O16178-080-U-D-00670-001
THERMAX LIMITED
WATER & WASTE SOLUTIONS


INDEX

SR.NO. CONTENTS
1.  OPERATION&CONTROLPHILOSOPHY
2. ANNEXURE1:SEQUENCEOPERATIONCHART


LEGENDSUSEDINTHEDOCUMENT:

LCP LocalControlPanel
SW Selectorswitch
SOC Sequenceoperationchart
PLC ProgrammableLogiccontroller
HRF HighRate Filter
OWS OperatorWorkStation




Page 1 of 9
THERMAX LIMITED
WATER & WASTE SOLUTIONS
1. OPERATION&CONTROLPHILOSOPHY


REFERENCES

Drawing/DocumentNo Title
BSPL&T10077/01A2408015DE P&IdiagramforHRF plant
02467,SH01
BSPL&T10077/01A2408015DE ProcessDesignBasisof HighRateFilter.
02467,SH02
BSPL&T10077/01A2400115BE P&IdiagramforIndustrialWater.
00040
BSPADPL10077/012400415DE P&IdiagramofContaminatedWaterSystemfor
00030 CCP(WTP4).


GENERALINFORMATION
TheoperationandcontrolofHRFPlantshallbethrough

A. PLC/DCSinAuto/ManualMode
B. LCPinLocalmode.

EachHRFisprovidedwithLocalControlPanel(LCP)formanualoperationfromfield.
WhenthereisselectioninLocal,ValveoperationfromON/OFFswitchprovidedonLCP

WhenthereisselectioninRemote,ValveoperationfromPLC


OPERATION&CONTROLPHILOSOPHY:

The plant operation shall be in AUTO cycle or Manual as per the Sequence Operation Chart
(SOC) attached below as Annexure 1. Plant operation in AUTO means that the units (vessels)
shalloperateinAutomaticwithoutmuchoperatorintervention.

Alltheunits(vessels)shallhavetheirownAUTOcycleandwillcontinuetorunaspertheprocess
requirement.OncetheSTARTcommandisgiventoAUTOcycleofaunit,therewillnotbeany
stoppingofthecycletillSTOPcommandisgiven,howeverforthesafetyofthesystemandto
maintain proper quality of the filter water during AUTO cycle operation, program will check if
requiredpermissivearehealthyornot.Keepinginmindtherequirementofcontinuousproduct
water.

Page 2 of 9
THERMAX LIMITED
WATER & WASTE SOLUTIONS
In AUTO mode after giving START common to selected filters first valve will be open as per
Annexure–1itwillbeactuatedSSTfeedpumpstostart(4W+3S).

For AUTO cycle operation, it is mandatory that the individual valves (not a part of sequence
operation)areselectedinAUTO.

If the permissive are not healthy at the start, the operation cannot be started. And if the
permissivegoesoutinbetweenthentheoperationisabortedwithanalarm.Inmanualmode,
all related valves and drives are kept in AUTO mode, the operation mode and the step are
selected and the start push button is pressed. The timer of the step can be changed at the
beginning.

TheoperationshallalwaysbecarriedoutinAUTO.MANUALselectionshallbechosen,only
whenmanualinterventionisrequiredduringtheoperation.


Philosophyforoperationofonoffvalves:

1. Onoff valves of units (except air release valves) – These valves shall open or close
AutomaticallyduringthesequenceoperationoftheunitsasshowninSOC.

Airreleaseineveryvesselistreatedasanindependentoperationandhenceairreleasevalve
operatelikeastandaloneonoffvalveasdetailedbelow.

