Professional Documents
Culture Documents
Tem 5003e
Tem 5003e
Tem 5003e
ELECTRICAL DESIGN
NO CONTROL
--
FWM A.G20.013
m
TOKYO @ JAPAN
ISSUED
/
h E,WINEERIM Cow.
SZ?.26’88
ENGINEERING MANUALS
CONTENTS
L
PAGZ 1
TEM
5003E
GF 57
1. PURPOSE 2
..
2. SWITCHROCM
FcRm A.G30.014
TOKYO @ JAPAN ENGINEERING MANUALS TEM
) I
H
h E,WINEEXIW Cm.
GUID.%YCE TO ELECTP.ICP.L WORK DESIG:J
ISSUED SE?.26’88
*
1. PURPOSE
2.
Most of these eq~ipment (other than a-c motor, 10CZ1 panel, z~d ~ower outlst
box for constructio~ work) are ifistalled wikhin or around the switchroom.
Therzfore, Ur.l$ss car2-‘u~ consid?zatior,s aze given for t~e locztion and
construction of swit.:hroorn, cocstr’<ction cost become enor~tous or various
~Lay
And, e~jen ?f the switchroom is distant from SUC5 areas, wind <irection (its
average through yezr) shail be investigated, because it may affect the
switchro~m greatly.
(2) If the switchrcom and control room are include~ in the same building,
it is preferable from the view point of monitoring an~ wiring, ‘to
arrange the control room a? t?.e plant sifis.
TOKYO @ JAPAN ENGINEERING MANUALS TEM
/
h EMiNEZXIK b.
GUID>.NCE TO ELECTRICAL WORK DESIGN
ISSUED sE?.261~8
w
(3) The switchroom shall have at least 2 doorways and either 0C2 of them
is to be used as opening for czrrying-in of equi~ment. The size of the
opening for carzyinq-in of equipment shall be determined according to
the packag=d size of the lar~est equipment.
..
In czse cf switchroom housing electrical equipment of 3 - 6 kV class,
most of the equipment can be carried in, if the opening of 2500 mm
(height) x 2000 mm (width) is provided.
(d) The location of the opening for carrying-in of equi?ment shall not
be in area whers vehicles cannot come nearby.
1 .
Attentions are required, es:dcially in case of overssas project,
because thexe are countries where installation of oil-immersed
I transformer adjacent to other equipment is prohibited if the quantity
of contained oil is more than z certain limit. .
I
I (7) Appropriate ventilation device shall be provided so that room
temperature in the switchroom will not exceed 40°C. For this pux?ose,
the air volume to be ventilated shall be calculated, on the assumption
that ~mwez loss as shown bel~w occurs in each electrical equipment.
FORM A.G30.014
9
ENGINEERING MANUALS TEM 1
TOKYO @ JAPAN
P
Tm E,WX~EZRSW ~w. 5003E
GUI DANC2 TO ELECTRICAL WORK DESIGN
ISSUED ~EP.2~t88 PAGE 4 OF 57
(c) Between 2 rows of switchboards, when they ar= installed with their
front surfaces facing each other: 1.8-m or more.
FORM A.G30,014
L ...
7
TOKYO @ JAPAN ENGINEERING MAiNUALS TEM
h E,W’INEZRIW Cm. 5003E
GUIDANCE TO Electrical WORK DESIGN
ISSUED S~?.2~@88 PAGE 5 OF 57
(i) Clearance abovs switchboard: 0.5 m or more undex beam and under
ceilinq.
(e) At the end of an? gzouge< switchboards, thsr? shall be s?ace for
enzbling installation of at least one more panels in the future.
—
(f) In case whers total lenqth of grouped switchbo~r~s becomes 10 m or
more, a p~ssaq~way leading to the backside shall be provided at an
interme~iate position.
.
(gj in case of motor c~ntrol ccnt~r which is to be installed on beams
laid across a cable trench, study shall be made, in accordance with
the Agpendix to this Sectien, to cafifirm whether the beams can bear
the Iozd. Moreover the location of the beams shall be determined-
so thzt they do not interfere with any opening for wizing to be
drawn in~o the board.
(3) When 2 or more equipments of the same kind are to be instailed, the
position relationship between the equipment and the panelboard shall
be given consideration so that any real-operation wili not be caused.
For e:<am?le, the ~sition relationship between a transformer and the
switchboard for the transformer, between a starting reactor Znd the
switchboard for the motor (including starter board), between a exciter
and the switchboard”~or the motors, shall be contrastive after their
installation.
FORM A.G30.014
L..
v
(6) Static type voltage regulators, battery chargzrs, invertzrs, etc. which
comprises semiconductors shall preferably be installed, avoitiing places
near the doorway of the switchroorn or near any transformer which
generat=s large quantity of heat, because they aze apt to be sffected
by dust or room temperature mor= easily thzn other equipment.
(7) When any rotating machine havi~g weiqht of 0.5 ton or more is to be
installed within the switchroom, the svitchroom shall preferably be
provided with hanging bolts or I-beam at the ceiling. And ZISO the
height of the machine’s foundation shall be sgecified, in this cass.
.
(8) Each el~ctrical equipment shall be installed so thzt zny opening for
carrying-in of equipment, emergency doorway, exha~sk fan, gallery, etc.
will not be blocked. Furthermore, if any equipment i= to be installed
on a block-made wall, a study is required on whether reinforcement is
necessary or not.
(a) Motors shzll have covering so that t>e worksr will not cG~e in
cant~ct with rotating parts when” doing clezning or cilinq.
(b) k~ot~rs shzll be- such that each one motor can be started and stooced
by one contrsl switch. The arrangement of the control switch s~;ll
cozres~ond with arzar.qemeat of rectors, so that an:l mal-o~eration
will not be caused.
