DOCUMENT:-
GTP, QAP and Drawing - Inverter
DC
100%
DC AC AC EMI
EMI Filter Filter
Filter 98%
DC
M
Ef f iciency
L1 96%
DC DC DC Bus Inverter Circuit 1 AC
Fuse Switch DC SPD
(DC/AC) Breaker
L2
94%
Vdc=960V
L3
DC Vdc=1100V
92% Vdc=1300V
DC AC AC EMI AC SPD
EMI Filter Filter
Filter 90%
DC 0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
M
DC DC DC Bus Inverter Circuit 2 AC Normalized Output Power
Fuse Switch DC SPD
(DC/AC) Breaker
© 2020 Sungrow Power Supply Co., Ltd. All rights reserved. Subject to change without notice. Version 1.2
SG3125HV-32
© 2020 Sungrow Power Supply Co., Ltd. All rights reserved. Subject to change without notice. Version 1.2
1 2 3 4 5
A A
Module Area
2280
B B
2280
C C
2212
D
Front View D
1 2 3 4 5
1 2 3 4 5
A A
2363
1600
Temperature and Humidity Sensor
Smoke Detector
DC Inputs Area
B B
9-Ø17
86 86
231 7X86(=602) 50
667
626
642
C C
601
Internal
2330
External ground (M10)
ground (M6)
Left View
D D
1 2 3 4 5
1 2 3 4 5
A A
B B
C C
Back View
D D
1 2 3 4 5
1 2 3 4 5
A A
2363
1600 Smoke Detector
B
DC Inputs B
Area
2280
9-Ø17
550 550
86 86
55 55
317.2 7X86(=602) 50
667
626
550
550
C C
642
601
366
Internal
2330
External ground (M10)
ground (M6)
Exterior View Equipment View
Right View
D D
1 2 3 4 5
1 2 3 4 5
A A
AC Output and
Breaker Area
B B
DC Input DC Input
and Breaker and Breaker
Area Area
C C
Module Area
Top View
D D
1 2 3 4 5
1 2 3 4 5
A A
10-Ø15X30
M12 Bolts, Stainless steel are recommended
Anchoring of all 10 points to foundation mandatory 105
13 1092
8-Ø7X10 10X4 EPDM
Adhesive strips 105
7 10
10
45
313
200
339
15
62
30
1118
1079
1079
B B
DC input cover
1158
2363
196
6-Ø8
321
2
45
DC Input
DC Input
114
130
106
12
149
321
8
149
12
301 301
1016 1016 90
650
882
Communication input cover
435 902
C 569
C
AC Output
Exterior View Equipment View
Bottom View
D D
1 2 3 4 5
1 2 3 4 5
A A
B Nameplate B
View A View B
9-Ø17
9-Ø17
Negative
Positive Negative wiring Positive
wiring wiring copper wiring
copper copper bar copper
bar bar bar
100
100
4 5 86 86
86 86
317.2 7X86(=602) 50
7X86(=602) 5 4
231 50
148.5 96 96 148.5
667
667
626
626
601
601
642
642
601
601
DC input DC input
C C
(View A) (View B)
D D
1 2 3 4 5
1 2 3 4 5
A A
2363
1600
B B
2280
View C
550
110 110
10 55
4
10
10
550
C C
366
AC Output
(View C)
1 2 3 4 5
1 2 3 4 5
A A
1099.5
Detailed Diagram of
External AC Cable Box Assembly
Busbar insulator 1016.5 Wiring Copper Busbar
1077
B B
Vi e w A
(View A) (View B)
695.0
14.5
14.5 93 240 240 93 6
13
Ø8 4
105.5
C C
10
480.0 625.0
B
240
Vi e w
105.5
Paste a circle of EPDM strip
around (A eagle 10X4)
D D
1 2 3 4 5
1 2 3 4 5
A A
301 301
B B
1079
1079
C C
A A-A
Front A
DC Cable Entry
D D
1 2 3 4 5
1 2 3 4 5
A A
B B
TX
C C
D
Communication Interface D
1 2 3 4 5
1 2 3 4 5
DC
CT FUSE 400A
DC1+
2500A
A DC2+
DC MLBS 1
A
DC3+ ACB 1
2000 A
DC4+
DC5+ CT
Customer SCOPE
DC6+ CT
Note: Can use multiple
C
DC7+ CT L
DC8+
DC9+ windings for bigger block size
C C C
C
DC1- AC
K1
DC9- CAPS
PE FUSE
DC
PE
SPD 1 RESISTOR L1 AC OUTPUT
(Type I+II)
L2
GND
L3
DC
CT FUSE 400A Output Voltage
DC10+ AC SPD
2500A (Type II) · SG3125HV-31 : 630V
DC11+
DC MLBS 2 · SG3125HV-32 : 660V
DC12+ ACB 2
B 2000 A B
DC13+
DC14+ CT
DC15+ CT C
CT L
DC16+
DC17+
DC18+
MV Switchgears
C C C CCV
13.5~36kV
C 630A
DC10- AC
K1
DC18- CAPS
BR
V: Circuit
PE FUSE Breaker
Grid Connection/Disconnection
DC
SPD 2 RESISTOR
Control Signal
(Type I+II) C: Switch
GND Disconnector
C: Switch
Disconnector
DC Input
To another MV Station
Insulation
Monitoring DSP Control Unit To Main Switchgear
A1 B1 A2 B2 DC Power Supply
Net (From DC Busbar)
External Communication Interface
D D
1 2 3 4 5
1 2 3 4 5
A A
To Plant To Plant
Earthing Earthing
NOTE
* Earth Pit
B Equivalent GI Strip B
Equivalent GI Strip
Earth Pit
Side View
C C
To Plant To Plant
Earthing Earthing
D D
1 2 3 4 5
1 2 3 4 5
A A
1200
4675
1007
B 1300 1300 B
1214
3370
3297
1214
1200
1007
C C
No Obstacles within the boundary above
Note:.