2. Standaloneonoffvalves(notapartofanyunit)–

ThesevalvesshalloperateAutomatically(insequenceoperationorduetoprocessinterlocks)
or manually operated from OWS as per process requirement detailed below. Each of these
valves are provided with faceplate on OWS.  For standalone valves which operate both in
AUTOormanual,AUTO/MANUALselectionswitchshallbeprovidedonthefaceplate.When
selectedinAUTO,thecoloroftheselectorswitchshallbecomeGREENandwhenselectedin
MANUAL, the color shall become BLUE. For Automatic opening and closing of the valve,
selection switch shall be in AUTO position. For manual operation of the valve, the selector
switchshallbeinMANUAL.Oneno.softtogglePBisalsoprovidedonfaceplate.ThePBhas
gottwodisplays–OPEN&CLOSE.ClickonOPENconditionofthebuttontoopenthevalve.
Whentheopencommandhasgone,thePBdisplaychangestoCLOSE.Toclosethevalve,click
onPBshowingCLOSE.ThevalveclosesandthePBdisplaychangestoOPEN.

INPUT/OUTPUTFORVALVES
PLCwillreceivethefollowinginputfromValve:
Page 3 of 9
THERMAX LIMITED
WATER & WASTE SOLUTIONS
x ValveOpenfeedback
x Valveclosefeedback
PLCwillsendthefollowingoutputstoValve
x ValveOpen/Closecommand

HIGHRATEFILTERS(7701PSF4001A/B/C/D/E/F/G/H/I/J/K)(9W+2S)

TheoperationofallHRFsisidenticalandhencetheoperatingphilosophyofonlyoneunitis
describedhere.

The following signals are transmitted to PLC from field. Indications for each measurement
givenbelowshallbedisplayedonOWS.
1. InstantaneousflowatthecommonoutletofHRFsensedbyFT610.Whentheunitis
executing service step (Step A.2 of SOC), the totalised flow shall be calculated and
indicatedonPLC.Whenthetotalisedflowoftheunitexceedsthepresetvalues,high
alarmisannunciatedonPLC.
2. Diff. Pressure across inlet & outlet of HRF sensed by DPS609 , high alarm is
annunciatedonPLC.


EachHRFhastoperformthefollowingoperationsaspertheSequenceoperationchart(SOC)
giveninAnnexure1:


1. SERVICE(SequenceAofSOC)
2. BACKWASH(SequenceBofSOC)

AUTOOPERATION

To start AUTO operation, AUTO field in the service block has to be selected. Also click on
PERMISSIVEPBtocheckthestatusofthepermissivegivenbelow(colourgreenorred):

PermissivesforAUTOoperationofHRF:

1. DPacrossanyoftheHRFisnothigh.

Permissiveshallbecheckedbeforethestartofthebackwashsequence.

IntheAUTOblockofthefaceplate,followingfourPBsaredisplayed:
x STARTClickonthePBtoinitiatetheAUTOcycle
x STOPClickonthePBtostoptheAUTOcycleatanystage.
Page 4 of 9
THERMAX LIMITED
WATER & WASTE SOLUTIONS
ApartfromtheabovetwoPBs,onemorePBgetsactivatedwhenbackwashsequenceforHRF
isinitiated.
x HOLD  By this PB, the operator can extend a step (during the backwash sequence)
morethanthepresettimebyclickingtheholdbutton.Thisisalatchedtypesingle
PB.Clickoncetoputthesteponhold.WhiletheHOLDison,thesteptimerkeepson
showingtheelapsedtime.ToreleaseHold,clickthePBagain.AssoonastheHOLDis
released, the timer checks whether it has completed the elapsed time. If YES, the
sequencemovestothenextstep.IfNO,itcontinuestocompletethebalancetimeand
thenmovesfurther.
x SKIP–BythisPB,operatorcanskipaparticularstep(duringthebackwashsequence).
Forexample,ifstep1ofbackwashsequenceisrunning&operatordoesnotwantto
executestep2,thenbyclickingsoftpushbutton“SKIP”onthefaceplatewillskipstep
no.2afterexecutingstep1&programshalljumptostep3.

ClickingtheSTARTPBwillstarttheAUTOcycleandthesequencesshallbecarriedoutasper
SOC.


ChangeoverfromServicetoBackwashshalltakeplacebasedontimeasperSOC.

Note:Backwashintervalfortwofiltersshallbekept80Min(StarttoStart).Atatimeonly
onefiltercanbebackwashed.