FORM A. G30.o14
,. 9
,,
TOKYO @ JAPAPJ ENGINEERING MANUALS TEM
)
~ ~AWIXEZRIK Cw. 5003E
GUI D.%VCE TO ELECTRiC1.L WORK DESIGN
ISSUED s~?.25:~o PAGE 7 OF 57
QI L
(a) Article 54
(b) Article 44
-
(2) Industrial Safety and Health Law
(a) Article 59
(b) Articl= 61
FORM A-C30C14
TOKYO @ JAPAPI ENG\NEERING NIANUALS TENI
i
% E.-:HEEx!.% COM 5003E
~JIDANCE TO ELECTRICAL WORK DESIGN
ISSUED SE?.25VSS PAGE 8 os 57
I ———
(c) Azticle 92
TF.e volume ar.d pressure of supglying air s>.all be such thst t?,s air
pressure in the vicinity of ~ooways is maintained hi~her than the
atmosphere outsitie the room.
FORM ~-G30.OIA
m
7
TOKYO @ JAPAN ENGINEERING MANUALS TEIM
/
Tm ~.WINEEXI.W Cm 5003E
GUIDANCE TO ELECTRICAL WCRK DESIGN
ISSUED SZP.26’8Si PA,GE g OF 57
I
Eoweverr this ne~d not apply, if the both are isolates each other
by a partition made of refractory-like materizl.
(b)
‘&B8
RA R8
- . Bending moment (M = t.m)
M=
PJ
M max. = ~
k $l?
= —
‘D :@-;& =~l?
.
..
. Max. strsss 0= ~sfc (t/cm2)
:
fs Allowabl~ shearing 8 kg/m2 for light gauge shaped
stress of material (kg/mm*) steel of 0.4 mm or less thickness.
9 kg/m2 in czse of ordinary steel.
FORM A-G30.014
L.
TOKYO @ JAPAN ENGINEERING MANUALS TEM
)
- EM1~EZRXW &x 5003E
GUIDANCE TO ELECTRICAL WORK DESIGN
ISSUED SE?.26’88 PAGE 11 OF 57
.[
II -,
,.‘ 1
.!
-
:: ~.
-—------——— .. ---- -. . . . A
- I
——— ——— — .~ — i + .- ----
——-—— _— _ —_
I I I -A
a
4 c
———— ——
— - -.
‘:j--=-==-
A5 r- 60-=
r 170
m.
/ ~1 ‘. &2
T +’
.
._’
— —
!
.——
L?
99
_.. —-’--—__ .
/
~,
/4 ~ Q
L
+
Mx”
+W
-w
❑
.
ALLOWED LOP-D
FWM A-G30.0t4
TOKYO @ JAPAN ENGINEERING MANUALS TEM
Tm Ew’l~sExIw C- 5003E
GUIDANCE TO Electrical wo~x DESIGN
ISSUED SEP.26’2G PAGE 12 OF 57
(3) Bracket
-Length L mm
— 400 500 700 900
Metier
,
L4x50 181 kg 136 kg 96 kg 49 kg
L6x50 256 192 116 64
L6x65 474 364 238 159
L6x75 673 505 336 234
[5X75X40 1520 1260 758 503
[5X1OOX5O 3020 2310 1520 1090
.
(b) Verification of welding of members
. ~e , , ]
B Throat
thickness
a
L
a~~ “ L;a
.
F ORM A.G30.014
.
TOKYO @
- JAPAN ENGINEERING MANUALS TENi
h Em>INZZXIX k 5003E
G~ID&~JcS To ELSCT?. ICAL WON< DESIGN
ISSUED sz?.26’2a PAGC 15 OF 57
L
Any cable r~uts shall not run such placss as follows an~ this shzll be
chec;ked enough ev~s a?tsz the plan has been est~blished.
(3) Place near any equ<$me~t or piping whose surfacs temperature becomes
hi~h, and places ufid=.rneath of steam tra?, e?~.
(4) P.oad and place where heavy cargos are carried in and out:
(5) Place wher2 the ground is base rock which is difficult to excavate. ..
(6) Place crossing over any large-size underground piping, sswer ditch,
etc.
(8) Plzce where the cable would be prone to operatcr’s contacting or the
czble wo~ld obstruct passageways. (Especially ta!<z care at the
position of going up or down of cable run)
(10) Place wkezs there is an existinq cable neaz~y which can greztly affect
. . cz.bleSs heat a;ssisakio~..
anfl. r’~wly la~c .
(c) If the buried par= is short, it is better to protect the cable with
conduit tube, rather t>an with concrete tr~ugh. In this case,
c’bsezve Pax. 5.5 (2) d.
., FO RM A.G30.014
r
TOKYO @ JAPAN ENGINEERING MANUALS TEM
P
k E,wlxzzRfx k 5003E
GUIDANCE TO ELECTRICAL WORK DESIGN
lSSUED SZP.26’88 PAGE 13 OF 57
4
(c) Verification of “HX~K-type’’anchor bolt
..
If 1 is too long, deformation of plate at this part can occur, and
if ~ is too short, shearing breakage can occur.
(4) Ventilation
v~ =60cA~2gRTl 1- m3/min.
( :)
= 440 A m3/min.
FORM A.G30.014
TOKYO @ JAPAN ENGINEERING MANUALS TEM
~ EM’INE~RIW W 5003E
G~I~~\:~E To ELEcT~Ic~.L ~oR~ DESIGN
ISSUED SE2.251G8 PAGE 14 OF 57
4
. (b) Ventilation air volume for disp~sing of heat generated in the room
(C2 - t3)
Q= ;gf:~”——
- t3) Cpap
m 3 /rtin
(Example of calculation)
FORM A-G30.014
TOKYO @ JAPAN ENGINEERING MANUALS TEM
k EM’:NBSXSW Cm. 5003E
GUIDANCE TO ELECTRICAL WORK DESIGN
ISSUED SE? .2613% P,AGE 15 OF 57
Assuming that Fr2ssure loss at air filter is 20%, and taking 10% as
all~wance, r~qcir=d czpacity of blower is,
H= gxIxN
.