Max Outside Dimension 1.In the Air-cooled system design, cold air enters the air duct from
(Door opening) the side of the box, and exits from the upper vent through the heat
sink;
2. The front and back sides should meet the 1.2 meters clearance, and
the left and right should meet 1.3 meters clearance
3. When the inverter is placed under the awning (shed), please ensure
that the distance from the top of the box to the awning is greater
than or equal to 1.0 meters
D D
1 2 3 4 5
1 2 3 4 5
A A
>2.5 m
>2.5 m
(Both Doors Open)
(Both Doors Open)
>1.5 m
>1.5 m
(One Door at a time)
(One Door at a time)
>2.5 m >4 m
Figure 1: Layout of doors with heat exchangers side by side Figure 2: The doors without heat exchanger are arranged side by side
B B
>2.5 m
(Both Doors Open)
>1.5 m
(One Door at a time)
>4 m
Figure 3: One door without heat exchanger and Other door with heat
exchanger are arranged side by side
1. Air cooling system design, cold air from the top side of the box into the air duct, through the internal fan spoiler from the bottom vents;
2. When two or more machines are installed side by side, first ensure that the doors do not interfere with each other, and then meet the cooling requirements:
The cooling requirements are as follows:
1) Figure 1: If the side-by-side layout with heat exchanger door body needs to meet the spacing of more than 2.5 meters (starting from the outside side panel
of the heat exchanger);
2) Figure 2: If there is no heat exchanger door body side-by-side layout to meet the spacing of more than 4 meters;
3) Figure 3: If there is no heat exchanger door body and with heat exchanger door body side-by-side layout needs to meet the spacing of more than 4 meters;
3. When the inverter is placed under the sunshade, make sure that the distance from the top of the enclosure to the sunshade is greater than or equal to 1.0
meters;
4. For Inverter Side to Side Spacing (The clearance between DC cabinets in Figures 1,2,3) : The spacing to open the DC Cabinet doors facing each other
D simultaneously should be more than 2.5 meters. D
Special Case : The spacing can be kept greater than 1.5 meters if only one door out of the two doors facing each other is opened at a time;
1 2 3 4 5
1 2 3 4 5
5172 4150 N
A A
1480
1480 1500
1450
1050
1020
1420
B B
5172
1500
900
300
220 223
200
106
106
200
4150
1500
1100
850
1100
1100
1450 1450
255
C C
120
500
200
1425
1425
D D
1 2 3 4 5
1 2 3 4 5
A A
B B
Lifting Lifting
point point
Sling1
Bottom View
Lifting instructions:
1. The specified built-in hanger (F-C-025673) must be used as shown in the diagram;
2280
C 2. The existing lifting points located at the bottom of the cabinet must be used for transport; C
3. The length of 4 equal length hanging ropes connected with the cabinet and hanger shall not be
less than 4.5m, and the load borne by the hanging rope shall not be less than 4t;
4. The ceiling of the hoisting rope of the cabinet shall be on the slot reserved by the wooden bar on
the top of the cabinet, which can prevent the swinging of the hoisting rope from scraping the cabinet;
5. After hoisting and positioning of the cabinet, the wooden strips on the top of both sides of the
cabinet shall be removed to avoid affecting the air inlet of the whole machine.
6. Avoid scraping with the inverter when positioning the lifting rope.
Front View
Hoisting
D D
1 2 3 4 5
SG3125HV-31 and SG3125HV-32
Characteristic Curve
Technical Information
Version 1.0
Confidential
1.Introduction
This document describes the characteristics curves for the SG3125HV-31, SG3125HV- 32,including inverter
temperature dependent derating behavior, DC voltage dependent derating behavior, altitude dependent derating,
Grid Voltage Derating Curve.
This document is intended to be used by the specific addressees. No part of this document may be reproduced or
distributed in any form or by any means without the prior written permission of Sungrow Power Supply Co., Ltd.
2.Characteristic Curves
SG3125HV-32
3781
3437
3125
2500
S[kVA]
1875
1250
Vmpp :960-1300V
625
SG3125HV-31
3610
3437
3125
2500
S[kVA]
1875
1250
Vmpp :915-1300V
625
1
Confidential
SG3125HV-32
3781
3125
2500
S[kVA]
1875
1250
625
312
SG3125HV-31
3610
3125
2500
S[kVA]
1875
1250
625
312
SG3125HV-32
3781
3437
3125
2812
2218
S[kVA]
1875
1250
30℃
625 45℃
50℃
2
Confidential
SG3125HV-31
3610
3437
3125
2812
2218
S[kVA]
1875
1250
30℃
625 45℃
50℃
SG3125HV-32
3781
3214
2500
S[kVA]
1875
1250
625
3
Confidential
SG3125HV-31
3610
3065
S[kVA] 2500
1875
1250
625
4
SG3125HV-31 and SG3125HV-32
P-Q Diagram
Technical Information
Version 1.0
Confidential
1.Introduction
This document describes the P-Q diagram used for SG3125HV-31, SG3125HV-32.
This document is intended to be used by the specific addressees. No part of this document may be reproduced or
distributed in any form or by any means without the prior written permission of Sungrow Power Supply Co., Ltd.
2.P-Q Capability
Inverter can support the grid by supplying the reactive power in different ways. The shaded area in the figure below
shows the inverter’s P-Q capability.
2750kW
2500kW
30°C
45°C
50°C
1875kVar Q (kVar)
Ind. 2269kVar 2062kVar
The Pmax=3781kW, Smax=3781kVA. The Max. Q is +/-2269 kVar, when the power factor is +/-0.8,at 30℃;
SG3125HV-31
3610kW P (kW)
3437kW 3610kVA
3125kW @PF=0.8
2888kW
2750kW
2500kW
30°C
45°C
50°C
The Max. Q is +/-2166 kVar, when the power factor is +/-0.8,at 30℃; The Q is +/-1574 kVar, when the power factor
is +/-0.9 at 30℃.
The Max. Q is +/-2062 kVar, when the power factor is +/-0.8,at 45℃; The Q is +/-1498 kVar, when the power factor
is +/-0.9 at 45℃.
The Max. Q is +/-1875 kVar, when the power factor is +/-0.8,at 50℃; The Q is +/-1362 kVar, when the power factor
is +/-0.9 at 50℃.
1
Confidential
30°C
45°C
50°C
1875kVar Q (kVar)
Ind. 2269kVar 2062kVar
The Pmax=3781kW, Smax=3781kVA. The Max. Q is +/-2269 kVar, when the power factor is +/-0.8 at 30℃;
SG3125HV-31
P (kW)
P=3610kW
P=3437kW 3610kVA
P=3125kW @PF=0.8
2888kW
2750kW
2500kW
30°C
45°C
50°C
The Max. Q is +/-2166 kVar, when the power factor is +/-0.8,at 30℃; The Q is +/-1574 kVar, when the power factor
is +/-0.9 at 30℃.
The Max. Q is +/-2062 kVar, when the power factor is +/-0.8 at 45℃; The Q is +/-1498 kVar, when the power factor
is +/-0.9 at 45℃.
