Professional Documents
Culture Documents
Spirax Sx25 Series Process Controller
Spirax Sx25 Series Process Controller
CH Issue 3
1. Safety Information
2. Installation
3. Electrical connections
4. Configuration
5. Operations
6. Commissioning examples
7. Automatic tuning
8. Technical specifications
Printed in theCH
IM-P323-25 UKIssue 3 © Copyright 20031
2 IM-P323-25 CH Issue 3
General Index
IM-P323-25 CH Issue 3 3
1. Safety Information
1.1 General
Please carefully read through the following before proceeding with the installation of the controller.
Your attention is drawn to Safety Information leaflet IM-GCM-10.
If the controller is handled improperly or not used as specified, the resultant may:
cause danger of the life and limb of the third party,
damage the controller and other assets belonging to the owner,
hinder the performance of the controller and control system.
1.2 Wiring notes
Every effort has been made during the design of the controller to ensure the safety of the user, but the following
precautions must be followed:-
i) Maintenance personnel must be suitably qualified in working with equipment containing hazardous live voltages.
ii) Ensure correct installation. Safety may be compromised if the installation of the product is not carried out as
specified in this manual.
iii) Isolate the controller from the mains supply before opening the unit.
iv) The controller is designed as an installation category II product, and is reliant on the building installation for over-
current protection and primary isolation.
v) Wiring should be carried out in accordance with IEC 60364 or equivalent. For installations in the US and Canada,
the controller must be wired in accordance with the Local and National Electrical Code (NEC) or the Canadian
Electrical Code (CEC).
vi) Fuses should be fitted in all phases. The instrument is protected with an internal fuse PTC, thermal protective
device. To protect the instruments internal circuits use 2A T fuses for Relay outputs and 1A T fuses for Triac
outputs. The Relay contacts are already protected with varistors. Fuses should not be fitted in the protective
earth conductor. The disconnection or removal of other equipment must not compromise the integrity of the
installation protective earth system.
vii) The mains cable connection at the rear of the controller must be retained in position (by tie wrapping Etc.) This will
prevent the high voltage cables at the rear of the controller from touching the SELV (Safe Extra Low Voltage)
connections, in the unlikely event of the terminals coming loose.
4 IM-P323-25 CH Issue 3
viii) A disconnecting device (switch or circuit breaker) must be included in the building installation. This must be
in close proximity to the equipment and within easy reach of the operator.
There must be a 3 mm contact separation in all poles.
It must be marked as the disconnecting device for the controller.
It must not interrupt the protective earth conductor.
It must not be incorporated into a mains supply cord.
The requirements for the disconnecting device are specified in IEC 60947-1 and IEC 60947-3 or equivalent.
ix) The controller must not be located in such a way that the disconnecting device is made difficult to operate.
The product may be exposed to interference above the limits of EN 61000-6-2 if:
The product or its wiring is located near to a radio transmitter.
Excessive electrical noise occurs on the mains supply.
Cellular telephones and mobile radios may cause interference if used within approximately one metre of the
product or its wiring. The actual separation necessary will vary according to the power of the transmitter.
Power line protectors (ac) should be installed if mains supply noise is likely.
Protectors can combine filtering, suppression, surge and spike arrestors.
IM-P323-25 CH Issue 3 5
2. Installation
2.1 General description
Installation must only be carried
out by qualified personnel.
6 IM-P323-25 CH Issue 3
2.2 Dimensional details 2.3 Panel cut-out
IM-P323-25 CH Issue 3 7
2.4 Environmental ratings
Operating conditions
Forbidden conditions
Corrosive atmosphere
Explosive atmosphere
8 IM-P323-25 CH Issue 3
2.5 Panel mounting
2.5.1 Insert the instrument 2.5.2 Installation securing 2.5.3 Clamps removing
1 Prepare panel cut-out 1 Fit the mounting clamps 1 Insert the screwdriver in the
2 Check front panel gasket position 2 Push the mounting clamps towards clips of the clamps
3 Insert the instrument through the panel surface to secure the 2 Rotate the screwdriver
the cut-out instrument
IM-P323-25 CH Issue 3 9
3. Electrical connections
3.1 Termination Unit
t
OP4 mA
(SX25 mA ONLY)
VMD
t
VMD
SX25-VMD t
Pt 100 Output onOP1:
OP3: t
SX25-mA
Output on OP4: mA
10 IM-P323-25 CH Issue 3
3.2 Precautions and advised
conductor course
Despite the fact that the instrument
has been designed to work in an harsh
and noisy environmental (level IV of the
industrial standard IEC 60801-4), it is
recommended to use the following
suggestions.