9: Volume of H2 ge~.crated from one ce!.1 of battery m3/min
1: Charging curr=nt A
N: Nu,mber of cells -.
3.
FQRM A.G30.014
TOKYO @ JAPAN ENGINEERING MANUALS TEM
P
k EMIXESRIM h.
GUIDANCE TO ELECTRICAL WORK DESIGN
[ssUSD SE?.26’88
&
(a) Cable rack shall be selected from those of standard size products
available, to satisfy the requirements from the formula shown
below.
where,
FOR,W A-G30.014
m
TOKYO @ JAPAN ENGINEERING MANUALS TEM
~ EN’lHExRIM w 5003E
GUi DkYCE TO ELECTRICAL WORK DZSiGN
ISSUED SZ?.2~’~8 PAGE 17 OF 57
These methcd shzll be adopted when the cable raute is to cros= a road
or wh~n cables will be a?ded or replaced in f~ture.
(a) The sleeve pipe used for the underground conduit draw-in type cable
layicg shzll be mainly of reinforced conczet= pipe (Hume pipe), the
insi<~ diameter being one of the 7 kinds, 75, 100, 125, 200, 250 -.
ar,d 300 mm.
(d) Pow2r cable shsll not come in contact with any instrumentation
cable or process piping, etc. Especially, power cable shall not
rufi in parallel with any izskrumentation cable at a distance of 1 m
or less. (Den-Gi Article 148)
(f) Sectional area cz ins2de diameter of the sleeve pipe shall be, 5 or
more tir,es the area occugied by cables, if 2 or more cables aze in
one F.oLe, and 1.5 or more time the outside diameter oi cable if one
cable is in one hole.
(g) Manholes shall be p~ovided, so that the sga~ of straight run of the
sleeve pipe is 50 T, or less, Manhcles shall also be provided at
places where sleeve pipe is bent to have angle of 120°C or smalle=.
(b; Cable trench shall be selected from those of <tandazd size series,
to satisfy the requirements from the formula shown below.
H~4Dy mm
FORM A-C30,0{4
———
TOKYO @ JAPAN ENGINEERING MANUALS TEM
h E,;IN~ZRXX h 5003E
GUIDANCE TO ELECTRICAL WORK DESIGN
ISSUED SZ?.25’88 PAGE lg OF 57
(c) Cable racks shsll be laid in an open sFace where such rzcks can be
wakclqed. (Den-Gi Article 160)
(d) E.V. and L.V. cables on a cable rat!< shall be separated each other
by a separation plate, so that they will not come in cofitzct.
(Den-Gi Article 220;
(e) Cable racks shall be Frovide5 with cover at places where cable can
be damaged from outside, such as neighborhood of proc$ss piping,
downwardly or u?wzr~ly verticai portions, etc. Cover s3all be
provided also at outdoor parts under dirsct sunshine.
(f) Cable racks shall be provi~ed with lugs or openings for grounding
use at 2 or more positions, so that grounding wire can be easily .-
c~nnecte~.
(b) Steel plates used for metallic ducts shall be of 1.2 mm or more
thickfiess and shail be those galvanized or cGated with enamel,
1 —
etc.
(d) Duct shall be such that intzusion of duct into the inside is
prevented.
This method is, as explained in Par. 2.3. (5), used mainly for
,. connection betwee~ th= L.V. side of transformer and a switchboard or
motor controi center=- While bus ducts for L.V. indoor wiring are
standardized by JIS and Den-Gi, any use of those for H.V. may recui~~
.
spec~zl perr,issi~n. The same a~~lies also when bus duct is to be used
outdoors.
FORM A.G20.014
m
TOKYO @ JAPAN ENGINEERING MANUALS TEM
h E~lx&ERfx fim 5003E
(b) Bus dUCtS, while they can be used at a house’s side or in outdoor
(only when used for 300 V or less), shall be used, in general, for
indoor wiring within dry, ope~ s~aces or Ezy concealed spaces where
inspection is -mssible. (Den-Gi Azticle 189)
(d) ~he~2 bus duct penetrates floor or wall, the bus duct shall not be
co~nzcte~ at the penetration part. -.
(c) The height of overhead cable shall be 3.5 m or more from ground and
the distance betwe=n supporting structures shall be 30 m or less,
the distance being dependent on the cable size. (Den-Gi Article 74)
. .
(d) Size of messen5er wire shall be selectsd so that the safety factor
of 2.5 oz more can be secured.
(8) Others
(a) When czble is laid along the surface of building or structure, the
distancz between the supporting pints of cable shall be 2 m or
less. (Den-Gi Article 20i)
/
: FCRM A.G30.OIA
r
m
7
Pipe used for protection cf cable against damage from outsise shall
p,z,l~ insi~~ diameter 1.5 or more tim~s t.b-e ol~tsids tiiameksr of tk,e
cab~e- For d~tails, refer to the manual TSN-5~30E.
(211S Article 2212)
.. (c) Ben~ing radius of czble shall be 8 or more times the diameter of
cable in case H.V., and 6 or more times thz diameter in cass of
L.v. However, if thz cable is steel tape-srmored lead-cove~ed oi~-
ir,pregxatsd pz?sr-insxlated H.V. cable, the bezding radius shall be
12 or mors times th~ diameter. (RIIS Article 22i2)
(a) Eech mOtOr shall have a branch circ,~it (Dee-Gi A~ticie ~S~), and
C~bie SiZ~ for ths branch circuit shall be as follaw~.
(b) Size Gf trunk line cable for motors, etc. shall be as follows.
FORM A.G30.0!4
T OK Y O @t JAPAN ENGINEERIIVG M A N U A L S TEM
~w E,w’x~E~~xx Gm. 5003E
GJID.%NcZ TO ELECTRICP.L WORK DESIGN
ISSUED SG2.26’83
T- PAGE 22 OF 57
L
Notes: (1) im is the sum Of rated currents of 10ads ot~e: t;>~n tfie
(2) In the aboev (a) and (b), cases where mode of ~~e is
s>ecial, such as intc~mittsnt us?, zzz exclude~.