1. TotalizedflowatHRFexceededcalculatedbyFT.
2. DPacrossDualMediaFilterhighalarmsensedbyDPS.

Allthestepsinthesequenceshallbetimerbasedi.e.,therunningstepchangesovertothe
nextstepwhentheelapsedtimereachesthepresettime.InAUTOoperationeachHRFshall
completethestepsasperSOCandduringbackwashthe“standBy1”HRFshallbeselected
into operation i.e. in “SERVICE” mode. Normally there shall be nine HRF which are in
“SERVICE”conditionandtwoshallbein“StandBy1”and“StandBy2”condition.Afterthe
backwashoftherespectiveHRFit shouldswitchoverto“StandBy2”conditionandatthe
sametimetheHRFwhichisin“StandBy2”conditionshallswitchoverto“StandBy1”ready
fornextserviceoperation.


Note:

x SERVICEandBACKWASHofHRFcannottakeplacesimultaneously
x WithoutthehealthinessofthePermissive,AUTOcyclewillnotstart.
Page 5 of 9
THERMAX LIMITED
WATER & WASTE SOLUTIONS
x DuringAUTOcycleIncaseofnonhealthinessofPermissive(DPSorFT)alarmshallbe
generatedandmanualinterventionrequiredtocarryoutthebackwash.
x INAUOTOcycle,duringthechangeoverfromSTANDBYtoMAINdelaytimeof5min
shallbeconsidered.
x PermissivePBcolourshallbegreenaftertheconditionsarehealthy.Ifthepermissives
arenothealthy,thePBcolourshallbered.
x Service step timer displayed in the faceplate showing the elapsed time has to be
retentive.ThetimershallgetresetwhenBackwashisinitiated.Forallthesequences
of HRF, only SERVICE step timer (A.2) is retentive and all otherstep timers are non
retentive.TheresettingoftimershallhappenirrespectiveofAUTO/manualoperation.


MANUALOPERATION:

To carry out manual operation, MANUAL field is selected. In manual operation, Service or
backwashsequenceofHRFshallbecarried outoneatatime.Alsobackwashof more than
one unit can’t be done simultaneously. Each step of a sequence (as given in SOC) shall be
selectedindependentlyandonlyonestepcanbeselectedatatime.Permissivedefinedabove
arealsoapplicableformanualoperation.

SERVICE:
Tostarttheserviceoperation,clickSERVICEfieldonthefaceplate.Thenthesteptobecarried
outshallbeselected.Inthemanualmode,thepresettimeissettable.Henceiftheoperator
wishestochangethedefaulttime(asshowninSOC),thesamecanbedone.
Afterallthesearedone,thefollowingtwoPBsontheSERVICEblockofthefaceplateareused
tooperateeachstep:
x START:Toinitiatethestep
x STOP:Tostopthestep.

FirsttheStepisselected.ThentheSTARTPBisclickedandthePLCgeneratescommandsto
the valves and drives of that step as per SOC. the step shall AUTOmatically stop as per the
presettime.ThestepcanalsobestoppedearlierbytheSTOPPB.
Thecompletionoftheservicerunshallbeannunciatedas“HRFSERVICECOMPLETED”.

BACKWASH:
AtatimeonlyoneHRFwillbetakenforbackwash.Toinitiatebackwashoperation,backwash
fieldoffaceplateisselected.
ThefollowingtwoPBsontheBackwashblockofthefaceplateareusedtooperateeachstep.
1. START:Toinitiatethestep.
2. STOP:Tostopthestep.
Page 6 of 9
THERMAX LIMITED
WATER & WASTE SOLUTIONS
FirsttheStepisselected.ThenSTARTPBisclickedandthePLCgeneratescommandstothe
valvesanddrivesofthatstepasperSOC.ThestepshallAUTOmaticallystopasperthepreset
timeorcanbestoppedearlierbytheSTOPPB.
Afterthecompletionofthelaststep,analarmisgenerated“HRFBACKWASHCOMPLETED”.

LOCALOPERATION:

TocarryoutLocaloperation,LCPisprovidedinField.