The Max. Q is +/-1875 kVar, when the power factor is +/-0.8,at 50℃; The Q is +/-1362 kVar, when the power factor
is +/-0.9 at 50℃.
2
SG3125HV-30/-31/-32 Series Inverter
Q at Night
Technical Information
Version 1.0
Confidential
1.Introduction
This document describes the 'Q at Night' function of the PV inverter SG3125HV-30, SG3400HV-30, SG3125HV-31,
SG3125HV-32.
This document is intended to be used by the specific addressees. No part of this document may be reproduced or
distributed in any form or by any means, without the prior written permission of Sungrow Power Supply Co., Ltd.
In order to ensure the stability of the utility grid, the grid operators require the energy producer to support the grid by
generating a certain amount of reactive power; the reactive power is normally provided by Q at night.
For PV power plants, the PV inverters are required to operate as Q at night by using its inherent reactive power
capability; most of the PV inverters in the market would have this function as standard, but only for the daytime when
the PV inverters stay in feed-in-operation. the Q at night function is required as well at night to compensate the
reactive power based on the actual needs in order to support the grid.
The Q at night uses the full-control component IGBT to connect the inverter's main circuit to the grid in parallel
through the inductor, it controls the AC-side current to feed or absorb the set amount of reactive current, so as to
achieve dynamic reactive power compensation.
. . .
UI UL=jXI
X=ωL
+ - .
I .
Us
+ +
. . . . . .
Us UI Us UL=jXI I
- -
.
UI
Current leading Current lagging
Here, U̇s : grid voltage; U̇I : Q at night AC voltage output; U̇L : Inductor L voltage (phasor difference between U̇s and
U̇I ). I is the current passing through the inductor, as well as the current absorbed by the Q at night from the grid. By
controlling U̇L , the I can be controlled;
suppose the power loss caused by Q at night can be neglected, the amplitude and the direction of the current
absorbed from the grid by the inverter can be controlled by keeping the U̇s and U̇I at the same phase and
changing the amplitude of U̇I ,.
When U̇I < U̇s, the lagging current voltage is 90°, and it is operating in inductive condition, the Q at night will absorb
inductive reactive power.
When U̇I > U̇s, the leading current voltage is 90°, and it is operating in capacitive condition, the Q at night will
absorb capacitive reactive power.
When U̇I = U̇s and the current and voltage are in phase, the Q at night will not absorb reactive power.
1
Confidential
The inverter uses reactive current vector control to cause a phase difference between the inverter output voltage and
the grid voltage, thereby achieving the necessary reactive power compensation. This makes grid access more
friendly and can adapt to future grid system access requirements.
The 'Q at night' function requires the inverter to stay in feed-in operation without DC voltage present, which involves
additional hardware components and software development.
During the 'Q at night' mode, the DC inputs must remain disconnected to prevent the PV inverter from producing a
negative effect on components. The inverter's DC switches have an electric operation function, allowing the inverter
control system to control the DC switches.
Control Unit
DC AC
DC Switch AC Switch
The inverter allows the users to activate or deactivate the 'Q at night' function locally on the HMI menu or remotely
via upper PC.
2
Confidential
Step 4: Enable the 'Q-adjust switch' first, then enable the 'Q at night switch'.
Once the 'Q at night switch' is enabled,, the 'Q at night' function is always active until the ' Q at night switch' is set to
be disabled; when the DC input power drops to a preset value for a certain amount of time, the inverter will enter 'Q
at night' mode and compensate the reactive as required.
When the inverter first enters 'Q at night' mode, the DC switches will remain in the closed status. After the inverter
remains in 'Q at night' mode for the preset time period, the DC switches will be opened to disconnect it. This will
avoid unnecessarily opening the DC switch. During this process, the inverter will continue to input reactive power to
the grid according to grid scheduling requirements.
When the inverter is in 'Q at night' mode, it continues to detect whether or not the conditions for feeding the active
power are met, if all conditions are met, it will switch on the DC switches and enter active power feed-in mode.
Pdc<3kW/10min
or Pdc<10kW/30min
or Pac<6kW/1hour
sting Vpv>Upv_start
and T>Tstart
MPPT in operation
When Sungrow inverter is working in "Q at night" mode, the inverter supports the utility grid during an instant
grid-voltage drop. In this case, the inverter will stay connected with the grid and wait to restart feeding in reactive
power after the voltage drop or feed in reactive during the voltage drop in accordance with local grid codes. during
the LVRT (low voltage ride through), there must be a certain power supply to keep the inverter active.
3
SG3125HV-30/-31/-32 Series
Transformer Requirements
Technical Information
Version 1.0
Confidential
1.Introduction
This document describes the technical requirements of MV transformer which is connected with the SG3125HV-30,
SG3125HV-31, SG3125HV-32 outdoor inverter.
This document is intended to be used by the specific addressees. No part of this document may be reproduced or
distributed in any form or by any means without the prior written permission of Sungrow Power Supply Co., Ltd.
2.Transformer Requirements
2) In case anti-PID solution (potential induced degradation) is used, transformer secondary windings shall be able to
handle higher Vac peak voltage reference to the ground for the 1500V system. For SG3125HV-32, the voltage is
Vrms=860V (
2
VAN VNg
2
); For SG3125HV-31 , the voltage is Vrms= 850V (
2
VAN VNg
2
); For
continuous voltage of lightning protection devices for the LV side of the transformer should comply with this
requirement.
3) The output voltage of SG3125HV-32 is 660Vac L-L (561~726Vac), 50Hz or 60Hz. The output voltage of
( 510~660Vac) ,50Hz or 60Hz. The voltage at the MV side shall be in line with the MV grid voltage at the
4) Transformer capacity shall be in line with the inverters max. output power.
5) Two-winding (one for LV, one for MV side) transformer is to be used, no multi LV windings needed.
6) The Dy11 and Yd11 configurations can be used. In case the Y connection is on the LV side, the neutral point
3.125MVA
Inverter Transformer Grid
If two inverters with the same type are connected by a three-winding transformer, Dy11y11 and Yd11d11
connections can be used.
Inverter 1#
6.25MVA
Transformer Grid
Inverter 2#
7) For double split transformer, the L1-L2 impedance is recommended to be no less than 10% (based on the half of
the nominal transformer kVA rating) without negative tolerance.
1
Confidential
8) Short-circuit impedance Z(%) of transformer shall comply with related standards. For example, recognized
minimum short-circuit impedance of 5000kVA/33kV/0.6kV in IEC60076-5 is 7% with tolerance of +/-10%.