(c) &!or= than one motor may belong to ,one branch circuit, if the rated
curz~ct of ovez-c~lrrsnti protective d~vice of tl~e branch cixc~it is
15 A or less (in case of molded-case cizcuit brea!<sr, 20 A cr less)
or if Cv=xload proactive Sevice is provided ta individual motors,
cr if ncmbe= cf motors are installed in a same machiz= and opezat=d
by the F.achine controller, or if the s’n~ft of motors are
mzchzzically coupled. (Den-Gi Article 135)
(a) It shall be remembered that an? ~rtable type equipment whose ingut
is 1200 VA or less shall not be-used in z circuit exceeding 300 V. ~
(JZAC Par. 300)
(bj ,~ova~~e w~r~ used for poztabl.e tY9e e ~~ig=ent Skall be cabtyrs
cable having sectional area of 0.75 mm or more, and the minim~m
size and meximum length C5 ths cable shall be as follows for eac’n
rated load!s current. (Den-Gi Article ’206, JEAC Par. 310)
FORM A.G30.oIA
n
7
(d) Receptacles shall be those provided with pole for grounding wire.
(a) Section switch shzll be provided at near the junction Feint between
the ?ower sl~ouly
- - cz~le and the travelinq czbtyrs cable. This
s.ditcP4 s>sll be operzhle from t~he floor and be suita>le to be
10Ck9d at its opened-Ci~cu~~ ~~sition.
(b) The travelir.g czbtyre ca.sle s;qa~l ha~~e sectionz~ azea of 0.75 mm 2
oz morz znd si~all not hzve any junction Feint throughout a len9?h.
.- (JE14C Par.310)
(c) The rats~ ca?acity of section switch shall be 50% or more of the
sum of short-time cuzreat ca~~city of all motors, or 75% Or more of
the sum of shcrt-tihe current ca?acit? of motors which are rsquir~d
duzing on? operation OZ th= czane.
(d) The traveling cab12 shzll be laid in such a way that no d=mage of
core Gr sheath is not caused by vibrzkion due to travelinq of the
crans, conksct with other mechanism, tension force at scpgorting
pint due to own weight, etc. (JEAC ?ar. 310)
(f) Crane operable from the SXOCZ2 shall be of such construction thzt
the circ~uit is opene~ automatically when the crane’s control device
. -
FORM A.G30.oIA
m
TOKYO @ JAPAN ENGINEERING MANUALS TEM
~ E.;lxEEx!w - 5003E
GUIDANCE TO ELECTRICM WORK DESIGN
ISSUED sE?.26’88 PAGE 24 OF 57
(g) Th3 traveling cabtyre c=ble shall be hung so that its lowest part
is 3 m or more above t’ne floor.
(4) Elevator
. Ia case of elevatar, TEC’S wiring is mainly that for supplying pwer
souzce an< that for emerge~cy si5naling or telephofie, and wiring within
the elevator is prsgared by manufacturer. Therefore, this does not .
conczr~ TEC’S ezginesring. But, the items to be observ~d a~e shown for
rsfsrencz as follows.
(a) El~va~c~ cabl~ ma? ~,e ~~e~ for L.1[. indoor wiring of 3C0 V or less
and L.V. movable wiring laid within th~ elevator shaft.
(Den-Gi Article 217) ..
(b) Wiring within the elevator shaft shall be firmly fixed to a frame
which is not likely to suffer damage. Moreover, piping other than
for elevztor, such as supgly water and drainzge piping, shall not
be laid within the shaft. (Standards on Construction of Elevator
Article 16, Cabinet OrSer on Building Standar2s Law Article 129)
(c) The movable wire shall not have any junction point throughout a
lsngth. (JEAC Par. 310)
(d) ~i~~s u~~~ for control, lighting, signaling znd telephone circuits
shall be contained in respective separate pipes or moldings.
Kowever, this need not apply if voltage is th~ same. (Standards on
Construction of Elevator Article 34)
(g) In the circuits of the above (d), the same cable shall not be used.
(h) Elevator machine ro~m shall havd ceiling bight of 2 m or more and
shall not accommodate zny equipment not relat=d to the elevator.
(i) The machine room shall be provided with oFening foz ventilation and
lighting fixtures, and the lightinq shall be switched by a switch
provided at a conspicuous place near the door way. (Tokyo
Metro.mlis’ Regulation on Building Safety, Lyticls 76)
(k) Elevator shall be provided with such safety devices as shown below
(Standards on CofiStruction of Elevator Article 30)
Zr FCRM A.G30.014
_T
TOKYO @ JAPAN ENGINEERING MANUALS TEM
P
k E.WINEZRIM M
GUI DMICZ TO ELECTRICAL WORK DESIGN
ISSUED s~?.25’88
s
- The cag~ cannot be put in motion unless all of the gateway doors
at the cage and shaft are closed
- The gateway door at the shaft can be ogened only by use of a key
unless the cage is at the floor of that door.
- Limit switch
(b) The allowabLe current of wire used for feeding 2 or more welde=s
may be smaller than the value multiplied by the factor shown in the
above (a). (NEC Article 630)
That is, 100% for the 1st and 2nd welders, 8S% for the 3rd, 70% for -
the 4th, and 60% for the r=st shall be taken into accccnt.
S FORM A-G30.014
z
TOKYO @ JAPAN ENGINEERING MANUALS TEM
h E.~lxEzxI~ Cm S003E
GUIDANCE TO ELECTRICAL WORK DESIGN
ISSUED sE2.26’8a
~
(a) Connection betw~en the metal conduit wiring a~d the electrical
equipment shall be done by uss of a terminzl box of increas~d-
safzty or flame-proof construction in accordance with the hazardous
. classification, and a sealing fitting shall be provided within 45
cm from the terminal box.
