4
7. Initial Start and Checks
Before putting the generator set under load condi- Frequency Meter
tions, verify the set will perform correctly by check-
ing the following areas. The generator frequency should be stable and the
reading should be the same as the nameplate rating
(50 or 60 hertz).
STARTING
AC Voltmeter
Move the Run/Stop/Remote switch on the engine
control panel to the Run position. The starter should Turn the phase selector switch to each line-to-line
crank the engine and the engine should start within phase selection shown on the volts scale (L1-L2 on
a few seconds. If after a few seconds of cranking the single phase sets; L1-L2, L2-L3 and L3-L1 on three
engine fails to start or starts, runs and then stops, phase sets). Read the AC voltmeter using the upper
refer to Troubleshooting charts in the Operator’s or lower scale as indicated by the scale indicator
Manual. light. At no load, the line-to-line voltage should be
the same as the set nameplate rating.
ENGINE GAUGES AC Ammeter
Check the following while the genset is operating: Turn the phase selector switch to each phase selec-
tion shown on the amperes scale (L1and L2 on
single phase sets; L1, L2 and L3 on three phase
Oil Pressure Gauge sets). Read the ammeter using the upper or lower
scale as indicated by the scale indicator light. At no
The oil pressure should be in the range of 40 to 60 load, the current readings should be zero. With a
psi (275 to 414 kPa) when the engine is at operating load applied, each line current should be approxi-
temperature. mately the same and no line current should exceed
the set nameplate reading.
Water Temperature Gauge
ENGINE MONITOR INDICATOR LAMPS
The water temperature should be in the range of Move the Run/Stop/Remote switch on the engine
165° to 195°F (74° to 91°C) depending on the load panel to the Stop position. Hold the Reset/Lamp
and ambient temperature. Test switch in the Test position. All indicator lamps
should light. Verify all the lamps are on and then re-
DC Voltmeter lease the switch. Contact your authorized service
center if any lamps require replacement.
This is a voltage reference gauge, indicating condi-
tion of the batteries and also of the battery charging EXHAUST SYSTEM
circuit. Gauge should read approximately 24 to 28
With the genset operating, inspect the entire ex-
volts while set is running. If reading is high or low,
haust system including the exhaust manifold, muf-
check batteries and the battery charging circuit.
fler, turbocharger and exhaust pipe. Visually and
audibly check for leaks at all connections, welds,
AC METERS (IF EQUIPPED) gaskets and joints. Make sure exhaust pipes are not
heating surrounding areas excessively. If any leaks
Note the AC instruments on the control panel. The are detected, have them corrected immediately.
frequency meter and voltmeter should indicate
rated nameplate frequency and voltage. Turn the WARNING Inhalation of exhaust gases can re-
control panel Voltage Adjust control (if equipped) for sult in severe injury or death. Inspect exhaust
nameplate voltage. Use the Phase Selector Switch system visually and audibly for leaks daily. Re-
to read each of the line-to-line voltages. pair any leaks immediately.

7-1
FUEL SYSTEM WARNING Ignition of explosive gases can
cause explosion and fire, resulting in severe
personal injury or death. Do not smoke while
With the genset operating, inspect the fuel supply servicing the batteries.
lines, filters and fittings for leaks. Check any flexible
sections for cuts, cracks and abrasions and make COOLING SYSTEM
sure they are not rubbing against anything that
could cause breakage. When the engine is first started, remove the radiator
pressure cap and monitor the coolant level. As
trapped air is expelled from the system, the coolant
WARNING Leaking fuel will create a fire hazard level will drop and additional coolant must be add-
that can result in severe personal injury or ed. Replace the pressure cap when the coolant lev-
death if ignited by a spark. If any leaks are de- el is stable.
tected, have them corrected immediately.
MECHANICAL ADJUSTMENTS

DC ELECTRICAL SYSTEM With the generator stopped, check for loose belts
and fittings, leaking gaskets and hoses, or any
signs of mechanical damage. If any problems are
With the generator set off, check the terminals on found, have them corrected immediately.
the battery for clean and tight connections. Loose or
corroded connections create resistance that can With the set running, listen for any unusual noises
hinder starting. Clean and reconnect the battery that can indicate mechanical problems. Check the
cables if loose. Always connect the negative battery oil pressure frequently. Refer to Operator’s or Ser-
cable last. vice Manual for required adjustments.

OIL PRES-
EXCITATION
SURE
FIELD
UPPER AND GAUGE
BREAKER RUN-STOP-REMOTE
LOWER SCALE
VOLTAGE INDICATOR LAMPS SWITCH RESET, LAMP TEST,
AC VOLTMETER ADJUST PANEL LAMP PANEL LAMP SWITCH
INDICATOR
LAMPS

AC AMMETER
COOLANT
TEMPERATURE
GAUGE

DC VOLTMETER

PHASE SELECTOR FREQUENCY


SWITCH
ADJUST
RUNNING TIME
METER
FREQUENCY METER
EMERGENCY STOP
PUSHBUTTON
WATTMETER
OTHER
OPTIONAL TACHOMETER
METERS OIL TEMP
GAUGE

FIGURE 7-1. CONTROL PANEL WITH OPTIONS

7-2
8. Wiring Diagrams
Reconnectible Voltages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-3
Non-reconnectible Voltages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-4

8-1
8-2
No. 625-2165 Sh 1 of 2
Rev. J Sys: Revisio
Modified 2/1994

RECONNECIBLE VOLTAGES

8-3
No. 625-2165 Sh 2 of 2
Rev. J Sys: Revisio
Modified 2/1994

NON-RECONNECIBLE VOLTAGES

8-4
Cummins Power Generation
1400 73rd Avenue N.E.
Minneapolis, MN 55432
1-800-888-6626
763-574-5000 International Use
Fax: 763-528-7229
Cummins is a registered trademark of Cummins Inc.

You might also like