3512C Generator Set LDJ00001-UP(SEBP5799 - 07) - Documentation Page 1 sur 1

Arrêter SIS

Ecran précédent

Produit: GENERATOR SET


Modèle : 3512C GENERATOR SET LDJ
Configuration: 3512C Generator Set LDJ00001-UP

Conduite et entretien
3512C Generator Set
Numéro d'imprimé -SEBU9095-00 Date de publication -01/11/2012 Date de mise à jour -03/12/2012

i00847451

Air Tank Moisture and Sediment - Drain - If Equipped


SMCS - 1466-543-M&S

Moisture and sediment in the air starting system can cause the following conditions:

• Freezing

• Corrosion of internal parts

• Malfunction of the air starting system

When opening the drain valve, wear protective gloves, a protective face
shield, protective clothing, and protective shoes. Pressurized air could
cause debris to be blown and result in personal injury.

1. Open the drain valve that is on the bottom of the air tank. Allow the moisture and sediment
to drain.

2. Close the drain valve.

3. Check the air supply pressure. The air starting motor requires a minimum of 620 kPa (90
psi) of air pressure to operate properly. The maximum air pressure must not exceed 1550
kPa (225 psi). The normal air pressure will be 758 to 965 kPa (110 to 140 psi).

Copyright 1993 - 2016 Caterpillar Inc. Wed Feb 24 21:56:38 UTC+0100 2016
Tous droits réservés.
Réseau privé pour utilisateurs autorisés de SIS.