TheLCPisprovidedwith1noLocal/Remoteselectionswitchforselectionofoperation.
WhenthereisselectioninLocal,ValveoperationfromON/OFFswitchprovidedonLCP

The open /close  indication lamps have been provided in the LCP for each valve. Once the
valveisopentheindicationgreenlampshallglow&incloseconditionredlampshallglow

ThelampisprovidedintheLCPforDPSacrossthevessel.IftheDPacrossvesselishigh,the
indicationlampshallglowforlocalindication

HRFAIRBLOWER(7701AB4001A/B)(1W+1S):
Therearetwonos.airblowersprovidedforairscouringinHRFduringbackwashoperation.

Theblowershallbeoperatedin

AUTO – During the sequence operation as defined in SOC. Each blower shall be selected
eitherMAINorSTANDBY.
REMOTEMANUAL–START&STOPpushbuttonsconfiguredinOWS.
LOCAL–StopoperationthroughField

There is Onoff valve VA31 provided   drain line of the blowers. The valves shall operate
AutomaticallyduringtheregenerationsequenceasperSOC.

NOTES:
x ProcessParameters
NetcapacityofFiltrationPlant:2341.8m3/hr.(operating),
Capacityofeachfilter:260.2m3/hr(min.)&275m3/hr.(max)
OperatingCycle:12hrs,
x InterlocksandprotectionsshallbetakencareofP&IDofHighRateFiltrationPlant.




Page 7 of 9
THERMAX LIMITED
WATER & WASTE SOLUTIONS



ProcessParametersforDiff.Pressureswitch:
TAGNo. ProcessParameter(DifferentialPressureHighAlarm)(DPAH)
DPS609 0.8kg/cm2
DPS610 0.8kg/cm2
DPS611 0.8kg/cm2
DPS612 0.8kg/cm2
DPS613 0.8kg/cm2
DPS614 0.8kg/cm2
DPS615 0.8kg/cm2
DPS619 0.8kg/cm2
DPS616 0.8kg/cm2
DPS617 0.8kg/cm2
DPS618 0.8kg/cm2


ProcessParametersforMagneticFlowTransmitter:
TAGNo. FlowIndication(FI) FlowTotalize(FQAH)HighAlarm
FT610 260.2m3/Hr 3122.4m3/Hr
FT611 260.2m3/Hr 3122.4m3/Hr
FT612 260.2m3/Hr 3122.4m3/Hr
FT613 260.2m3/Hr 3122.4m3/Hr
FT614 260.2m3/Hr 3122.4m3/Hr
FT615 260.2m3/Hr 3122.4m3/Hr
FT616 260.2m3/Hr 3122.4m3/Hr
FT617 260.2m3/Hr 3122.4m3/Hr
FT618 260.2m3/Hr 3122.4m3/Hr
FT619 260.2m3/Hr 3122.4m3/Hr
FT620 260.2m3/Hr 3122.4m3/Hr










Page 8 of 9
THERMAX LIMITED
WATER & WASTE SOLUTIONS

InterlockList:
Interlock InterlockDescription.
No.
U101 DPAH609TOSTOPFILTERATIONOF7701PSF4001A
U102 DPAH610TOSTOPFILTERATIONOF7701PSF4001B
U103 DPAH611TOSTOPFILTERATIONOF7701PSF4001C
U104 DPAH612TOSTOPFILTERATIONOF7701PSF4001D
U105 DPAH613TOSTOPFILTERATIONOF7701PSF4001E
U106 DPAH614TOSTOPFILTERATIONOF7701PSF4001F
U108 DPAH615TOSTOPFILTERATIONOF7701PSF4001G
U109 DPAH619TOSTOPFILTERATIONOF7701PSF4001H
U110 DPAH616TOSTOPFILTERATIONOF7701PSF4001I
U111 DPAH617TOSTOPFILTERATIONOF7701PSF4001J
U112 DPAH618TOSTOPFILTERATIONOF7701PSF4001K
U113 FQAH610TOSTOPFILTERATIONOF7701PSF4001A
U114 FQAH611TOSTOPFILTERATIONOF7701PSF4001B
U115 FQAH612TOSTOPFILTERATIONOF7701PSF4001C
U116 FQAH613TOSTOPFILTERATIONOF7701PSF4001D
U117 FQAH614TOSTOPFILTERATIONOF7701PSF4001E
U118 FQAH615TOSTOPFILTERATIONOF7701PSF4001F
U119 FQAH616TOSTOPFILTERATIONOF7701PSF4001G
U120 FQAH617TOSTOPFILTERATIONOF7701PSF4001H
U121 FQAH618TOSTOPFILTERATIONOF7701PSF4001I
U122 FQAH619TOSTOPFILTERATIONOF7701PSF4001J
U123 FQAH620TOSTOPFILTERATIONOF7701PSF4001K