(RIIS Article 2223)
(b) Leading-in of cable to the terminal box shall be by use of
flamep~oof packing-type gland or flameproof sealing-compound type
gland. In case of flameproof packing-ty?e gland, the czble shall
be of rounti crass-section. (RIIS Article 2231)
(8) Others -.
(a) Minimum size of L.V. cable shall be 3.S mm2 or more in case of
—
power use, and 2.0 mm2 or more in case of control use. However,
this does not apply to wiring of portable type motors and wiring
attsched to equigment such as crane, hoist, elevator, etc. (Den-Gi
Article 9)
(c) Maximum siz= of c=ble shall be 1000 mm2 in case of single core, and
.
32S m2 in case of 3 core.
Assuming that;
FCRM A-=30.014
TOKYO @ JAPAN ENGINEERING MANUALS TEM
I
h EMXXEZR]W Cw 5003E
GUIDANCE TO ELECTRICAL WORK DESIGN
ISSUED SEP.26f3~ PAGE 27 OF 57
Receiving force,
“Reaction force,
‘A =RB=;=84X5-5
2
= 231 kg % 250 kg
~~%”c ~x~~~~::~;-5)2=211kg.m :
FORM A-G30.OIA
L.
m
TOKYO @ JAPAN ENGINEERING MANUALS TEM
) 1
v- 25000
J ,Z
z = 1450
— = 170 kg/cm2 < 1500 kg/cm2 @K
.
BQckizg factar 0 = 1.04, Radins of gyration
of area
iy = 2.27
fl’
A=— 7G = 31
iy 2.27
(e) Foundation
Kei5ht of foundation
~-?=2.92+338=6.3 t
0.51X0.8=Q.488t.m
~3/1=1.85~0.488=Z338t.m
XM 2 3 3 8
——=
e— —=0.371-0.37
xv 6.3
D 160
‘=—=26.7<40 OK
6 6
F9RM A-G3G.014
TOKYO @ JAPAN ENGINEERING MANUALS TEM
/
Tm EXIXZE~lX M 5003E
GUIDmC2 TO ELECTRICAL WORK DESIGN
ISSUED sz?.26’8g PAGZ 2g OF 57
23V = 2 x 6.3
3C= = ~2.6
33 (~ - e) 3.X 1.2 (+ - 0.37) 1.55—
FGRM A.C30.314
m
TOKYO @ JAPAN ENGINEERING MANUALS TEM
P
TM E,w~Nz~RI?w Cc-. 5003E
GUID&~lCE TO ELECTRICAL WOK{ DESIGN
1~~~~~ SZ?.2G198
,=AGE 30 OF 57
‘2 =a x a xh x 2.3
Mi = 60@1x~1xcixh1
M2 =. 60X2xA2xC2xh2
~1 F OR M A.G30.o(A
- *
m
TOKYO @ JAPAN ENGINEERING NIANUALS TEM
/
As for four classes of grocnding, that is, Class 1, Class 2, Class 3, and
Extra Class 3, and design requirements for each ClaSS O? grounding, refer ta
Articles 18, 19 and 20 of “Den-Gi”.
—jz..
TOKYO @ JAPAN ENGINEERING MANUALS TEM
k E.W’INEERIW Cm. 5003E
GUI D~lCE TO ELECTRICAL WORK DESIGN
ISSUED S5?.26’88
m
(2) Metallic part of conduit tube, cable duct, cable rat!<, ezc. containing
cabls shall be grounded in such a way that,
(3) Tubes used in metal conduit wiring, boxes use< in hzrd PVC conduit
wiring, dust-proof typ~ fittings, etc. shall be grounded (Extza Class 3
or Class 3 grounding tiepen<ing on the circuit voltage).
(Den-Gi Articles 193 - 196)
(4) Housing of ballast for discharge lamps, and metallic parts of lighting
fixtures shall be grounded.
(a) If the voltage of lamp circuit is H.V. and the secondary short-
circuit current of stabilizer or the working current of lamp tube
is more than 1 A . . . . . Class I
(b) If the voltage of lamp circuit is L.V. higher than 300 V and the
ssc~~dary short-circuit currsnt of stabilizer or worki~g current of
iamp tube is more than 1 A . . . . . Extra Class 3
.
(c) in Other cases than (a) to (b) . . . . . Class 3
(Den-Gi Article 221)
(6) In hazardous area, the grounding resistance between the grounding wire
and tne ground shall be 10Q or less. However, the grounding
resistance may be 100~ ar less, if circuit voltage does not exceed 300
v. (~llS Article 2622)
(7) Size of groundinq wire used for exposed metallic part of L.V. motor,
etc. shali be as follo(ws. (JEAc par. 140)
2 FCRM A.G3@.o!a
L, .———.
r
.
* Ratsd current cagacity of t;he smallest overcurrent protective dsvice
pr~vided at L.V. ‘elec~rical circuit for the metalli~ housing of
machi~e and tool, piping, etc. to be grounded.
** In case of groundi~ig far movable machine and tool, where, cord or
cabtyrz cable is to be used at the parts requizinq flexibility.
(1) Any building, etc. w’nose height is 20 m or more, and building, etc. in
which any dangerous ?roducts are handled or stored shall be provided
with lighting protection. It should be remembered that, in some
countri~s, judgement of whether this” is necessary or not is done
deFending on the pur~ose, type of construction of the building; object
contained in there or degree of its anticipated damage; -degree of
isOlatiOn frOm surroundings; condition of site; height of the building;
and lightning prevalence.
(2) Parts of H.V. c~rcu!t= shown below or their neighboring parts shall be
provided with lightizg arrsstsr. (Den-Gi Article42)
Incoming port at pwer consumer sup?lied with more than 500 kw power
from E.V. or E.X.V. overhead line.