9) The transformer shall be capable of withstanding a certain level of harmonic current, the max. total harmonic
10) The transformer shall be able to withstand a certain level of DC component, 0.5% of fundamental current at
nominal power.
11) The transformer shall be able to withstand a certain phase imbalance, 5% of the current at nominal power.
12) The LV winding of the MV transformer shall withstand a voltage gradient dU/dt of up to 500V/μs to ground.
13) An electrostatic ground shield between the primary and secondary windings is recommended.
14) The transformer shall be grounded at only one point, and the grounding of the transformer must be secure.
15) The insulation class shall be at least F for dry type transformer, A for oil type.
Insulation class A E B F H N C
Max. temperature (˚C) 105 120 130 155 180 200 220
Temp. raise of winding (K) 60 75 80 100 125 135 150
16) The load Weighed efficiency shall be compliant with the latest local requirements.
17) The local environment (temperature, humidity, altitude, air etc.) shall be taken into consideration.
18) The temperature rise and min. electric clearance shall be taken into consideration especially when the altitude is
over 1000m.
19) The country specific grid frequency & standards shall be respected.
2
SG3125HV-32
Efficiency Curve
Technical Information
Version 1.0
Confidential
1.Introduction
This document describes the efficiency profile of SG3125HV-32, which is given for the minimum MPP voltage, the
rated input voltage and the maximum MPP voltage.
The European Efficiency is calculated by: η EU = (0.03 x η5%) + (0.06 x η10%) + (0.13 x η20%) + (0.1 x η30%)
+(0.48x η50%) + (0.2 x η100%)
This document is intended to be used by the specific addressees; No part of this document may be reproduced or
distributed in any form or by any means, without the prior written permission of Sungrow Power Supply Co., Ltd.
2.Curve Details
SG3125HV-32 efficiency test data at different power point and DC voltage level as below:
1
SG3125HV-31
SG3125HV-32
Power Consumption
Technical Information
Preliminary
Version 1.0
Confidential
1.Introduction
This document gives a brief introduction of the devices self-consumption of SG3125HV-31 and SG3125HV-32.
This document is intended to be used by the specific addressees. No part of this document may be reproduced or
distributed in any form or by any means without the prior written permission of Sungrow Power Supply Co., Ltd.
1
SG3400HV-30 and SG3125HV-30 Series
Insulation Monitoring and Negative Grounding
Technical Information
Version 1.0
1.Introduction
This document describes the Insulation Monitoring and Negative Grounding used for SG3400HV-30,
SG3125HV-30/31/32,SG2500HV-30, SG3000HV-30,SG3400HV-MV-30, SG3125HV-MV-30,,
This document provides instructions for PV inverter insulation monitoring and negative grounding equipment. It
primarily covers standard requirements, electrical principles, system component selection, system requirements,
and other detailed analyses and descriptions. This document aims to help customers understand the equipment
functions and provide guidance to customers during system design.
This document is intended to be used by the specific addressees. No part of this document may be reproduced or
distributed in any form or by any means, without the prior written permission of Sungrow Power Supply Co., Ltd.
2.Design Principles
Insulation Monitoring
The photovoltaic system's array insulation resistance monitoring function serves to reduce the risk of electric shock
or fire caused by DC-side ground faults.
For non-isolated inverters, DC-side ground faults form a loop between the fault point and electrical grid, directly
leading to a fault current. Non-isolated inverters must detect the array insulation resistance before connecting to the
grid. If the resistance falls below the threshold, the inverter shall trigger an alarm and shall not be operated
connected to the grid.
For isolated inverters, if the insulation is found to fall below the threshold, the inverter may continue to operate
connected to the grid, but it must continuously monitor the resistance and trigger an alarm.
According to section 4.8.2.1 in IEC62109-2, the minimum value set for the insulation resistance threshold must not
be lower than R=VMAX PV/30mA.
PV inverter insulation threshold value parameters are set according to the IEC62109-2 standard.
For grounded or non-grounded photovoltaic systems, when the ground fault leakage current exceeds a certain
threshold, the inverter will disconnect from the grid and trigger an alarm.
According to the provisions in section 4.8.3.5 in the IEC62109-2 standard, for Sn>30kVA inverters, when the array's
ground fault leakage current exceeds Sn*10mA/kVA, the inverter shall disconnect from the grid within 0.3 ms and
trigger an alarm.
Inverter has a built-in negative functionally grounding + insulation resistance monitoring module, as shown below.
N1
PV+
L1
MPPT1 L2
L3
PV-
NC
DC Contactor
K1 Insu lati on Control
Monitoring
Fuse
Resistor
N2
PV+
MPPT2
PV-
NC
DC Contactor
K1 Insu lati on Control
Monitoring
Fuse
Resistor
Before the inverter connection to the grid, the control unit issues a priority control signal to DC contactor K1 to open
K1's NC and thereby disconnect the circuit between the negative end and ground, the DC side can be seen as
floating system. At this time, the insulation monitoring units detects the positive to ground resistance R+ and
negative to ground resistance R- relatively. If the value of R+ and R- meets the setting threshold , the control unit will
send a control signal to the DC relay K1 to close K1, the DC side becomes a negative grounding system, then the
inverter connects to the grid.
The threshold of the positive to ground and negative to ground insulation resistance can be set by LCD, the default
value is 50K, and the setting range is 15K-100K. Please refer to the product user manual for specific setting
methods.
After the inverter connecting to the grid, the control unit can calculate the residual current by the negative to ground
voltage and the intentional resistance(this function can be called RCD), and determines whether the inverter needs
to indicate a fault alarm or disconnect from the grid according to the standard requirements.
1) Negative functionally grounding system can only be used on inverters with isolated transformers,at the
same time, an array residual current function (RCD) is required.
2) The RCD device is connected to the DC positive or negative ends to monitor and disconnect ground faults.
If the system is installed with a RCD device, the DC positive or negative ends cannot have another ground point.
3) Installing a RCD device will increase the system's overall AC-side ground potential, so this must be taken into
consideration when selecting the inverter's AC-side components.
For DC 1500V PV systems, the PV- and ground are equipotential and the maximum PV+ ground voltage is 1500V.
2 2
The rms value of inverter AC phase-to-ground voltage is Vrms=: (VDC / 2) + (Uac *1.1) . Uac is the grid's phase
voltage.
Taking the voltages above into consideration when selecting AC/DC lightning protection devices and cables. The
required DC withstand voltage is 1500Vdc and the AC withstand voltage must be no less than 842Vac. The DC
lighting protector must be a 2+1 model and the AC lightning protect must be a 3+1 model.