IM-P323-25 CH Issue 3 11
3.3 Wiring details
3.3.1 Power supply 3.3.2 PV control unit
Please read the safety information A For L-J-K-S-T thermocouple type
and the wiring notes before • Connect the wires with the polarity as
proceeding with the installation of shown
the controller. • Always use compensation cable of the
The controller provides switching correct type for the thermocouple used Wire
power supply with multiple isolation • The shield, if present, must be resistance
and internal PTC connected to a proper earth 150W max
• Nominal voltage 100 - 240V~ B For Pt100 temperature sensor
(-15% +10%) Frequency 50/60Hz • If a 3 wire system is used, always use
• Power consumption 1.6 W max cables of the same diameter (1 mm2 min.)
(line 20 W / lead maximum resistance) For 3 wires
• when using a 2 wire system, always use only 20 W / lead
cables of the same diameter 1mm2 maximum
(AWG 18) and link terminals 5 and 6 resistance
C For DT (2xRTD Pt100) Special
When the distance between the
controller and the sensor and the sensor Use wires of same
is 15 m, using a cable of 1mm2 length and 1mm²
(AWG 18) size.
(AWG 18) diameter, produces an
20W / lead
error on the measure of 1°C
maximum
R1 + R2 must be <320W
12 IM-P323-25 CH Issue 3
3.3.2 PV control unit
Rj >10MW
IM-P323-25 CH Issue 3 13
3.3.5 Output configuration OP2 output can be Relay or logic.
The 'jumper' on the auxiliary
The functionality associated to each of the outputs is defined during the
board selects the output type:
configuration of the instrument, index L (see section 4.1).
The suggested combinations are: Link Pins 1-2 for OP2-Relay
(Factory set)
Output Alarms
Link Pins 2-3 for OP2-Logic
Primary Secondary AL2 AL3
A Single Action Heat or Cool OP4 none none OP2 OP3
Jumper
SX25 mA
Note: With heat or cool control AL2 and AL3 share the same output.
14 IM-P323-25 CH Issue 3
SX25 mA Output combination
3.3.5 – A, B
OP4 Analogue mA control output 3.3.5 – C Double action analogue mA / relay control output
Galvanic isolation 500V~/1 min
0/4...20mA, (750W or 15V max)
load
coil
15
Relay output 2
load
SPST Relay N.O., 2A/250 V~ 16
coil
for resistive load, fuse 2A ~ T
3.3.5 – E Double action relay / analogue mA control output
Logic output not isolated
0...5V, ±20%, 30 mA max
OP2, use Relay (terminals 15,16) or
Logic (terminals 10,11) load
coil
3.3.5 – F Double action relay / analogue mA control output
15
2
load
16
coil
IM-P323-25 CH Issue 3 15
SX25 VMD Output combination
3.3.5 – G Valve Motor Drive 3.3.5 – H Single Action Relay 3.3.5 – I Single Action Logic
Relay / Relay Control Output Control Output Control Output
16 IM-P323-25 CH Issue 3
3.3.5 – L Double Action
Logic / Relay Control Output 3.3.6 Alarms outputs
Fuse
Relay Relay
Relay output
SPST Relay N.O., 2A/ 250 V~
for resistive load, fuse 2A ~ T 15
2
Logic output not isolated
16
0...5 V, ± 20 %, 30 mA max
Coil of the load Coil of the load
alarm contactor alarm contactor
IM-P323-25 CH Issue 3 17
3.4 Wiring examples 3.5 Auxiliary Relays for Valve Motor
Example 1. SX25-mA for Pressure control: Using a 4-20mA Drive actuators
pressure transmitter and a control valve with 4-20mA
Electric or Electro-pneumatic positioner.
SX25mA
18 IM-P323-25 CH Issue 3
4. Configuration
4.1 Configuration coding Input type and range I
RTD Pt100 IEC 60751 -99.9...300.0 °C -99.9...572.0 °F 0
The configuration code consists of RTD Pt100 IEC 60751 -200...600 °C -328...1112 °F 1
4 digits that identify the operating TC L Fe-Const DIN43710 0...600 °C -328...1112 °F 2
characteristic of the controller, as TC J Fe-Cu45% Ni IEC 60584 0...600 °C 32...1112 °F 3
chosen by the user. TC T Cu-CuNi -200...400 °C -328...752 °F 4
Refer to section 5.6 configuration TC K Cromel -Alumel IEC 60584 0...1200 °C 32...2192 °F 5
menu and section 6, TC S Pt10%Rh-Pt IEC 60584 0...1600 °C 32...2912 °F 6
commissioning examples for 0...20mA/0...50 mV, linear Engineering units 7
additional help. 4...20mA/»10...50 mV, linear Engineering units 8
Custom input and range [1] 9
[1] For example, other thermocouples types, DT (with 2 PT 100), custom linearisation etc.