END
Page 9 of 9
ANNEXURE-1 -SOC
SHEET
NO LEGENDS & NOTES
1

LEGENDS

O OPEN
C CLOSE
M DRIVE SELECTED IN MAIN SHALL START

NOTES:

1 SEQUENCE OPERATION CHART SHALL BE READ IN CONJUNCTION WITH THE CONTROL PHILOSOPHY
2 'O','C','M'
O , C , M IN THE MATRIX INDICATES PLC OUTPUT IS HIGH (STATE 1).
3 VALVE POSITION / DRIVE STATUS INDICATES THE DEFAULT STATE OF THE ON-OFF VALVE / DRIVE
4 WHEN A DRIVE IS REQUIRED TO BE RUN FOR CONSECUTIVE STEPS, PLC OUTPUT SHALL BE HIGH EVEN DURING
DURING STEP CHANGEOVER
FILL

REFILL
SERVICE

DRAIN DOWN

AIR SCOURING
BLOWER START

BACKWASH 2 (WATER)
SERVICE MODE
7701-PSF-4001-A

BACKWASH MODE
STEP DESCRIPTION

BACKWASH 1 (AIR + WATER)


(7701-PSF-4001-A)
HIGH RATE FILTER - 1

4
2

6
1

5
3
2
1
A

B
2

2
2

5
1
1
2

15
NO

720
MINS
STEP
SHEET

STEP NO TIME IN

VALVE VALVE VALVE


TAG DESCRIPTION POSITION
7701-PSF-4001-A

O
O

VA1 SERVICE INLET CLOSE


O O

VA2 SERVICE OUTLET CLOSE


O O VA3 BACKWASH INLET CLOSE
O

VA4 BACKWASH OUTLET CLOSE


O O O
O O

VA11 AIR INLET CLOSE


O
O
O

VA12 AIR RELEASE CLOSE

OTHERS
C

VA31 BLOWER DRAIN OPEN


O

VA3A BACKWASH INLET COMMON CLOSE


O

VA3B BACKWASH INLET COMMON CLOSE

DRIVE DRIVE
TAG DESCRIPTION
M
M
M

7701-AB-4001A/B AIR BLOWER


FILL

REFILL
SERVICE

DRAIN DOWN

AIR SCOURING
BLOWER START

BACKWASH 2 (WATER)
SERVICE MODE
7701-PSF-4001-B

BACKWASH MODE
STEP DESCRIPTION

BACKWASH 1 (AIR + WATER)


(7701-PSF-4001-B)
HIGH RATE FILTER - 2

4
2

6
1

5
3
2
1
A

B
3

2
2

5
1
1
2

15
NO

720
MINS
STEP
SHEET

STEP NO TIME IN

VALVE VALVE VALVE


TAG DESCRIPTION POSITION
7701-PSF-4001-B

O
O

VA1 SERVICE INLET CLOSE


O O

VA2 SERVICE OUTLET CLOSE


O O VA3 BACKWASH INLET CLOSE
O

VA4 BACKWASH OUTLET CLOSE


O O O
O O

VA11 AIR INLET CLOSE


O
O
O

VA12 AIR RELEASE CLOSE

OTHERS
C

VA31 BLOWER DRAIN OPEN


O

VA3A BACKWASH INLET COMMON CLOSE


O

VA3B BACKWASH INLET COMMON CLOSE

DRIVE DRIVE
TAG DESCRIPTION
M
M
M

7701-AB-4001A/B AIR BLOWER


FILL

REFILL
SERVICE

DRAIN DOWN

AIR SCOURING
BLOWER START

BACKWASH 2 (WATER)
SERVICE MODE
7701-PSF-4001-C

BACKWASH MODE
STEP DESCRIPTION

BACKWASH 1 (AIR + WATER)