FORM A.Gso.014
TOKYO @ JAPAN ENGfNEERING MANUALS TEM
)
GUIDANCE To ELECTRIc3.L WoR~ DZS~GN
= &
(5) Liqhkni~g r~ds shall be installed to caver the objects within the
pratsction angle of 60” or less. How~ver, in cass of a place where
danqerous objects such as gun powder, flammable liquid, flammable gas,
etc- are sto~zd or handled, the lightning rcd shall be installed to
cavez such objects within the protection angle Of 45° or less. -.
(JiS A4201)
—. (6) The air terminal of lightzing rods shall protrude beyond the object to
be protected by 1.5 m or more and shall be distant from any valve,
exhaust port, etc. by 1 m or more.
(7) In case of tanks or Ii!<e which are made of metsllic plate having
thickness of 3.2 mm or more and are tightly closed, air terminal of
lightning rod may be omitted.
(1) Information shall b2 obtained from the project grou? about tow2rs and
tanks, pi~ing, etc. where the accumulation of static electricity is
likely. It is recommended to have the P&I or pipin~ arrangement
.- drawing maked up with color at the portions concerned, if ~ssijle.
(2) RequeSt Shall be made to the related department to tie effect that
lugs for grounding be provided at 2 ?oints of any tower and tank, and 1
point ~r 30 m of piping which requi~s graunding.
(3) These lugs for grounding shall be connect~d to th2 grounding main for
graunding of supporting structure or housing of electrical equipment,
cable protection pipes, etc. However, in case of towez and tank where
the grounding is also to be made for the purpose of lightning
protection, independent groun~in~ shall be made.
FC9M A-C30.014
L
TOKYO @ JAP~PI ENGINEER!NG MANUALS TEM
P
h E.wiY~zxz,w k 5GG3E
GOIDANCE TO Electrical WORK DESIGN
ISSUED SEP.26’82i PAGE 35 OF 57
(s) Potable water pipi~g mzy be used ss gxounding electrode. In this case,
the c~nnsction of grountiin~ wire shall be at piping’s Fart where
intsrr.al diameter is 7S mm or mors, or at brazch piFe part within
distancs of 5 m frcm t5e above-said Figing’s part.
(Den-Gi Article 21, J15.A4201)
.
(7) Twa ways are conceivable for burying cop-per plates, horizontal laying
a~~ veztical lzying. Horizantzl la?ing is more prsfezable, in regard
to the volume of excavation=. Groun2ing resistance does not differ so
much..
?6
2 FCRM A-G30.Old
As gr~un~ing czntiuckor, WiYP having insulation grzde equal to or mere
than that of PVC-insulzt~ti wir2 shall be us~d, the COIOC Of sheath
beinq green. Howev?r, bar? wirz shall be uszd, in c~se Of grounding
. for lightning protection. (JEAC par. 140)
(3) GrounEing wirz foz lightning protection shall not be nounted oz an~~
sup&wrtiP.q material wb.ere gzou~.ding wire is mounted. Eowevzr, this -.
need not agply, if it is apart from the lattsr by 2 m
(Den-Gi Article 19)
(5) Li?htni~q cozductor shall have sectional area of 30 mm2 or more an<
be~~inq ra~~us of 20 cm or more, a?,d s>,all be apart from azy wiring fOr
lightin~, wiring for comnunica’~ion, gas pi~ing, etc. by 1.5 m or ~,or=.
(5) Groun?in2 main liae sha~l preferably have Sroundiag electrodes at both
ezds Or be r,ade izto a ~oog.
e = 0.00s (:)2s
A
w-nere,
= 0.0057 I &
A =J
g FCqM a-c30.oi4
TOKYO @ JAPAN ENGINEERING MANUALS -rEM
)
Tm ~.WINEZXIM Cm 5003E
GUi DA~7CE TO ELECTRICAL WORK DESIGN
SSUE2 SEP.26’85 PAGE 37 OF 57
if {I = 11,300 A A= 32.2 M*
s = 0.25
—
(2) Groucding resistance
R=&{Alo&2~(L+D)+L:Tlo&
L -D(L+2T)
L;2~J
— . . . . (1)
(2)
(by I<iso)
FCRM A.G20.o ! A
.L
TOKYO @ JAPAN ENGINEERING MANUALS TEM
)
Tm E,WXNEZRIW h 5003E
GUIDANCE TO ELECTRICAL WORK DESIGN
ISSUED SS2.25’88 PAGE 38 OF 57
L
R=—
2:Llo~e# . ● . “ ‘4)
where;
5. LIGRTING F~CiLITy
39
<
FORM A-G30.0!4
TOKYO @ JAPAN ENGINEERING MANUALS TEM
/
— It is said in general that the glare index shall be examined and that
unconfoztabie qlarz is produced when this value exceeds 20. The glare can be
prevent=d by changing the type, dir2ction of installation, or height of
mounting of the fixtures, ~inting of wall or ceiling, etc.
5.2
lamp, fiUOreSCe~t lamp, mercury-vapor lamp, etc. and they shali be sslected
so that the characteristics 02 each selected light source is most suitable
fox its purpse.
Mainly, incandescs>t lamps are used for emergency lighting and for local
lighting, fluorescent lamps.are used for illumination of offices, waiting
rooms, switchrooms, contr~l rooms, etc..and merccry-vagor lamFs are used
fox illumination at cutdoor pipe racks, towers and tanks, ceiling Of
machine room, and for illumination of raads.
.1
r
(1) Distance between wall and a lighting fixture near the wall shall be 1/2
of the mounting distance of other lighting fixtures. .
(3) Some of the lighting at upper parts of towers or tanks may require an
ornamental design andi- therefore, shall be installed at a??ropriate
places per each platform.
g
FORM 4-G30.Q14
M
?
m
TOKYO @ JAPAN ENGINEERING P/lANUALS TEPd
/
Branch circ~~its shall depend ugon the Fosition of liqhting fixtur~s and
require~ condition of on/off. Sut each branch circuit shall be one of 15,
20, 30, 40 or 50 A.