5.Conclusions
1) Functional ground safety complies with the requirements of the IEC62109-2 standard;
SG3125HV-30 Series
Key Components
Technical Information
V10
Confidential
1. Introduction
This document is intended to be used by the specific addressees; No part of this document may be
reproduced or distributed in any form or by any means, without the prior written permission of
Sungrow Power Supply Co., Ltd.
2. Key Components.
Manufacture/Specification Blank
The actual product might not use the main supplier, please refer to the actual scope of delivery.
2
公开 Public
出厂检验报告
Inspection Report
Q/SUNGROW 009.2-2021-001-V1.1 报告编号(Report No.):
产品名称 光伏并网逆变器
Product Name Grid-connected PV Inverter
产品型号 产品编号
SG3125HV-32
Product Model Product NO.
序
检验项目 标准要求 判定
号
Test Item Standard requirement Result
No.
机架组装有关零部件数量、质量均应符合各自的技术要求;
The quantity and quality of all accessories related to the device assembly meet their technical
requirements respectively;
油漆电镀应牢固、平整,无剥落、锈蚀及裂痕等现象;
Painting and electroplate are secure and flat without peeling, corrosion or cracks;
外观与结构检查
机架面板应平整,文字和符号要求清楚、整齐、规范、正确;
Inspection of
1 Racks and panels are flat, texts and symbols are legible, correct, regular and in line;
appearance and
标牌、标志、标记应完整清晰;
structure
Nameplates, labels and signs are intact and legible;
各种开关应便于操作, 灵活可靠;
Switches are easy and flexible to operate;
零部件牢固无松动。
Spare parts are secure.
输入电路对地、输出电路对地、输入电路对通讯端子、输出电路对通讯端子以及输入电路
绝缘电阻测试 与输出电路间的绝缘电阻应不小于 1MΩ。
2 insulation Inverter DC input to PE insulance value, AC output to PE insulance value, DC input to
resistance test communication terminal insulance value, AC output to communication terminal insulance value
and DC input to AC output insulance value should not be less than 1 MΩ.
输入电路对地、输出电路对地、输入电路对通讯端子、输出电路对通讯端子以及输入电路
工频耐受电压(绝
与输出电路间施加 DC2550V,无绝缘闪络、击穿及任何破坏性放电现象。
缘耐压测试)
3 When Inverter DC input to PE, AC output to PE, DC input to communication terminal, AC output
Dielectric strength
to communication terminal and DC input to AC output applied 2550Vdc , no insulation
test
flashover , breakdown or other destructive discharge is detected.
接地电阻测试(保
护连接) 所有可触及的活动金属零部件与接地导体间的电阻:不大于 0.1Ω;
4 Ground resistance The resistance between any touchable moving metal parts and grounding conductor should be
test (protection not greater than 0.1Ω
connection)
1/ 3
公开 Public
自动开关机及恢
复并网
逆变器根据电压输入情况,或故障及故障恢复后等情形,实现对应的自动开、关机操作。
Automatic
5 The inverter automatically starts up or shuts down based on the voltage input or fault or fault
startup/shutdown
recovery situation.
and Grid-tied
recovering
转换效率
逆变器转换效率最大值应不低于 98.5%。
6 Conversion
The maximum conversion efficiency is no less than 98.5%.
efficiency
谐波和波形畸变
逆变器设置额定功率工况下,总谐波小于 3%。
7 Total harmonics
Inverter should be set rated power. The THD is less than 3%.
distortion (THD)
电气参数及有功
逆变器设置额定功率工况下,最大输入电流或功率不超过标称最大输入值的 110%,输出电
功率容量
流不超过标称最大输出值的 110%,输出功率不超过标称额定输出功率的 110%。
Electrical
8 Inverter should be set rated power, the maximum input current or power cannot exceed 110%
parameters and
of the nominal maximum input. The output current cannot exceed 110% of the nominal
Active power
maximum output. The output power cannot exceed 110% of the nominal rated output power.
capacity
直流侧输入电压高于逆变器允许的接入电压最大值时,逆变器不得启动,同时发出警示信
直流过压保护 DC
号。
9 over-voltage
When the DC input voltage is higher than the maximum voltage, the inverter shall not startup
protection
and send warning signal.
当逆变器交流输出端电压超出规定的电压范围时,逆变器应停止向电网供电,同时发出警
示信号。此要求适用于多相系统中的任何一相。其对应的响应动作和(或)动作时间应符
交流过\欠压保护
合规范要求
AC output
10 When the AC grid voltage exceeds the specified voltage range of inverter, the inverter should
over-/under-
stop supplying power to the grid and send out a warning signal. This requirement applies to any
voltage protection
phase in a multi-phase system. the corresponding response actions and (or) action time should
meet the requirement.
交流过/欠频保护 逆变器交流电网端频率超限时,逆变器应在规定时间内停止向电网供电,当电网频率恢复
AC output 到允许运行的电网频率时逆变器应能启动运行。
11 overfrequency/un When the inverter AC grid frequency exceeds the specified frequency range of inverter, the
derfrequency inverter should stop supplying power to the grid within set time. The inverter should restart
protection operation when the grid frequency recovers to the allowable range.
2/ 3
公开 Public
门禁信号节点测
试 关闭所有装有行程开关的门,显示屏内门禁状态显示正确。
14 Access control Close all doors with access control switches and the doors states are displayed correctly in
system signal screen.
node test
稳定运行
额定功率运行 2 小时,逆变器正常工作。
15 Reliable operation
The inverter works normally for 2 hours at the nominal power.
test
出厂设置 时钟校准,故障记录及运行记录进行删除等恢复出厂值设置。
16
Default settings Clock calibration,delete all fault records and running records to return to the default setting.
结论 Conclusion:
3/ 3
MANUFACTURING QUALITY PLAN PROJECT
SL. COMPONENT & TYPE OF QUANTUM OF CHECK REFERENCE ACCEPTANCE FORMAT OF AGENCY
CHARACTERISTICS CLASS REMARKS
NO. OPERATIONS CHECK DOCUMENT NORMS RECORDS
M S/C M S C
1 2 3 4 5 6 7 8 9 ** 10 11
LEGEND:
** M: MANUFACTURER/ SUB-SUPPLIER, Atchayakumar David Mallikarjun
S: EPC/ INSPECTION AGENCY APPOINTED BY EPC
C: CLIENT.