SX25-VMD SX25-mA L
Control Output Output
mode configuration Alarms configuration Alarms
Control OP1 OP2, OP3 Control OP4 OP2, OP3 0
PID
Control OP2 OP1, OP3 Control OP4 OP1, OP3 1
Control OP1 OP2, OP3 Control OP4 OP2, OP3 2
ON - OFF
Control OP2 OP1, OP3 Control OP4 OP1, OP3 3
Control OP1-OP3 OP2 Control OP4-OP3 OP2 6
Heat / Cool
Control OP1-OP2 OP3 Control OP4-OP2 OP3 7
The configuration code can be Action
Control OP2-OP3 OP1 Control OP4-OP3 OP1 8
displayed on the front panel,
following the instructions on page PID VMD Control OP1-OP3 OP2 N/A N/A 9
22 section 5.2.2. Control action type M
2.5W Reverse (single action) Linear Cool (Heat / Cool double action) 0
1% shunt resistor must be fitted
for mA input signal. See section 3.3.2 Direct (single action) On-Off Cool (Heat / Cool double action) 1
IM-P323-25 CH Issue 3 19
Alarm 2 type and function N
Not active 0
When the controller is powered up Sensor break alarm/ Loop Break Alarm 1
for the first time, the display shows active high 2
the following message. Process
active low 3
active high 4
Deviation
active low 5
active out 6
Band
active in 7
CON2
Alarm 3 type and function O
Disabled 0
Sensor break alarm/ Loop Break Alarm 1
This shows that the controller has active high 2
not been configured. Process
active low 3
Input the first code ILMN , using the active high 4
Deviation
up and down arrow keys, then press active low 5
the enter key. The lower display will active out 6
show Con2 . Now input code O for Band
active in 7
alarm 3, then press enter.
The controller will remain in stand-by For alarm type and function see page 30.
until the configuration code is set
correctly (see section 5.6 page 36).
20 IM-P323-25 CH Issue 3
5. Operations
5.1 Keys and display overview
5.1.1 Key functions and display
in operator mode
IM-P323-25 CH Issue 3 21
5.2 Display 5.2.1 Process variables 5.2.2 Configuration codes
During the operation, the
parameters values cannot be
modified by the user Operator mode Operator
mode
Engineering Engineering
units [1] units [1]
Configuration
code
Note (see page 19)
[1] See table page 38
[2] This display is not shown if the
instrument has been configured Software
as an On - Off controller release
22 IM-P323-25 CH Issue 3
Operator
5.3 Parameter setting 5.3.1 Numeric entry mode
working Setpoint
(i.e. the modification of the displayed
Setpoint value from 275.0 to 240.0 )
Press or momentarily to
Local
change the value of 1 unit every push. Setpoint display
Continued pressing of or
changes the value, at a rate that
doubles every second. Releasing the Lower
button causes the rate of change to —Lower Setpoint
decrease. modification
In any case the change of the value
stops when it has reached the
max / min limit set for the parameter. Raise
IM-P323-25 CH Issue 3 23
5.3.2 Mnemonic codes setting
Engineering Degree
(e.g. configuration see page 36)
Units Fahrenheit
Degree
Press the or to display the Centigrade
next or previous mnemonic for the
selected parameter.
Degree no units
Continued pressing of or Fahrenheit defined
will display further mnemonics at a rate
of one mnemonic every 0.5 sec.
Degree
Centigrade
Ph
24 IM-P323-25 CH Issue 3
5.3.3 Keypad lock 5.3.4 Outputs lock 5.3.5 Auto / Man
To lock / unlock the keypad press The outputs are switched to the
Operator
the keys and OFF status by pressing the keys
mode
simultaneously for 2 seconds. and together.
To confirm the keypad lock / unlock When the outputs are locked, the
the display flashes once. message Off is displayed
instead of the Setpoint value. Select N¢ n
To unlock the outputs press both to switch to
keys simultaneously (the Soft-start manual mode
will be enabled).
IM-P323-25 CH Issue 3 25
5.4 Parameter menu
27.4.8 Operator
Auto/Man
selection
Note:
275.0
(see page 25)
mode
[1] This will not be displayed if the U
controller has been configured
with alarm 2 not active or if
A. 8n
sensor break type selected.
Digit N / M of the configuration
code is assigned to 0 or 1.
[2] Before Adpt is switched off,
note down the calculated
values. P.b., t.¡, t.d. are not
The parameter setting procedure automatically stored.
has a timeout. If no key is pressed
for 30 seconds, the controller
automatically switches back to the 0 1.00
A35.Pp t.d.
