Supplement
Table of contents
1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
2 Physical interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4 Protocol specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
6.1 DOType . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
6.2 EnumTypes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
6.2.1 PhyHealth . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
6.2.2 CtlModelKind . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
1 Introduction
The technical file contains detailed descriptions for implementing the IEC
61850 interface protocol. The technical file applies to MMS Identify version
2.12.
This technical file is intended solely for specially trained and authorized per-
sonnel.
2 Physical interfaces
The device has been developed in accordance with applicable EMC stan-
dards. In regards to complying with EMC standards, please refer to the cor-
responding section on the topic of "Electromagnetic Compatibility" in the de-
vice's operating instructions.
Refer to the operating instructions provided with the device for further infor-
mation about the physical interfaces.
Please refer to the device's operating instructions for more information re-
garding setting the device parameters.
4 Protocol specification
The device provides an extract of commands and messages from the inter-
face protocol IEC 61850 for communication. The device supports IEC 61850
Edition 1 and IEC 61850 Edition 2. You can select the edition on the device.
Device-specific data points You can find the device-specific data points and presettings in the device's
ICD file. You can request the following documents for the device or down-
load from the device:
■ MICS (Model Implementation Conformance Statement)
■ PICS (Protocol Implementation Conformance Statement)
■ PIXIT (Protocol Implementation eXtra Information for Testing)
■ TICS (Technical Issues Conformance Statement)
Only the following elements may differ between the imported IED and the
exported IED from the TEMPLATE.icd:
■ DataSet elements can be created in each LN
■ ReportControl elements can be created in the LN containing the
associated DataSet
■ IP address (if this is not present, the preset one is used)
■ Subnet mask (if this is not present, the preset one is used)
■ Gateway IP address (if this is not present, the preset one is used)
■ Name of IED (IED name)
■ Name of access point (AccessPoint attribute name)
■ Name of logical device (LDevice attribute inst)
OSI-PSEL, OSI-SSEL, and OSI-TSEL cannot be adjusted.
A URCB, a BRCB, and a DataSet are created in LLN0 by way of example for
report use.
It may take several minutes to import a complete SCD file. The SCD file
should only contain the IEDs needed.
5 Data points
Please note possible restrictions and comments regarding device-specific
data points and default settings. You will find this information the documents
stated in the "Protocol specification" [► 7] chapter.
Measured values
- - - - -
Status information
Beh INS Behaviour (No value change) M -
Health INS Health (For all LNs the same value) M -
Loc SPS Local operation (For all LNs the O -
same value)
Settings
- - - - -
Table 4: LN0 - Logical node zero (LLN0)
Measured values
- - - - -
Status information
Beh INS Behaviour M -
Health INS Health M -
Ind1 SPS DI 1 (DIO 42-20) O -
Ind2 SPS DI 2 (DIO 42-20) O -
Ind3 SPS DI 3 (DIO 42-20) O -
Ind4 SPS DI 4 (DIO 42-20) O -
Ind5 SPS DI 5 (DIO 42-20) O -
Ind6 SPS DI 6 (DIO 42-20) O -
Ind7 SPS DI 7 (DIO 42-20) O -
Ind8 SPS DI 9 (DIO 42-20) O -
Ind9 SPS DI 10 (DIO 42-20) O -
Ind10 SPS DI 11 (DIO 42-20) O -
Ind11 SPS DI 12 (DIO 42-20) O -
Ind12 SPS DI 13 (DIO 42-20) O -
Ind13 SPS DI 14 (DIO 42-20) O -
Ind14 SPS DI 15 (DIO 42-20) O -
Ind15 SPS DI 17 (DIO 42-20) O -
Ind16 SPS DI 18 (DIO 42-20) O -
Ind17 SPS DI 19 (DIO 42-20) O -
Ind18 SPS DI 20 (DIO 42-20) O -
Ind19 SPS DI 21 (DIO 42-20) O -
Ind20 SPS DI 22 (DIO 42-20) O -
Ind21 SPS DI 23 (DIO 42-20) O -
Ind22 SPS DI 25 (DIO 42-20) O -
Ind23 SPS DI 26 (DIO 42-20) O -
Ind24 SPS DI 27 (DIO 42-20) O -
Ind25 SPS DI 28 (DIO 42-20) O -
Ind26 SPS DI 29 (DIO 42-20) O -
Ind27 SPS DI 30 (DIO 42-20) O -
Ind28 SPS DI 31 (DIO 42-20) O -
Ind29 SPS DI 33 (DIO 42-20) O -
Ind30 SPS DI 34 (DIO 42-20) O -
Ind31 SPS DI 35 (DIO 42-20) O -
Measured values
PPV DEL Phase to phase voltages (VL1VL2, O SIUnit: V
...) multiplier: none
PNV WYE Phase to neutral voltage E SIUnit: V
multiplier: none
A WYE Phase currents (IL1, IL2, IL3) O SIUnit: A
multiplier: none
TotW MV Total active power (total P) O SIUnit: Watts
multiplier: none
TotVAr MV Total reactive power (total Q) O SIUnit: VAr
multiplier: none
TotVA MV Total apparent power (total S) O SIUnit: VA
multiplier: none
TotPF MV Average power factor (total PF) O SIUnit: none
multiplier: none
Hz MV Frequency O SIUnit: Hz
multiplier: none
Measured values
- - - - -
Status information
Beh INS Behaviour M -
Health INS Health M -
OvVEx SPS Voltage high limit exceeded E -
UnVEx SPS Voltage low limit exceeded E -
OvAEx SPS Current overload E -
UnAEx SPS Current underload E -
OvVAEx SPS Apparent power high limit E -
exceeded
OvVA2Ex SPS Apparent power high limit 2 E -
exceeded
UnVAEx SPS Apparent power low limit exceeded E -
UnVA2Ex SPS Apparent power low limit 2 E -
exceeded
OvWEx SPS Active power high limit exceeded E -
OvW2Ex SPS Active power high limit 2 exceeded E -
UnWEx SPS Active power low limit exceeded E -
UnW2Ex SPS Active power low limit 2 exceeded E -
OvVArEx SPS Reactive power high limit exceeded E -
OvVAr2Ex SPS Reactive power high limit 2 E -
exceeded
UnVArEx SPS Reactive power low limit exceeded E -
UnVAr2Ex SPS Reactive power low limit 2 E -
exceeded
6 Extensions
6.1 DOType
dataNs was also added to DOTypes with the _ADD ending.
6.2 EnumTypes
6.2.1 PhyHealth
Value Description
0 Ok
1 Warning
2 Alarm
Table 15: PhyHealth EnumTypes
6.2.2 CtlModelKind
Value Description
0 status-only
1 direct-with-normal-security
2 sbo-with-normal-security
3 direct-with-enhanced-security
4 sbo-with-enhanced-security
Table 16: CtlModelKind EnumTypes
Glossary
ATCC
Automatic Tap Changer Controller
AVCO
Automatic Voltage Control
EMC
Electromagnetic compatibility
ICD
IED Capability Description
IED
Intelligent Electronic Device
IP
Internet Protocol
LLN0
System Logical Nodes, common
LPHD
System Logical Nodes, Physical Device
MMXU
Measurement Unit