Professional Documents
Culture Documents
CHAPTER TWO-WPS Office New
CHAPTER TWO-WPS Office New
2.1 Distribution networks carry power the last few miles from transmission or sub-transmission to
consumers. Power is carried in distribution networks through wires either on poles or, in many urban
areas, underground. Distribution networks are distinguished from transmission networks by their
voltage level and topology. Lower voltages are used in distribution networks, as lower voltages require
less clearance. Typically, lines up to 35 kV are considered part of the distribution network. The
connection between distribution networks and transmission or subtransmission occurs at distribution
substations. Distribution substations have transformers to step voltage down to the primary distribution
level (typically in the 4–35 kV range in the United States). Like transmission substations, distribution
substations also have circuit breakers and monitoring equipment. However, distribution substations are
generally less automated than transmission substations.
Distribution networks usually have a radial topology, referred to as a “star network,” with only one
power flow path between the distribution substation and a particular load. Distribution networks
sometimes have a ring (or loop) topology, with two power flow paths between the distribution
substation and the load.
Distribution system
The distribution system is the part of power system which distributes electric
power for domestic used (to consumer). It is the electric system between the
substation fed by the transmission system and the consumer meters. The
distribution system consists of feeders, distributors and the service mains.
- Feeders: these are the conductors which connect the source (distribution or
localized generating station) to the distributors serving a particular area.
- Service mains: this is the connecting wires or link between distributors and
the consumer’s terminals.
The supporting structure for overhead line conductors are various types of poles
and towers called line support.
i. Excitation test
ii. Ratio test
iii. Short circuit test
iv. Insulation test
Below are the explanation, practical aspects, equipment used and the
result obtained from the entire above listed test conducted on a
transformer
3.2 EXCITATION TEST
Insulation between the body of the transformer and bushing is 330 ohms.
Insulation between in the primary and secondary bushing is 350 ohms.
Note: if the meter reads less than 300ohms, it means the insulation is not okay
and need to be improved.
The purpose of short circuit test on the transformer is to confirm the current
carrying capacity of both primary and secondary windings.
By the name plate on the transformer, the power is 500KVA with voltage
rating 11/0.515 KV and current rating 26.24/696 amps, this means that the
primary current carrying capacity for the coils is 26.24 amps, and 696 amps for
the secondary windings. To ascertain this, short circuit test was conducted by
applying the three phases where the short circuited with a 50mm2 bare copper
conductor. This will provide a circuiting current path.
Result obtained:
Table 3.3: short circuit test result using three phases supply voltages
1069530
41200
= 25.959
= 26Amps.
11/
0.415kv transformer at primary. The actual current from the name place is
26.24Amps.
%deviation = actual current value obtained current value /actual current value
= 0.91%
This percentage value confirm that the primary winding of the transformer
were for the 500kva.
3.6 TRANSFORMERS
It consists of two (2) main sides’ primary and secondary side. And a
transformer can be step up or step down transformer by which the voltage in a
circuit with corresponding increase or decrease current.
Fig. 2. Transformer
1. Tank
5. Bushings CTs
6. Conservator
8. Cooling system
9. Fitments
Fuse: this is a device use to open a circuit by means of conductor designed to melt
when an excessive current flows through it. By the earliest means, fuse is called
protection against over currents in a conductor.
Basically, it’s consisting of short length of material often in the form of wire which
has a very small current which is greater than the current rating of the wire, the
wire will get out.
Fusing current: this is the maximum current that will cause the fuse to heat
and melt blow.
Fusing factor: this is the ratio of fusing current to the current rating.
Current rating: this is the current which the fuse element will carry
continuously without deterioration.
Types of fuse
Rewire able fuse: this consist of a porcelain bridge and base. The bridge has
two sets of copper contacts which is fit in to contact in the base.
Cartridge fuse: this type has come in to common use with the fuse 13A plug
used in the domestic ring circuit. The fuse element is contained in a
porcelain tube fitted with two connecting caps.
High breaking capacity (HBC) this type of fuse is designed to protect
circuit’s again heavy overloads and is capable of opening a circuit under
short circuit conditions without damaging surrounding equipment’s.
Fitting (J&P Fuse): this is a protective devices installed on overload line to
protect the transformer. The fuse taking in to consideration the rating of the
transformer to be protection
Marketing System
This section works hand in hand with function business unit. The duties of
this section are distribution of bill to various consumers’ premises and general
construction and reconnection of light or service mains.
i. Illegal service
Types of Disconnection
2.3 The following are the exercises performed and the experiences
acquired during my stay at the company:
i. Disconnection Exercise.
This is normally done to the users or consumers of PHCN and industries.
Disconnection normally occurs if the charge against the consumers is not settled or
a result of violation of the rules and regulations lay down by PHCN authorities.
The function of the feeder pillar is to take in a supply of electrical energy from a
transformer and distribute it, via fuseways, to a number of outgoing circuits,
providing each with a means of protection and control.
v. Phases.
In case of a three phase power supply, the combination of Red, Yellow and Blue
are used for the active line power conductors, Black color for neutral conductor
and Green or Green – Yellow for protective ground. All the above mentioned
color code for electrical wiring is to transmit AC current from the mains.