AL3 alarm Deriv
operator mode. threshold [1] (PID
(see page 30) Off / 0
After having selected the parameter
or the code, press and to 5.0 20
Proportional band Cycle
display or modify the value (see
page 24) The value is entered when p.b. (PID algorithm only)
0.5...999.9% of span
t.c. (time
algori
the next parameter is selected, by
pressing the key. 5.0 1.00
Overs
t.i. O.C.
Integral time
(PID algorithm only) (PID
Pressing the key, the next 0ff / 0.1...100.0 min 0.01..
group of parameters will be
displayed.
26 IM-P323-25 CH Issue 3
33 0
PP Ass
p A25.p
Password entry 1st GROUP
only if Code value AL2 alarm threshold
³ 5000 [1]
(see page 38) (see page 30)
5000
Code entry
from 5000 to 9999
Must be equal to
the value of the
parameter Code
OK
NO YES
60 1.0 100.0
N0U.t.0 r.C.w6a
Control output
Op. H
ivative time Valve travel time Cool relative gain
D algorithm only) (Valve motor drive only) (heat/cool configuration high limit
0.01 - 10.00 15...600 secs only) 0.1...10.0 (PID algorithm only)
10.0...100.0%
IM-P323-25 CH Issue 3 27
tun8
2nd GROUP
Tuning run / stop
(PID algorithm only)
Adpt
Continuous Tuning start / stop
(adaptive tuning)
(PID algorithm only)
OFFff
p.6. a
Calculated Proportional
sl. u
Setpoint ramp up
band [2] (display only) 0ff /0.1...999.9 digit/min
(available when adaptive
tuning is selected)
OFFff H. range
sl. Dd Ss.p. H
Setpoint high limit
t.i. A
Calculated Integral Time Setpoint ramp down
[2] (display only) 0ff / 0.1...999.9 digit/min s.p. l. ....high range
(available when adaptive
tuning is selected)
L. range 0.5
Ss.p. l A2hYy
Setpoint low limit
t.d. A
Calculated derivative AL2 Hysteresis
time [2] (display only) low range...s.p. H 0.1...10.0% of span
(available when adaptive
tuning is selected)
28 IM-P323-25 CH Issue 3
pass Password entry
only if Code value <5000
(see page 38).
Direct access
to the configuration
(pages 36 – 38)
none OFff
A2l.b
AL2 latching and Input shift
blocking functions
non£ / Ltch In.5h 0ff / -60...60 digit
bloc / Lt.bL
OFff
A3hy
AL3 hysteresis Error dead band
0.1...10.0% of span [1]
d.Err (PID algorithm only)
0ff / 0.1...10.0 digits
OFFff OFff
A3l.b
AL3 latching and Soft-start output value
blocking functions
non£ / Ltch
st.OPp 0ff / 0.1...100.0%
bloc / Lt.bL
OFFff 1
Soft-start
Tt.lbA
LBA delay
(see page 32)
0ff = sensor break
st.t0 activation time
(only if st.0p different
1...9999 sec LBA than 0ff) 1...9999 sec.
OFFff OF
t.fil sa.Op
Time constant Output safety value
input filter 0.0...100.0%
1...30 sec or 0ff (-100.0...100.0% for
heat/cool) Back to the 2nd parameter group
IM-P323-25 CH Issue 3 29
5.5 Parameter description Integral
First Group t.¡. time
The controller parameters have been
organised in groups, according to their The integral time value specifies the
functionality. time required by the integral term to
generate an output equivalent to
A2S.P AL2 alarm
threshold
the proportional term. When Off the
integral term is not included in the
Derivative
The alarms use OP1, OP2 and OP3 t.d. time
outputs in different ways, according to
The time required by the
the configured types of alarms, as
proportional term P to repeat the
illustrated.
output provided by the derivative
With double action control output,
term D. When Off the derivative
(VMD or heating and cooling).
term is not included in the control
There is only one control output left.
algorithm.
Alarm AL2 and AL3 will share the
same output. (see table on page 14). Control output
t.c. cycle time
Cycle time
t.c. C
Proportional cool
P.b band This is the cycle time of the logic
This parameter specifies the control output.
proportional band coefficient that
multiplies the error (SP - PV)
30 IM-P323-25 CH Issue 3
O.C. Overshoot control HY. Control output
A2hy
AL2
hysteresis alarm hysteresis
(Automatically disabled when the
Cool output AL3
adaptive tuning is running). hy. C hysteresis A3hy alarm hysteresis
This parameter specifies the span
of action of the overshoot control. Hysteresis of the threshold of both
The lower the O.C. value is, the the alarms, that activate OP1 and
smaller the overshoot will be during OP2 control output. It is specified as
a set point change.The overshoot a % of the full scale.
control doesn’t affect the PID
Setpoint
algorithm. If set to 1, the overshoot
control is disabled.