(7701-PSF-4001-C)
HIGH RATE FILTER - 3

4
2

6
1

5
3
2
1
A

B
4

2
2

5
1
1
2

15
NO

720
MINS
STEP
SHEET

STEP NO TIME IN

VALVE VALVE VALVE


TAG DESCRIPTION POSITION
7701-PSF-4001-C

O
O

VA1 SERVICE INLET CLOSE


O O

VA2 SERVICE OUTLET CLOSE


O O VA3 BACKWASH INLET CLOSE
O

VA4 BACKWASH OUTLET CLOSE


O O O
O O

VA11 AIR INLET CLOSE


O
O
O

VA12 AIR RELEASE CLOSE

OTHERS
C

VA31 BLOWER DRAIN OPEN


O

VA3A BACKWASH INLET COMMON CLOSE


O

VA3B BACKWASH INLET COMMON CLOSE

DRIVE DRIVE
TAG DESCRIPTION
M
M
M

7701-AB-4001A/B AIR BLOWER


FILL

REFILL
SERVICE

DRAIN DOWN

AIR SCOURING
BLOWER START

BACKWASH 2 (WATER)
SERVICE MODE
7701-PSF-4001-D

BACKWASH MODE
STEP DESCRIPTION

BACKWASH 1 (AIR + WATER)


(7701-PSF-4001-D)
HIGH RATE FILTER - 4

5
4

6
3
2
1
1
2
A

B
5

5
2
1
1
2
2

15
NO

720
MINS
STEP
SHEET

STEP NO TIME IN

VA
ALVE VALVE VALVE
TA
AG DE
ESCRIPTION POSITION
7701-PSF-4001-D

O
O

V
VA1 SERVIC CE INLET CLOSE
O O

VA2
V SERVIC CE OUTLET CLOSE
O O VA3
V BACKW WASH INLET CLOSE
O

VA4
V BACKW WASH OUTLET CLOSE
O O O
O O

VA
A11 AIR INLLET CLOSE
O
O
O

VA
A12 AIR RELLEASE CLOSE

OTHERS
C

VA
A31 BLOWE
ER DRAIN OPEN
O

VA
A3A BACKWA
ASH INLET COMMON CLOSE
O

VA
A3B BACKWA
ASH INLET COMMON CLOSE

DR
RIVE DRIVE
TA
AG DESCRIPTIION
M
M
M

7701-AB
B-4001A/B AIR BLO
OWER
FILL

REFILL
SERVICE

DRAIN DOWN

AIR SCOURING
BLOWER START

BACKWASH 2 (WATER)
SERVICE MODE
7701-PSF-4001-E

BACKWASH MODE
STEP DESCRIPTION

BACKWASH 1 (AIR + WATER)


(7701-PSF-4001-E)
HIGH RATE FILTER - 5

4
2

6
1

5
3
2
1
A

B
6

2
2

5
1
1
2

15
NO

720
MINS
STEP
SHEET

STEP NO TIME IN

VALVE VALVE VALVE


TAG DESCRIPTION POSITION
7701-PSF-4001-E

O
O

VA1 SERVICE INLET CLOSE


O O

VA2 SERVICE OUTLET CLOSE


O O VA3 BACKWASH INLET CLOSE
O

VA4 BACKWASH OUTLET CLOSE


O O O
O O

VA11 AIR INLET CLOSE


O
O
O

VA12 AIR RELEASE CLOSE

OTHERS
C

VA31 BLOWER DRAIN OPEN


O

VA3A BACKWASH INLET COMMON CLOSE


O

VA3B BACKWASH INLET COMMON CLOSE

DRIVE DRIVE
TAG DESCRIPTION
M
M
M

7701-AB-4001A/B AIR BLOWER


FILL

REFILL
SERVICE

DRAIN DOWN

AIR SCOURING
BLOWER START

BACKWASH 2 (WATER)
SERVICE MODE
7701-PSF-4001-F

BACKWASH MODE
STEP DESCRIPTION

BACKWASH 1 (AIR + WATER)