Erancll
I Re~eptac~e
FORM A.G30.OIA
TOKYO @ J.APAN
)
ENGINEERING MANUALS TEM
5003E
I
GUT DPNCE TO ELECTRICAL WORK D~SI~N
?~~E 42 OF 57
=_
(c) ?he size of wire for branch circuit shall be determined so that the
vo~tace
> ~ro~ in the branch circuit is 2% or 12SS (4% OT less if
feeder is i~~~ud~d), uniess r~the~~~is~ sr~cif:=a
. .-s. The voit.~?~ d~oP
in feeder may be incr~as2d up to 3% if the gowez is fed only from
the trzssformer instal12d in the plant area. Howev?r, regzr~l :ss
of th:s ~rescripkion, th~ sizs of wir~ for branch cizc.uit can be
determined in accordance with following table, if t?~e wiring
tiistance from sscon6ary terminal of powzr transformer. (or from
the sezvice entrance of purchased pow2r) to tl~e farthesk lc,:d
exceeds 60 m. (JEA.C Par. 120)
—
Total voltage drop (feeder and branch) (%)
Wirifig distznce
L (m) F2~2 th~ powez fram tr=nsf. Dirsct fesding fzom
. installed <n Dlant ar?a Purchased power
I
‘ti
._ > FORM A-G30.014
—
m
TOKYO @ JAPAFI
P
ENGINEERING MANUALS TEM
I
Among con~uit tcbes are, rigid steel co~~zit~, hard p~~c con~uit~,
fle:cible contiuits, etc. For lighting wirin~, heavy-gauge rigid steel
cc~<uits az~ mzinly ussd.
(a) Conduit tube shall not contact with any low-energy wirin%, water
pi?iag, gas pigin~, etc. (9en-Gi Article 204)
~ 50 T&m 2 30 m
~ Ioc mm* 25 m
~ i50 m2 . 20 m
< 250 mm2 15 m
> 250 mm2 12m
FCRM A-G30.oId
J
TOKYO @ JAPAN EtNGINEERING MAINUALS TEM
k E,~lNE~Riw h 5003E
GU15WVCZ TO Electrical woRK DESIGPj
ISSUED SS?.26’88i PAGE 44 GF 57
i ! I -— I _ - ’ 1
(!<) Flexible ccaZuits shzll be provided with bare copFer wiz~ of 1.6
m.m or mole, inserte< in or laid alcng with it, so that its both
ezds are c~ncsct~< electrically, if the l~ngth of the flexi51e
cafidtiit is ~.~re thzn 4 m. (Den-Gi ?.rticle lg~;
-Any st=uctuze whose height is 60 m or more from the ground or from the ssa
level or a~y str:cture which ssziously affects safety of aizcraft
cavi~ation shall be provi2s2 with a.n aircrait obstruction li~’nt, which is
prescribe5 in Transgort Ministry Ordinance. (Aizcraft Navigation Law
$.rticle 5i)
,
4
TOKYO @ JAPAN ENGINEERING NIANUALS TEM
% E.;XNEXRIX h. 5003E
GUI DPJICE TO ELECTRICAL WORK DESIGN
ISSUED SEP.25’881 L
PAGE 45 OF 57
(a) The circuit for aircraft obstruction light shall be a branch circuit
exclusively used for this purpose and the w~ring shall be laid having a
6istanc2 from lightninq conductor by 1 m or more.
~/
FCRM A-G30.OIA
r
TOKYO @ JAPAN ENGINEERING MANUALS TEM
)
GUIDANCE TO ELECTRICAL WORK DESIGN
= w
T where,
WI
2+ H3~
50m
~+ H ~k +
k
TOKYO @ JAPAN ENGINEERING MANUALS TEM
/
~m E,WIXE~XIM C-. 5003E
GUIDANCE TO ELECTRICAL WORK DESIGN
ls~uED SE?.2~183
PAGE 47 OF 57
H12
K{ dl— + d2H2(H1 + >) + d3H3(H1 + E2 + :)]
2
+ 0.891 X 2.815))
2.815 x (1.55 + 1.635 + —
2
H22
K[d2~ + d3H3(H2 + ~)]
2
157.5 { 0.1143 x (1.635) + 0.0891 X 2.815 (1.635 +2”815
~))
2
. H32
K(d37)
-
M ’A = MA + MW + pA(HA. >) + PO H A
HD
M ’B = MB + Mw + P~(Hs -
~, + pO~B
FCRM A.G30.014
TOKYO @ JA?AN ENGINEERING MANUALS
Tm E,;lXEZXIX ~. 5003E
GUIDmJCE TO ELECTRICAL WORK DESIGN I
SSUED SZP.26’88 PAGE 48 OF 57 I
P~H~
M’D=MW+— + pOHD
2
W2 + w~
MW = WI x w~ +
2
-. M ’A 55800 = -
‘A=—= 663 kg/m2
z~ 88.8
M ’D
‘D = — = 6610 = 1614 kg/cm2
ZD n
FQRM A.G30.014
TOKYO @ JAPAN ENGINEERING MANUALS TEM
P
the n2xt, th~ shearinq Str2sses due to torsion ~Jti, ‘B? ‘c, and
are,
= ?(?A + 2po)
‘T ‘here MTA=%B=MTC=MTD=MT ‘“
=@x (17.8+2x22)
2
= 4625 kg.cm
,
~
lF~ = $ d3 - (d3 - 2t3)4 ]= 172 cm~
. 4525 x ——
—— 16.52 = 104 kg/cn2
1465 2
.—
M d
3
rc - ~ . _=— 4625 x 8.91
= 476 kg/cm2
~p~ 2 172 2
I
i.. M
~~=L.s = 4525 ~~ = 602 kg/cn2
lPD 2 18.6 2
(d) Ther3fozs, the resulksnt stzesses at the ground le’~el and zt each
pGsicion change in diameter Gf pole are,
FORM A-G30.0J4
m
TOKYO @ JAPAN ENGINEERING MANUALS TEM
5003E
GUi DANCE TO Electrical WCRK DESIG21
a PAGE so OF 57
= 1~~6 ~ 1
1 1 8 62 + 4 X (282)2 = 1249 kg/cn2
2 :
1
1 =— ‘C *+ -
/.c 2
T
1~00 + 4 X (476) 2 = 1355 kg/cm2
——
2 + 47D2
JuD
.