SP. L low limit
Heat / Cool Control or alarm output hysteresis Setpoint
d.bnd dead band span, set in % of the full scale. SP. H high limit
This parameter specifies the width
Setpoint Low / high limit of the Setpoint value.
of the deadband between the Cool SL. v ramp up AL2, AL3
and the Heat channel.
A2L.b latching
NU.tn Valve travel time Setpoint
SL. d and blocking
NU.HY Valve movement ramp down
A3L.b functions
sensitivity This parameter specifies the
Control output maximum rate of change of For each alarm it is possible to
OP. H high limit select the following functions
the Setpoint in digit / min.
Cool output When the parameter is Off, non£ none
OP.HC high limit this function is disabled. Ltch latching
This parameter specifies the
maximum value the control output
bloc blocking
can be set Lt.bL both latching and blocking
IM-P323-25 CH Issue 3 31
Second group
Ltch Latch Alarm Alarms with LBA (Loop Break Alarm) and Sensor Break Operation
Using the latch function, the alarm The Loop Break Alarm will detect faults in the input and output circuit of the
will remain energised after the controller.
alarm condition is no longer Select the code 1 on N or O configuration indexes (see page 20) to
present. To reset the latch, press select the Loop Break Alarm. The following parameter is then available.
any key and the alarm will switch
off. t.lba LBA delay
With the parameter set to OFF,
bloc Start up disabling This parameter will provide a the alarm will work with no
time delay [1] of 1 to 9999 sec to delay.
the Loop Break Alarm The alarm condition is indicated by
The alarm condition is indicated by the red alarm LED and the upper
the red alarm LED and the flashing display will show the following:
display.
32 IM-P323-25 CH Issue 3
Second group
Input filter Soft-start control The Soft-start function is a warm up
t.f ¡l time constant St.op output value phase after the controller is first
Set the value of the control ouput powered up.
This input filter provides a time
during the Soft-start activation time The Soft-start will set the control
constant (in seconds) to the PV input.
(in %). To de-activate the Soft-start, value to a desired position (ST.OP).
set to 'OFF'. for the set duration (St.tn).
Soft-start Output
st.tN sa0p Safety value
activation time
Set the time duration (starting at If the input signal fails, the control
power on) for the Soft-start function value can be set to a safe position
(in seconds). (in %).
in.sh Input shift
The value entered into this
parameter will offset the PV input
value. Its effect is to shift the whole
PV scale by ± 60 digits.
IM-P323-25 CH Issue 3 33
Heat cool control
Using one PID control algorithm, the A Heat /Cool actions separated C Cool action adjusting
controller can handle two different Insert positive d.bnd value Example with different relative cool gains.
outputs, one of these performs the (0...10%)
Heat action, the other one the Cool
action.
It is possible to overlap the
outputs.
The dead band parameter d.bnd is
the zone where it is possible to
separate or overlap the Heat and
Cool actions.
The Cool action can be adjusted
B Heat /Cool actions overlapped D On-Off Cool action
using the relative cool gain
Insert negative d.bnd value
parameter r.C.G¢ .
(-10...0%)
To limit the Heat and Cool outputs
the parameters Control Output High
Limit OP. H and Cool Control
Output High Limit 0p.HC can be
used.
When there is an overlap, the
displayed output OU t shows the
sum of the Heat and Cool outputs.
34 IM-P323-25 CH Issue 3
Analogue control output OP4
r£tr
Analogue control
output range
0-20 / 4-20
rt.H
Control output
selection
non£ Not used
N.U. Heat (single action)
N.U. C. Cool
IM-P323-25 CH Issue 3 35
5.6 Configuration menu
Operator
The configuration of the controller is Press or to display mode
Auto / Man
specified through a 4 digit code that the next parameter or the next selection
defines the type of input, of control (see page 25)
code and change its value.
output and of the alarms. The new value entered is stored
(section 4.1 page 19). into the controller when the next
parameter is selected by
pressing .
Pressing the will display
the next group of parameters.
Note:
You must remember
the password code.
If the code is changed
from 33, and the operator
forgets the code, Control output
he will be locked out selection
(only if installed)
of the controller. non£ Not used
N.U Heat N.U. C Cool
36 IM-P323-25 CH Issue 3
1st GROUP 2nd GROUP
Password entry
only if Cod£ value
³ 5000
(see page 38).
Direct access
to the configuration
Code entry if code ³ 5000
from 5000 to 9999
Must be equal to
the value of the
parameter Code.
No of decimals
(linear scale only)
0...3
IM-P323-25 CH Issue 3 37
Table 1 -
Password entry Supported Engineering Units.
only if Cod£ value
<5000 Centigrade degrees* °C
Fahrenheight degrees* °F
no units non£
Code entry mV nU
from 0 to 4999 (33 default
from factory)
Volt U
The entered password must mA NA
correspond to the one store
in the Cod£ parameter on Ampere A
NO YES page 36.