(7701-PSF-4001-F)
HIGH RATE FILTER - 6

4
2

6
1

5
3
2
1
A

B
7

2
2

5
1
1
2

15
NO

720
MINS
STEP
SHEET

STEP NO TIME IN

VALVE VALVE VALVE


TAG DESCRIPTION POSITION
7701-PSF-4001-F

O
O

VA1 SERVICE INLET CLOSE


O O

VA2 SERVICE OUTLET CLOSE


O O VA3 BACKWASH INLET CLOSE
O

VA4 BACKWASH OUTLET CLOSE


O O O
O O

VA11 AIR INLET CLOSE


O
O
O

VA12 AIR RELEASE CLOSE

OTHERS
C

VA31 BLOWER DRAIN OPEN


O

VA3A BACKWASH INLET COMMON CLOSE


O

VA3B BACKWASH INLET COMMON CLOSE

DRIVE DRIVE
TAG DESCRIPTION
M
M
M

7701-AB-4001A/B AIR BLOWER


FILL

REFILL
SERVICE

DRAIN DOWN

AIR SCOURING
BLOWER START

BACKWASH 2 (WATER)
SERVICE MODE
7701-PSF-4001-G

BACKWASH MODE
STEP DESCRIPTION

BACKWASH 1 (AIR + WATER)


(7701-PSF-4001-G)
HIGH RATE FILTER - 7

4
2

6
1

5
3
2
1
A

B
8

2
2

5
1
1
2

15
NO

720
MINS
STEP
SHEET

STEP NO TIME IN

VALVE VALVE VALVE


TAG DESCRIPTION POSITION
7701-PSF-4001-G

O
O

VA1 SERVICE INLET CLOSE


O O

VA2 SERVICE OUTLET CLOSE


O O VA3 BACKWASH INLET CLOSE
O

VA4 BACKWASH OUTLET CLOSE


O O O
O O

VA11 AIR INLET CLOSE


O
O
O

VA12 AIR RELEASE CLOSE

OTHERS
C

VA31 BLOWER DRAIN OPEN


O

VA3A BACKWASH INLET COMMON CLOSE


O

VA3B BACKWASH INLET COMMON CLOSE

DRIVE DRIVE
TAG DESCRIPTION
M
M
M

7701-AB-4001A/B AIR BLOWER


FILL

REFILL
SERVICE

DRAIN DOWN

AIR SCOURING
BLOWER START

BACKWASH 2 (WATER)
SERVICE MODE
7701-PSF-4001-H

BACKWASH MODE
STEP DESCRIPTION

BACKWASH 1 (AIR + WATER)


(7701-PSF-4001-H)
HIGH RATE FILTER - 8

4
2

6
1

5
3
2
1
A

B
9

2
2

5
1
1
2

15
NO

720
MINS
STEP
SHEET

STEP NO TIME IN

VALVE VALVE VALVE


TAG DESCRIPTION POSITION
7701-PSF-4001-H

O
O

VA1 SERVICE INLET CLOSE


O O

VA2 SERVICE OUTLET CLOSE


O O VA3 BACKWASH INLET CLOSE
O

VA4 BACKWASH OUTLET CLOSE


O O O
O O

VA11 AIR INLET CLOSE


O
O
O

VA12 AIR RELEASE CLOSE

OTHERS
C

VA31 BLOWER DRAIN OPEN


O

VA3A BACKWASH INLET COMMON CLOSE


O

VA3B BACKWASH INLET COMMON CLOSE

DRIVE DRIVE
TAG DESCRIPTION
M
M
M

7701-AB-4001A/B AIR BLOWER


FILL

REFILL
SERVICE

DRAIN DOWN

AIR SCOURING
BLOWER START

BACKWASH 2 (WATER)
SERVICE MODE
7701-PSF-4001-I

BACKWASH MODE
STEP DESCRIPTION

BACKWASH 1 (AIR + WATER)