P: PERFORM,
W: WITNESS
V: VERIFICATION. AS APPROPRIATE, PREPARED BY REVIEWED BY APPROVED BY
MANUFACTURER/ (QA-MANAGER) (QA-HEAD) (PROJECT MANAGER) APPROVAL SEAL -
SUB-SUPPLIER SEAL H: HOLD POINT- EPC SHALL IDENTIFY IN COLUMN “S” AS “H” CLIENT
MANUFACTURING QUALITY PLAN PROJECT
QUANTUM OF
SL. COMPONENT & TYPE OF REFERENCE ACCEPTANCE AGENCY REMARKS
CHARACTERISTICS CLASS CHECK FORMAT OF RECORDS
NO. OPERATIONS CHECK DOCUMENT NORMS
M S/C M S C
1 2 3 4 5 6 7 8 9 ** 10 11
Manufacturer
d HV Withstand Major Electrical As per As per Specifications / Specifications / Incoming Inspection
P V V
ISO2859-1 ISO2859-1 Approved Drawings Approved Drawings Report /
Comparative & Datasheet / IEC & Datasheet / IEC Supplier Test
e Major Electrical P V V
Tracking Index Certificate
1.03 Reactor / Capacitor
Specifications / Specifications /
Make Check & Approved Drawings Approved Drawings Manufacturer
a Major Visual 100% 100% P V V
Rating plate Check & Datasheet IS & Datasheet IS Incoming Inspection
5553 / IEC 60289 5553 / IEC 60289 Report /
Routine tests as per for reactors & for reactors & Supplier Test
b Major Electrical 100% 100% IS 15395 / IEC IS 15395 / IEC Certificate P V V
relevant standard
61642 for Capacitor 61642 for Capacitor
1.04 Air Break switches / Switch fuse unit / Indicating lamp / AC/DC Power & Auxiliary contactor
Manufacturer
Specifications / Specifications / Incoming Inspection
Rating, Make, Type
a Major Visual 100% 100% Approved Drawings Approved Drawings Report / P V V
Check
& Datasheet/ IEC & Datasheet / IEC Supplier Test
Certificate
LEGEND:
** M: MANUFACTURER/ SUB-SUPPLIER, Atchayakumar David Mallikarjun
S: EPC/ INSPECTION AGENCY APPOINTED BY EPC
C: CLIENT.
P: PERFORM,
W: WITNESS
V: VERIFICATION. AS APPROPRIATE, PREPARED BY REVIEWED BY APPROVED BY
MANUFACTURER/ (QA-MANAGER) (QA-HEAD) (PROJECT MANAGER) APPROVAL SEAL -
SUB-SUPPLIER SEAL H: HOLD POINT- EPC SHALL IDENTIFY IN COLUMN “S” AS “H” CLIENT
MANUFACTURING QUALITY PLAN PROJECT
1.05 Gasket
LEGEND:
** M: MANUFACTURER/ SUB-SUPPLIER, Atchayakumar David Mallikarjun
S: EPC/ INSPECTION AGENCY APPOINTED BY EPC
C: CLIENT.
P: PERFORM,
W: WITNESS
V: VERIFICATION. AS APPROPRIATE, PREPARED BY REVIEWED BY APPROVED BY
MANUFACTURER/ (QA-MANAGER) (QA-HEAD) (PROJECT MANAGER) APPROVAL SEAL -
SUB-SUPPLIER SEAL H: HOLD POINT- EPC SHALL IDENTIFY IN COLUMN “S” AS “H” CLIENT
MANUFACTURING QUALITY PLAN PROJECT
SL. COMPONENT & TYPE OF QUANTUM OF CHECK REFERENCE ACCEPTANCE FORMAT OF AGENCY REMARKS
CHARACTERISTICS CLASS
NO. OPERATIONS CHECK DOCUMENT NORMS RECORDS
M S/C M S C
1 2 3 4 5 6 7 8 9 ** 10 11
1.07 Electronic Cards
Specifications/
Specifications/
Manufacturer Manufacturer
Internal Quality As per As per Manufacturer
procedure for Incoming
a checks by Major Electrical ISO2859-1 ISO2859-1 procedure for testing P V V
testing of Inspection
manufacturer of electronics cards/
electronics cards/ Report
IEC
IEC
1.08 SPV Inverter - Power Module
Specifications/
Specifications/ Manufacturer
Approved
Approved Datasheet/ Incoming
Datasheet/
Manufacturer Inspection
a Quality Checks Major Electrical 100% 100% Manufacturer P V V
procedure for testing Report/
procedure for
of power modules/ Supplier Test
testing of power
IEC Certificate
modules/ IEC
1.09 C.T. / P.T.
Specifications/ Manufacturer
Routine tests & Specifications/
Approved Datasheet/ Incoming
type test as per Approved Datasheet/
Manufacturer Inspection
a relevant standard Major Electrical 100% 100% Manufacturer P V V
procedure for testing Report/
Magnetization procedure for testing
of power modules/ Supplier Test
curve for all CTs of power modules/ IEC
IEC Certificate
LEGEND:
** M: MANUFACTURER/ SUB-SUPPLIER, Atchayakumar David Mallikarjun
S: EPC/ INSPECTION AGENCY APPOINTED BY EPC
C: CLIENT.
P: PERFORM,
W: WITNESS
V: VERIFICATION. AS APPROPRIATE, PREPARED BY REVIEWED BY APPROVED BY
MANUFACTURER/ (QA-MANAGER) (QA-HEAD) (PROJECT MANAGER) APPROVAL SEAL -
SUB-SUPPLIER SEAL H: HOLD POINT- EPC SHALL IDENTIFY IN COLUMN “S” AS “H” CLIENT
MANUFACTURING QUALITY PLAN PROJECT
QUANTUM OF
SL. COMPONENT & TYPE OF REFERENCE ACCEPTANCE FORMAT OF AGENCY REMARKS
CHARACTERISTICS CLASS CHECK
NO. OPERATIONS CHECK DOCUMENT NORMS RECORDS
M S/C M S C
1 2 3 4 5 6 7 8 9 ** 10 11
2 IN-PROCESS CHECK
2.01 Equipment Mounting
Specifications/ Specifications/ Manufacturer
Verification of Rating &
Approved Drawings & Approved Drawings In-process
a Make of all components Major Visual 100% 100% P V V
Datasheet, GA, BOM/ & Datasheet, GA, Report/ QC
as per BOM
IEC BOM/ IEC Record
2.02 Busbar Support Insulator Fixing
Specification / Specification / Manufacturer
Checking of air gaps
Approved Drawings / Approved Drawings / In-process
a (clearance) & Creepage Major Measurement 100% 100% P V V
Manufacturer Standard Manufacturer Report / QC
distances
/ IEC Standard / IEC Record
2.03 Busbar Fixing
Torque value
Specification/ Specification/ Manufacturer
to be
Checking of busbar/ Approved Drawings / Approved Drawings/ In-process
a Major Mechanical 100% 100% P V V furnished by
Nut bolt tightness Manufacturer Standard Manufacturer Report / QC
the
/ IEC Standard/ IEC Record
manufacturer
2.04 Cable Termination
Checking of Power Specification/ Specification/ Manufacturer
cabling & Control/ Logic Approved Drawings/ Approved Drawings/ In-process
a Major Mechanical 100% 100% P V V
wiring termination by Manufacturer Standard Manufacturer Report/ QC
pull check / IEC Standard/ IEC Record
LEGEND:
** M: MANUFACTURER/ SUB-SUPPLIER, Atchayakumar David Mallikarjun
S: EPC/ INSPECTION AGENCY APPOINTED BY EPC
C: CLIENT.