Bar bAr
PSI ps1
Rh rh
pH ph
Direct access to the configuration
A From parameter menu, "PASS" (see page 29). * For inputs from thermocouple or
B At the first power on when the resistance thermometer, the choice
controller is not configured: is between °C and °F only.
Notes
[1] Minimum Range 100 digits.
In this situation, the controller has its outputs and inputs not active. [2] To hide the parameters, change
This situation ends when a correct configuration code is entered.
the password to a number
between 5000 to 9999.
38 IM-P323-25 CH Issue 3
6. Commissioning Examples
When the controller is first powered To change the configuration code it 6.1 Example of pressure control
up the display will show: is necessary to access the for SX25-mA
configuration menu. Section 5.6
The SX25-mA controller is
shows how to access this menu.
monitoring system pressure with a
To configure the controller a code pressure transmitter, and provides
number must be entered into the a 4-20mA control signal to the
controller. The configuration code control valve.
ILMNO, covers the input type, the
Configuration Code and
control type, and the alarms.
parameters:
Refer to Configuration Coding, in
section 4.1 to select the desired Pressure transmitter 0 to 50 barg,
configuration settings. Selected producing a 4-20mA output signal.
This indicates that the controller codes should be recorded in the Control Valve with Electric or
is not configured (the controller customer configuration and Electro-pneumatic positioner
will not function without being parameter record sheet. accepting a 4-20mA input signal.
configured). The following show examples of Two Event alarms are required.
If on power up the display does commissioning the SX25 controller Event Y2 set for active high
not show the above, but instead providing guidance for similar process alarm at 25 bar with the
the operator mode (process applications. Latch function. Event Y3 set
variable and set point) is shown for active outside band alarm
it signifies that the controller has set at 5 bar.
already been configured. If this This process requires only one set
is the case it is unlikely that the point. The local set point is 20 bar
pre-set configuration will be
suitable for your application.
IM-P323-25 CH Issue 3 39
Configuration code This selects engineering units for the input signal. Using the table below
enter the following values into these parameters.
Using the and keys, enter
the first part of the configuration Parameter Description Default Value New Value
code 'ILMN', conf. Unit Input Eng. units C bar
I L M N Sc.d.d Number of decimals 0 1
8 0 0 2 Sc.Lo Low input value -999.9 0.0
Sc.Hi High input value 999 50.0
Then press the enter key
rert Analogue output range 4 - 20 mA 4 - 20 mA
Enter the last digit for code 'O' rtH Output Heating / Cooling nu nu
CON2. Code Change Security code 33 33
O
Press the enter key to review the data you have entered
4 or press the scroll key to exit the configuration menu.
40 IM-P323-25 CH Issue 3
First group parameters
Parameter Description Default Customer set
Value Values
Press the scroll key
The display will show A2S.P Alarm 2 set point Stop Stop
A3S.P Alarm 3 set point Stop Stop
Avto P.b. Proportional band 5.0 5.0
A.N¢n t.i. Integral time 5.0 5.0
which provides the option of t.d. Derivative time 1.00 1.00
selecting Automatic or manual
control. O.C. Overshoot Control 1.00 1.00
nu.tn Valve travel time 60 40
Press the scroll key again. nu.hy Valve Minimum output step 0.5 .05
The display will show
OP.H Control output high limit 100.0 5.0
A2S.P Alarm 2 threshold value.
Press the enter key to save the
value entered and to move to the
Using the table opposite, enter the
next parameter.
following values into the parameters.
When the last parameter has been
entered, press the enter key
to save this value.
Now press the scroll key to
edit the second group parameters.
IM-P323-25 CH Issue 3 41
Second group parameters
Parameter Description Default Customer
The display will show Stop Value set Values
tvn£ tune Tuning PID Stop Stop
This is used to start the automatic AdPt Adaptive tuning PID Stop Stop
tuning. Using this table enter the SL. u Set point ramp up Off Off
following values into these
SL. d Set point ramp down Off Off
parameters.
S.P. L Set point low limit 0.0 0.0
Press the enter key to save
S.P. H Set point high limit 50.0 25.0
the value entered and to move to
the next parameter. A2hy Alarm 2 hysteresis 0.5 0.5
When the last parameter has been A2L.b Alarm 2 latching and blocking none Ltch
entered, press the enter key A3hy Alarm 3 hysteresis 0.5 0.5
to save this value. A3L.b Alarm 3 latching and blocking none none
To exit press the scroll key . t.F iL Time constant input filter Off Off
pass
The display will show: PASS In.Sh Input shift Off Off
Press the scroll key again d.Err Error dead band Off Off
and the display will return to the St.OP Soft start output value Off Off
normal operating mode. Sa.OP Control output high limit 0.0 0.0
The controller is ready to operate.