(7701-PSF-4001-I)
HIGH RATE FILTER - 9

4
2

6
1

5
3
2
1
A

2
2

5
1
1
2
10

15
NO

720
MINS
STEP
SHEET

STEP NO TIME IN

VALVE VALVE VALVE


TAG DESCRIPTION POSITION
7701-PSF-4001-I

O
O

VA1 SERVICE INLET CLOSE


O O

VA2 SERVICE OUTLET CLOSE


O O VA3 BACKWASH INLET CLOSE
O

VA4 BACKWASH OUTLET CLOSE


O O O
O O

VA11 AIR INLET CLOSE


O
O
O

VA12 AIR RELEASE CLOSE

OTHERS
C

VA31 BLOWER DRAIN OPEN


O

VA3A BACKWASH INLET COMMON CLOSE


O

VA3B BACKWASH INLET COMMON CLOSE

DRIVE DRIVE
TAG DESCRIPTION
M
M
M

7701-AB-4001A/B AIR BLOWER


FILL

REFILL
SERVICE

DRAIN DOWN

AIR SCOURING
BLOWER START

BACKWASH 2 (WATER)
SERVICE MODE
7701-PSF-4001-J

BACKWASH MODE
STEP DESCRIPTION

BACKWASH 1 (AIR + WATER)


(7701-PSF-4001-J)
HIGH RATE FILTER - 10

4
2

6
1

5
3
2
1
A

2
2

5
1
1
2
11

15
NO

720
MINS
STEP
SHEET

STEP NO TIME IN

VALVE VALVE VALVE


TAG DESCRIPTION POSITION
7701-PSF-4001-J

O
O

VA1 SERVICE INLET CLOSE


O O

VA2 SERVICE OUTLET CLOSE


O O VA3 BACKWASH INLET CLOSE
O

VA4 BACKWASH OUTLET CLOSE


O O O
O O

VA11 AIR INLET CLOSE


O
O
O

VA12 AIR RELEASE CLOSE

OTHERS
C

VA31 BLOWER DRAIN OPEN


O

VA3A BACKWASH INLET COMMON CLOSE


O

VA3B BACKWASH INLET COMMON CLOSE

DRIVE DRIVE
TAG DESCRIPTION
M
M
M

7701-AB-4001A/B AIR BLOWER


FILL

REFILL
SERVICE

DRAIN DOWN

AIR SCOURING
BLOWER START

BACKWASH 2 (WATER)
SERVICE MODE
7701-PSF-4001-K

BACKWASH MODE
STEP DESCRIPTION

BACKWASH 1 (AIR + WATER)


(7701-PSF-4001-K)
HIGH RATE FILTER - 11

4
2

6
1

5
3
2
1
A

2
2

5
1
1
2
12

15
NO

720
MINS
STEP
SHEET

STEP NO TIME IN

VALVE VALVE VALVE


TAG DESCRIPTION POSITION
7701-PSF-4001-K

O
O

VA1 SERVICE INLET CLOSE


O O

VA2 SERVICE OUTLET CLOSE


O O VA3 BACKWASH INLET CLOSE
O

VA4 BACKWASH OUTLET CLOSE


O O O
O O

VA11 AIR INLET CLOSE


O
O
O

VA12 AIR RELEASE CLOSE

OTHERS
C

VA31 BLOWER DRAIN OPEN


O

VA3A BACKWASH INLET COMMON CLOSE


O

VA3B BACKWASH INLET COMMON CLOSE

DRIVE DRIVE
TAG DESCRIPTION
M
M
M

7701-AB-4001A/B AIR BLOWER