(2)
Therefore, it is OK.
IE the above,
K: 3 X 107 kg/rn4
c.
u. 0.001 tangient of allowable tilting an~le of the sup&wrtea
Gbject .
F09M A-G30.OIA
6. CC&! MUNICATiGN SYSTEM
—
FDRM A-G30.014
9
TOKYO @ JAPAN EPJGINEERING M A N U A L S TEM
P
T- EMIxz~RIw ~ 5003E
GUIDANCE TO ELECTRICAL WOK< DESIGN
ISSUED ,sEP.25’831 PAGE 52 OF 57
I
(c) Self-stafid tyge main distribution frame s>all be distant from wall,
column, or other appara2us/equipment by 0.9 m or nore, at its
devics-mounting surface.
(d) Rectifier apparatus shall be, alike to the case of abov~ (c),
.. distznt by 0.8 m or nor=, at the front.
(f) Trunk line attendant board shall be in a room separated from the
room of automatic private branch exchangez and the forner and
lattsr room shall be adjacent each other, or adjacent as far as
possible. ..
(b) Gf16erqxound wiring for t~leshofie sh~.11 be distant from L.V. or E.V.
cable by 30 cm or more, from extra E.V. eable_by -60 cm or more, and
water or gas piping by 15 cm or more (if parallel, 30 cn or rnor2).
— (Den-Gi Article 148)
(d) PVC indoor-use wire shall be used for wiring between indoor
terminal box and trunk line terninal board (rosette). Howevert
outdoor-use wire shall preferably be used in moisty places.
FCPM A.C30.0!4
TOKYO g JAPAN ENGINEERIFJG M A N U A L S TEM
/
5003E
GUI DWCE TO ELECTRIC.W WOR:< DESIGN
.. - F,AGE 53 OF 57
(e) When wiring between terminal box and tsle?hone outlzk is laid in
conduit, the number of boxes which the w-irs passes through shall be
3 or less and, the distance between box~s shall be 20 m or less, so
that th2 insertion of wire can be easily done. Rowever, the
distznce shall bs 25 m or less, if the canduit route is in the same
horizontal plane, and 8 m oz less if the conduit rout2 is vertical.
(f) When tzlephone cable is lai~ in ths pipe, one pipe shall be used
for one run of cable, in principle.
(1) The slave clock shall be one in one room, in principle, but may be 2
or more in ore room, in case of larg= room, the number depending u~on
the diameter of dial plate and the distznce of personnel’s vision.
FORM A-G30.014
9
TOKYO @ JADAN ENGINEERING MANUALS TEM
/
Tm EmIxzzRr,w C- 5003E
GUIDANCE TO ELECTRICAL WORK DESIGN
ISSUED SEP.26’88 PAGE 5 4 0F57
Nc . of handsets 10 20 50 - 100
No. of louds~eakers 10 25 25 - 150
I
(b) The control part and amplifier part are, if they ar? of small size,
containe~ together in a desk-top ty?e case, and, if they are of
medium or large siz~, contained-in separate cubicles. In eithei
czse, they shall preferably be installed in the instrument room.
(c) The power su~gly eq3ipmect shall com?rise battery charger and
battsry, in order that th2 system caa be used even when power
service is interrupted.
FORM A.G30,014
m
TOKYO @ JAPAN ENGINEERING MANUALS TEM
5003E
GUI DLVCE TO ELECTRICAL WCR% DESIGN
- PAGE 55 0F57
L
‘==
where,
(e) Eandssts
(g) In pIaCSS wherz e:c~os~~ wirin~ parts are liable to suffer external
. damage Or wher2 t~?~ wirizg is to be concealed, the wiring s~al~ he
contsincd in conduits, etc. In this CZSZ, insertion of wir2 mixed
with other wiring in the same conduits shall be avoitied. However t
this ne2d not apply if both of th2s2 circuits are of low-energy
c’~rrsnt of less than 60 V. Moreover, heat-resist~nt wire shall be
use< in a bcil<iz~ desiccated as an object Of fir?-prevention.
(FiYe Defense Law)
F OR M A.G30.014
m
m
TOKYO @ JAPAN ENGINEERING MANUALS TEM
)
b E.WINZZRIW cm. 5003E
. GUI D>.NCE TO ELECTRICAL WOF.K DZSIGFJ
\ ISSUEG IszP.2E 188 PA.GZ 56 Ci57
(1) Detectors
(a)
out~oor use a~d CLass 2 snd 3 for indoor use. -.
(b) Tlher~ s.nail not be any ~~jec~ ~rcuz~ thz Contrcl Fan-cl, which can
.
a5struct the operation of th~ ccntrol par.sl.
(Cabinet Order on Fizz Defense Article 24)
(5) W;ring
(c) ~~A e wirin3 sh~ll not be inse=ted mixed with other wiring into the
same tubs, duct, Full box, etc. (Ordinanc2 on Fire Defense ArticIe.
25)
FORM A-C30.014
TOKYO @ JA?APi ENGINEERING MANUALS TEM
)
5003E
GUI D3JJCE TO ELECTRICAL WORK DZSIGN
PAGE 57 0F57
This cabls is that ussd for connecting between the television camera
SK6 the controller. This comnrises 19 cores including 2 cores of
coaxial ca~le.
i
‘L’7.is cable is that used for connecting betwesn the c~ntroller and the
video-switch. This com~zisss 16 cores.
[
I