Now enter the required set point of To improve control of the application,
20.0 bar by using the and adjust the proportional band and
integral time accordingly.
keys.
42 IM-P323-25 CH Issue 3
6.2 Example of temperature Configuration code
control for SX25-VMD Using the and keys, enter the first part of the configuration code
'ILMN'.
The SX25-VMD controller is I L M N
then press the enter key
monitoring system temperature 8 0 0 2
with a RTD Pt100, and provides a
Valve Motor Drive control signal to Enter the last digit for code 'O' O then press the enter key
the electric control valve. 4
The configuration code is now
Configuration Code and entered,and the oC This selects Celsius or Fahrenheit for
display will show: the temperature units.
parameters:
vn¡t
Temperature sensor with an
effective range from 0°C to Using the table below enter the following values into the parameters.
100°C.
Parameter Description Default Value New Value
Control Valve with 20mm stroke Unit temperature units °C °C
and Valve Motor Drive electric
Code Change Security code 33 33
actuator, speed 0.5mm/s .
Press the enter key
Two Event alarms are required. When the configuration menu is exited, the
Event Y2 set for active low to save the value entered display will now show the normal operating
process alarm set at 35°C with and to move to the next mode, with the process variable at the top
the blocking function. Event Y3 parameter. and the set point at the bottom.
set for an active high deviation For example:
alarm set at 10°C. Use the enter key to With the controller
review the data you have
The process temperature configured, the
required is 60°C is the control entered or press the parameters can
temperature. scroll key to exit the now be entered.
configuration menu.
IM-P323-25 CH Issue 3 43
First group parameters
Parameter Description Default Customer set
From the normal operating mode Value Values
press the scroll key . The
A2S.P Alarm 2 set point 0.0 35.0
display will show
Avto A3S.P Alarm 3 set point 0.0 10.0
A.N¢n P.b. Proportional band 5.0 5.0
which provides the option of t.i. Integral time 5.0 5.0
selecting Automatic or manual
control. t.d. Derivative time 1.00 1.00
O.C. Overshoot Control 1.00 1.00
Press the scroll key again. nu.tn Valve travel time 60 40
The display will show A25.p nu.hy Valve Minimum output step 0.5 .05
Alarm2 set point. Using the table OP.H Control output high limit 100.0 5.0
opposite, enter the following values
into the parameters. When the last parameter has been
entered, press the enter key
Press the enter key to save the to save this value.
value entered and to move to the Now press the scroll key .
next parameter.
44 IM-P323-25 CH Issue 3
Second group parameters
The display will show
Stop Parameter Description Default New
Value Values
tvn£ tune Tuning PID Stop Stop
This is used to start the automatic
tuning. Using the table opposite, AdPt Adaptive tuning PID Stop Stop
enter the following values into these SL. u Set point ramp up Off Off
parameters.
SL. d Set point ramp down Off Off
Press the enter key to save the S.P. L Set point low limit -99.9 5.0
value entered and to move to the S.P. H Set point high limit 300.0 80.0
next parameter. A2hy Alarm 2 hysteresis 0.5 0.5
When the last parameter has been A2L.b Alarm 2 latching and blocking none bloc
entered, press the enter key to A3hy Alarm 3 hysteresis 0.5 0.5
save this value. A3L.b Alarm 3 latching and blocking none none
t.F iL Time constant input filter Off Off
Press the scroll key .
In.Sh Input shift Off Off
The display will show: Pass d.Err Error dead band Off Off
Press the scroll key again and St.OP Soft-start output value Off Off
the display will return to the normal
operating mode. Sa.OP Output safety value 0.0 0.0
The controller is ready to operate. Now enter the required
set point of 60°C by using the and keys.
And read section 5 (Automatic tuning), for the self-setting of
the PID values.
IM-P323-25 CH Issue 3 45
7. Automatic tuning
Two tuning methods are provided: This method provides a more
Operator
Initial one shot Fuzzy-tuning accurate PID calculation but will
mode
Continuous, self learning take more time to complete.
Adaptive Tuning If the natural frequency tune is
press until
Fuzzy-Tuning allows the calculation of taking too long to complete, try
the optimal PID parameters by the step response time.
monitoring the response of the
process.
To start
The controller provides 2 types of
select
tuning algorithms, that are selected
strt
automatically according to the
process condition when the
operation is started.
Step response
To stop
This type is selected when the
select
process is started.
stop
There must be a difference between
the set point and the PV of more then
5% of the input scan.