P: PERFORM,
W: WITNESS
V: VERIFICATION. AS APPROPRIATE, PREPARED BY REVIEWED BY APPROVED BY
MANUFACTURER/ (QA-MANAGER) (QA-HEAD) (PROJECT MANAGER) APPROVAL SEAL -
SUB-SUPPLIER SEAL H: HOLD POINT- EPC SHALL IDENTIFY IN COLUMN “S” AS “H” CLIENT
MANUFACTURING QUALITY PLAN PROJECT
QUANTUM OF
SL. COMPONENT & TYPE OF REFERENCE ACCEPTANCE FORMAT OF AGENCY REMARKS
CHARACTERISTICS CLASS CHECK
NO. OPERATIONS CHECK DOCUMENT NORMS RECORDS
M S/C M S C
1 2 3 4 5 6 7 8 9 ** 10 11
2.05 Final Assembly
Degree of protection
c check including gasket Major Visual 100% 100% Specifications/ Specifications/ Manufacturer P V V
material & profile Approved Drawings & Approved Drawings In-process
Datasheet, GA, BOM/ & Datasheet, GA, Report/ QC
Functional checking of
d Major Electrical 100% 100% IEC BOM/ IEC Record P V V
SPV Inverter
Uploading of software
to control board &
checking of general
e Major Visual 100% 100% P V V
parameter setting
including protection
settings
LEGEND:
** M: MANUFACTURER/ SUB-SUPPLIER, Atchayakumar David Mallikarjun
S: EPC/ INSPECTION AGENCY APPOINTED BY EPC
C: CLIENT.
P: PERFORM,
W: WITNESS
V: VERIFICATION. AS APPROPRIATE, PREPARED BY REVIEWED BY APPROVED BY
MANUFACTURER/ (QA-MANAGER) (QA-HEAD) (PROJECT MANAGER) APPROVAL SEAL -
SUB-SUPPLIER SEAL H: HOLD POINT- EPC SHALL IDENTIFY IN COLUMN “S” AS “H” CLIENT
MANUFACTURING QUALITY PLAN PROJECT
SL. COMPONENT & TYPE OF QUANTUM OF CHECK REFERENCE ACCEPTANCE FORMAT OF AGENCY REMARKS
CHARACTERISTICS CLASS
NO. OPERATIONS CHECK DOCUMENT NORMS RECORDS
M S/C M S C
1 2 3 4 5 6 7 8 9 ** 10 11
3 TYPE & SPECIAL TESTS
*Type test & Special
test reports should be
of equipment having
similar Type, Rating,
Class to be supplied
Specifications/ Specifications/ under this contract
Review of Type Test
Approved Approved Type Test *All the reports for
a & Special Test Critical Verify 100% 100% P V/H* V
Drawings & Drawings & Reports Type test & Special test
Reports
Datasheet/ IEC Datasheet/ IEC should be within last
10 years of span
LEGEND:
** M: MANUFACTURER/ SUB-SUPPLIER, Atchayakumar David Mallikarjun
S: EPC/ INSPECTION AGENCY APPOINTED BY EPC
C: CLIENT.
P: PERFORM,
W: WITNESS
V: VERIFICATION. AS APPROPRIATE, PREPARED BY REVIEWED BY APPROVED BY
MANUFACTURER/ (QA-MANAGER) (QA-HEAD) (PROJECT MANAGER) APPROVAL SEAL -
SUB-SUPPLIER SEAL H: HOLD POINT- EPC SHALL IDENTIFY IN COLUMN “S” AS “H” CLIENT
MANUFACTURING QUALITY PLAN PROJECT
QUANTUM OF
SL. COMPONENT & TYPE OF REFERENCE ACCEPTANCE FORMAT OF AGENCY REMARKS
CHARACTERISTICS CLASS CHECK
NO. OPERATIONS CHECK DOCUMENT NORMS RECORDS
M S/C M S C
1 2 3 4 5 6 7 8 9 ** 10 11
4 ROUTINE TESTS
Dimensional check on 10% /
a Major Measurement 100% P W V
Enclosure Rating
Maximum
Verification of rating & make of 10% /
c Major Visual 100% P W V visible
all components as per BOM Rating
components
Degree of protection check Specifications/ Specifications/ Verify with
d including gasket material & Major Visual 100% Random Approved Drawings Approved Drawings P V V Type test
profile & Datasheet, GA, & Datasheet, GA, Routine design
Mechanical function & BOM/ IEC 62109/ BOM/ IEC 62109/ Test Report
interlocks of all components IEC 61683/ IEC IEC 61683/ IEC
e Major Visual 100% Random 61439 61439 P W V
Checking of doors and its
handles alignment
Testing the functionality of
f Major Testing 100% P W V
door instrumentation
10% of
Uploading of Software to Rating /
control board & checking of Panel
g Major Visual 100% P W V
general parameter setting
including protection setting
LEGEND:
** M: MANUFACTURER/ SUB-SUPPLIER, Atchayakumar David Mallikarjun
S: EPC/ INSPECTION AGENCY APPOINTED BY EPC
C: CLIENT.