This method has the big advantage The green led will flash when
of fast calculation, with a reasonable the Fuzzy Tuning is in operation.
accuracy in the PID calculation. At the end of this operation, the
Natural frequency calculated PID values are stored
This is selected when the Process and used by the control algorithm
Variable (PV) is close to the Setpoint and the controller automatically
(SP). returns to the operator mode. The
green led will switch off.
46 IM-P323-25 CH Issue 3
The self-learning Adaptive Tuning is On the basis of this data and their
non-intrusive. It doesn’t affect the statistical values, stored in the Operator
process during the calculation of instrument, it automatically mode
the optimal PID values. modifies the PID values.
Note:
Before the Adaptive is switched
off, note down the calculated PID
values.
It is particularly suitable for
controlling process whose If the Adaptive is switched off To start
control characteristics change the new PID values will be lost select
with time or are not linear in
strt
relation to the Setpoint values. If the power fails during Adaptive
It doesn’t require any operation by Tuning, the PID values are lost.
the user. It works by continuously At power on, the Adaptive Tuning
sampling the process response to starts automatically and will
the various process disturbance, To stop
re-calculate the PID values.
determining the frequency and the select
amplitude of the signals. stop
IM-P323-25 CH Issue 3 47
8. Technical specifications
Features
Description
(at 25°C environmental temp.)
From the keypad the user can select:
Total configurability - type of input - associated functions and the corresponding outputs
(see section 4.1 page 19 - type of control algorithm - type of output and the safe conditions
section 5.6 page 36) - type and functionality of the alarms - values of all the control parameters.
48 IM-P323-25 CH Issue 3
Features
Description
(at 25°C environmental temp.)
Single Control output AL2 alarm AL3 alarm
Operating modes 1 double action OP1-Relay /Triac OP2-Relay or logic OP3-Relay/Triac
and outputs action PID OP2 -Logic OP1-Relay /Triac OP3-Relay/Triac
loop or On/Off
with 1 or 2 Double action OP1-Relay /Triac OP3-Relay /Triac OP2-Relay or logic
alarms Heat/cool OP1-Relay /Triac OP2 Logic OP3-Relay/Triac
OP2 Logic OP3-Relay /Triac OP1-Relay /Triac
Algorithm PID with overshoot control or On-off
Proportional band (P) 0.5…999.9%
Integral time (I) 0.1…100.0 min
Derivative time (D) 0.01…10.00 min OFF = O PID algorithm
Error band 0.1…10.0 digit
Cycle time 1…200 sec
Control mode
Dead band -10.0…10.0%
Cool relative gain 0.1…0.10 Heat / cool
control action
Cool cycle time 1…200 sec
Overshoot control 0.01…1.00
PID algorithm
High limit 100.0…10.0% (heat) -100.0…-10.0%(cool)
Hysteresis 0.1…10.0% On-Off algorithm
IM-P323-25 CH Issue 3 49
Features
Description
(at 25°C environmental temp.)
SPST Relay N.O., 2A/250V~ for resistive load
OP1 output
Triac, 1A/250V~ for resistive load
Protection by
Logic not isolated: 5V–, ± 10%, 30mA max Jumper selectable varistor
OP2 output
SPST Relay N.O., 2A/250V~ for resistive load (page 13) for 220V ~
and capacitor
OP3 output SPST Relay N.O., 2A/250V~ for resistive load
Triac, 1A/250V~ for resistive load
OP4 countinuous control Galvanic isolation: 500 V~/1 min
Resolution 12bit (0.025%) In current: 0/4…20mA 750½/15V max
output (option)
Accuracy: 0.1 %
Hysteresis 0.1…10.0% c.s.
Active high Deviation threshold ±range
Action type Band threshold 0…range
AL2 - AL3 alarms Active low
Action Absolute threshold whole range
Sensor break, heater break alarm,
Latching/Blocking, Loop Break Alarm
Ramp up and down. User inhibited. 0.1…999.9 digit / min
Setpoint Low limit from low range to high limit
High limit from low limit to high range
Fuzzy-Tuning The controller selects automatically the best Step response
method according to the process conditions Natural frequency
Tuning
Adaptive Tuning self-learning, not intrusive, analysis of the process response to perturbations and
continuously calculation of the PID parameters
Auto/Man station Standard with bumpless function
Auxillary supply +18V- ±20%, 30mA max. for external tranmitter supply
50 IM-P323-25 CH Issue 3
Features
(at 25°C environmental temp.) Description
Measure input Detection of out of range, short circuit or sensor break with automatic activation
of the safety strategies and alerts on display
Control output Safety value: -100%…100%
Operational safety Parameter and configuration data are stored in a non volatile memory for an
Parameters
unlimited time
Password to access the configuration and parameters data,
Access protection
keypad lock, output lock
IM-P323-25 CH Issue 3 51