P: PERFORM,
W: WITNESS
V: VERIFICATION. AS APPROPRIATE, PREPARED BY REVIEWED BY APPROVED BY
MANUFACTURER/ (QA-MANAGER) (QA-HEAD) (PROJECT MANAGER) APPROVAL SEAL -
SUB-SUPPLIER SEAL H: HOLD POINT- EPC SHALL IDENTIFY IN COLUMN “S” AS “H” CLIENT
MANUFACTURING QUALITY PLAN PROJECT
QUANTUM OF
SL. COMPONENT & TYPE OF REFERENCE ACCEPTANCE FORMAT OF AGENCY REMARKS
CHARACTERISTICS CLASS CHECK
NO. OPERATIONS CHECK DOCUMENT NORMS RECORDS
M S/C M S C
1 2 3 4 5 6 7 8 9 ** 10 11
Control circuit function check Each
including operation of Rating 1
h Major Testing 100% P W V
contactors, relays & circuit Panel /
breaker lot
LEGEND:
** M: MANUFACTURER/ SUB-SUPPLIER, Atchayakumar David Mallikarjun
S: EPC/ INSPECTION AGENCY APPOINTED BY EPC
C: CLIENT.
P: PERFORM,
W: WITNESS
V: VERIFICATION. AS APPROPRIATE, PREPARED BY REVIEWED BY APPROVED BY
MANUFACTURER/ (QA-MANAGER) (QA-HEAD) (PROJECT MANAGER) APPROVAL SEAL -
SUB-SUPPLIER SEAL H: HOLD POINT- EPC SHALL IDENTIFY IN COLUMN “S” AS “H” CLIENT
MANUFACTURING QUALITY PLAN PROJECT
COMPONENT
SL. TYPE OF QUANTUM OF CHECK REFERENCE ACCEPTANCE FORMAT OF AGENCY REMARKS
& CHARACTERISTICS CLASS
NO. CHECK DOCUMENT NORMS RECORDS
OPERATIONS M S/C M S C
1 2 3 4 5 6 7 8 9 ** 10 11
M/s Sungrow has to
ensure in all inverter
Ambient Temperature sensor
m Major Visual 100% 10% P W V temperature sensors
Location
are to be kept in
identical position.
Testing of wake-up/ auto
n start & stop with grid Major Testing 100% Specifications/ P W V
Specifications/
connectivity Approved
Approved
Command Signal check/ Drawings &
Drawings &
Manual switching ON/OFF Datasheet, GA, Routine
o Major Testing 100% Datasheet, GA, P W V
from Inverter display panel BOM/ IEC Test Report
BOM/ IEC 62109/
with grid connectivity 10% / 62109/ IEC
IEC 61683/ IEC
Testing of the optional Rating / 61683/ IEC
p Major Testing 100% 61439 P W V
emergency stop circuit Lot 61439
Each
Maximum power point Electrical
q Critical Rating 1 P W V 10% of load.
tracking test Test
Panel / lot
Demonstration Inverter
Electrical
r operation at DC threshold Critical 100% P W V
Test
voltage
LEGEND:
** M: MANUFACTURER/ SUB-SUPPLIER, Atchayakumar David Mallikarjun
S: EPC/ INSPECTION AGENCY APPOINTED BY EPC
C: CLIENT.
P: PERFORM,
W: WITNESS
V: VERIFICATION. AS APPROPRIATE, PREPARED BY REVIEWED BY APPROVED BY
MANUFACTURER/ (QA-MANAGER) (QA-HEAD) (PROJECT MANAGER) APPROVAL SEAL -
SUB-SUPPLIER SEAL H: HOLD POINT- EPC SHALL IDENTIFY IN COLUMN “S” AS “H” CLIENT
MANUFACTURING QUALITY PLAN PROJECT
LEGEND:
** M: MANUFACTURER/ SUB-SUPPLIER, Atchayakumar David Mallikarjun
S: EPC/ INSPECTION AGENCY APPOINTED BY EPC
C: CLIENT.
P: PERFORM,
W: WITNESS
V: VERIFICATION. AS APPROPRIATE, PREPARED BY REVIEWED BY APPROVED BY
MANUFACTURER/ (QA-MANAGER) (QA-HEAD) (PROJECT MANAGER) APPROVAL SEAL -
SUB-SUPPLIER SEAL H: HOLD POINT- EPC SHALL IDENTIFY IN COLUMN “S” AS “H” CLIENT
MANUFACTURING QUALITY PLAN PROJECT
LEGEND:
** M: MANUFACTURER/ SUB-SUPPLIER, Atchayakumar David Mallikarjun
S: EPC/ INSPECTION AGENCY APPOINTED BY EPC
C: CLIENT.
P: PERFORM,
W: WITNESS
V: VERIFICATION. AS APPROPRIATE, PREPARED BY REVIEWED BY APPROVED BY
MANUFACTURER/ (QA-MANAGER) (QA-HEAD) (PROJECT MANAGER) APPROVAL SEAL -
SUB-SUPPLIER SEAL H: HOLD POINT- EPC SHALL IDENTIFY IN COLUMN “S” AS “H” CLIENT
MANUFACTURING QUALITY PLAN PROJECT
LEGEND:
** M: MANUFACTURER/ SUB-SUPPLIER, Atchayakumar David Mallikarjun
S: EPC/ INSPECTION AGENCY APPOINTED BY EPC
C: CLIENT.
P: PERFORM,
W: WITNESS
V: VERIFICATION. AS APPROPRIATE, PREPARED BY REVIEWED BY APPROVED BY
MANUFACTURER/ (QA-MANAGER) (QA-HEAD) (PROJECT MANAGER) APPROVAL SEAL -
SUB-SUPPLIER SEAL H: HOLD POINT- EPC SHALL IDENTIFY IN COLUMN “S” AS “H” CLIENT
MANUFACTURING QUALITY PLAN PROJECT
LEGEND:
** M: MANUFACTURER/ SUB-SUPPLIER, Atchayakumar David Mallikarjun
S: EPC/ INSPECTION AGENCY APPOINTED BY EPC
C: CLIENT.
P: PERFORM,
W: WITNESS
V: VERIFICATION. AS APPROPRIATE, PREPARED BY REVIEWED BY APPROVED BY
MANUFACTURER/ (QA-MANAGER) (QA-HEAD) (PROJECT MANAGER) APPROVAL SEAL -
SUB-SUPPLIER SEAL H: HOLD POINT- EPC SHALL IDENTIFY IN COLUMN “S” AS “H” CLIENT
Heat Run test
Performance of inverters will be better when components are working in safe operating area (SOA).
Heat run test is carried out to measure temperature raise of major components in the factory ambient
temperature conditions at rated power (3125 kW,UPF).
T+ 0.5 hr
T+ 1 hr
T+ 1.5 hr
T+ 2 hr
T+ 2.5 hr
T+ 3 hr
T+ 3.5 hr
T+ 4 hr